SINAMICS G120 Frequency converters with the Control Units CU230P-2 HVAC CU230P-2 DP CU230P-2 CAN Operating instructions · 01 2011 SINAMICS Answers for industry.
Frequency inverters with Control Units ___________________ Change history CU230P-2 HVAC, SINAMICS SINAMICS G120 Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN Operating Instructions 1 ___________________ Introduction 2 ___________________ Description ___________________ 3 Installing 4 ___________________ Commissioning 5 ___________________ Adapting the terminal strip ___________________ 6 Configuring the fieldbus ___________________ 7 Functions ___________________ 8 Se
Legal information Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
Change history Important changes with respect to the manual Edition 07/2010 New functions in firmware V4.
Change history Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 4 Operating Instructions, 01/2011, FW 4.
Table of contents Change history .......................................................................................................................................... 3 1 2 3 4 Introduction.............................................................................................................................................. 11 1.1 About this manual ........................................................................................................................11 1.
Table of contents 5 6 4.3.1 Wiring examples for the factory settings ..................................................................................... 61 4.4 4.4.1 4.4.2 4.4.3 4.4.4 Commissioning with the BOP-2 .................................................................................................. 63 Menu structure ............................................................................................................................ 64 Freely selecting and changing parameters .....
Table of contents 7 6.2.2.6 6.2.2.7 6.2.2.8 6.2.2.9 6.2.3 6.2.3.1 6.2.3.2 6.2.3.3 6.2.3.4 6.2.3.5 6.2.3.6 6.2.4 6.2.4.1 6.2.4.2 6.2.4.3 USS read request ......................................................................................................................128 USS write job .............................................................................................................................129 USS process data channel (PZD).............................................................
Table of contents 7.5.2 Ramp-function generator .......................................................................................................... 203 7.6 7.6.1 7.6.1.1 7.6.1.2 7.6.1.3 7.6.2 7.6.2.1 7.6.2.2 7.6.2.3 Motor control ............................................................................................................................. 204 V/f control .................................................................................................................................
Table of contents 8 9 10 A Service and maintenance ...................................................................................................................... 281 8.1 Overview of replacing converter components............................................................................281 8.2 Replacing the Control Unit .........................................................................................................282 8.2 Replacing the Power Module ...............................
Table of contents Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 10 Operating Instructions, 01/2011, FW 4.
Introduction 1.1 1 About this manual Who requires the operating instructions and what for? These operating instructions primarily address fitters, commissioning engineers and machine operators. The operating instructions describe the devices and device components and enable the target groups being addressed to install, connect-up, parameterize, and commission the inverters safely and in the correct manner.
Introduction 1.2 Guide through this manual 1.
Introduction 1.3 Adapting inverter to application 1.3 Adapting inverter to application 1.3.1 General basics Inverters are used to improve and extend the starting and speed response of motors. Adapting the inverter to the drive task The inverter must match the motor that it is controlling and the drive task to be able to optimally operate and protect the motor.
Introduction 1.4 Frequently required parameters 1.
Introduction 1.
Introduction 1.5 Extended scope for adaptation 1.5 Extended scope for adaptation 1.5.1 BICO technology: basic principles Principle of operation of BICO technology Open/closed-loop control functions, communication functions as well as diagnostic and operator functions are implemented in the inverter. Every function comprises one or several BICO blocks that are interconnected with one another.
Introduction 1.5 Extended scope for adaptation Definition of BICO technology BICO technology represents a type of parameterization that can be used to disconnect all internal signal interconnections between BICO blocks or establish new connections. This is realized using Binectors and Connectors. Hence the name BICO technology. ( Binector Connector Technology) BICO parameters You can use the BICO parameters to define the sources of the input signals of a block.
Introduction 1.5 Extended scope for adaptation What sources of information do you need to help you set parameters using BICO technology? ● This manual is sufficient for simple signal interconnections, e.g. assigning a different significance to the to digital inputs. ● The parameter list in the List Manual is sufficient for signal interconnections that go beyond just simple ones. ● You can also refer to the function diagrams in the List Manual for complex signal interconnections. 1.5.
Introduction 1.
Introduction 1.5 Extended scope for adaptation Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 20 Operating Instructions, 01/2011, FW 4.
2 Description 2.1 Modularity of the converter system Thanks to their modular design, the converters can be used in a wide range of applications with respect to functionality and power. The following overview describes the converter components, which you require for your application. Main components of the converter Each SINAMICS G120 converter comprises a Control Unit and Power Module.
Description 2.
Description 2.1 Modularity of the converter system Component or tool Order number Drive ES Basic To commission the frequency converter via the PROFIBUS interface.
Description 2.2 Control Units 2.2 Control Units The CU230P 2 Control Units have integrated technology functions for pumps, fans and compressor applications. The I/O interfaces, the fieldbus interface and the specific software functions optimally support these applications. The integration of technological functions is a significant differentiating feature to the other Control Units of the SINAMICS G120 drive family.
Description 2.3 Power Module 2.3 Power Module Power Modules are available in various degrees of protection with a different topology in the power range from between 0.37 kW up to 250 kW. The Power Modules are sub-divided into various frame sizes (FS). Power Modules with degree of protection IP20: PM240, PM250, PM260 Frame size FSA FSB FSC FSD FSE FSF FSGX PM240, 3AC 400V - power units with integrated braking chopper1) Power range (LO) in kW line filter, Class A 0.37 … 1.5 2.2 … 4 7.
Description 2.4 Reactors and filters PM230 Power Module, IP55 degree of protection / UL Type 12 Frame size FSA FSB FSC FSD FSE FSF PM230, 3AC 400V - power units with low line reactions Power range (LO) in kW 0,37 … 3 4 … 7,5 11 … 18.5 22 … 30 37 … 45 55 … 90 line filter, Class A ● ● ● ● ● ● line filter, class B ● ● ● ● ● ● 2.
3 Installing 3.1 Procedure for installing the frequency inverter Preconditions for installation Check that the following preconditions are fulfilled before installing: ● Are the required components, tools and small parts available? ● Are the ambient conditions permissible? See Technical data (Page 303).
Installing 3.2 Installing reactors and filters 3.2 Installing reactors and filters Fitting inverter system components in space-saving manner Many inverter system components are designed as base components, that is, the component is mounted on the baseplate and the inverter mounted above it to save space. Up to two base components can be mounted above one another.
Installing 3.2 Installing reactors and filters PM250 Line Line filter supply Power Module Line supply Output reactor or sine-wave filter Power Modules Line filter to the motor Basic layout of a PM250 Power Module with class Basic layout of a PM250 Power Module with a B line filter as a base component class B line filter as a base component and output reactor or sine-wave filter Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN Operating Instructions, 01/2011, FW 4.
Installing 3.3 Installing Power Module 3.3 Installing Power Module Installing Power Modules with degree of protection IP20 ● Install the Power Module vertically on a mounting plate in a control cabinet. The smaller frame sizes of the converter (FSA and FSB) can also be mounted on DIN rails using an adapter. ● When installing, observe the minimum clearances to other components in the control cabinet. These minimum clearances are necessary to ensure adequate cooling of the converter.
Installing 3.3 Installing Power Module 3.3.1 Dimensions, hole drilling templates, minimum clearances, tightening torques Note For Power Modules up to 132 kW, degree of protection IP20, the CU230P-2 increases the total inverter depth by 50 mm - and an additional 30 mm if you use an IOP.
Installing 3.
Installing 3.
Installing 3.
Installing 3.3 Installing Power Module 3.3.
Installing 3.3 Installing Power Module 3.3.3 Connecting the line supply and motor Preconditions Once the inverter has been properly installed, the line and motor connections can now be established. The following warning information must be observed here. WARNING Line and motor connections The inverter must be grounded on the line supply and motor side. If the inverter is not correctly grounded, this can lead to extremely hazardous conditions which, under certain circumstances, can result in death.
Installing 3.3 Installing Power Module Note Electrical protective equipment Ensure that the appropriate circuit breakers / fuses for the inverter's rated current are fitted between the line and inverter (see catalog D11.1).
Installing 3.3 Installing Power Module Connecting the inverter Motor connection ● If available, open the terminal covers of the inverter. ● Connect the motor to terminals U2, V2 and W2. Carefully observe the regulations for EMC-compliant wiring: EMC-compliant connection (Page 39) EMC-compliant installation for devices with degree of protection IP55 / UL Type 12 (Page 42) ● Connect the protective conductor of the motor to the terminal The following cable lengths are permissible: of the inverter.
Installing 3.3 Installing Power Module 3.3.4 EMC-compliant connection The inverters are designed for operation in industrial environments where high values of electromagnetic interference are expected. Safe, reliable and disturbance-free operation is only guaranteed if the devices are professionally installed. Inverters with degree of protection IP20 must be installed and operated in an enclosed control cabinet.
Installing 3.3 Installing Power Module ● Signal and data cables and the associated equipotential bonding cables must always be routed in parallel with the smallest possible clearance between them ● Shielded motor cables must be used ● The shielded motor cable should be routed separately away from the cables to the motor temperature sensors (PTC/KTY) ● Signal and data cables must be shielded.
Installing 3.3 Installing Power Module EMC-compliant installation of Power Modules in degree of protection IP20 The EMC-compliant installation of power modules is shown in the following diagram using two examples.
Installing 3.3 Installing Power Module 3.3.5 Shielding with shield plate: Shield connection kits are available for all Power Module frame sizes (you will find more information in Catalog D11.1). The cable shields must be connected to the shield plate through the greatest possible surface area using shield clamps. Shielding without shield plate: EMC-compliant shielding can also be implemented without an optional shield plate.
Installing 3.3 Installing Power Module EMC-compliant installation of the inverter The EMC-compliant installation of the PM230 Power Module and Control Unit is shown in the following diagram.
Installing 3.4 Installing Control Unit 3.4 Installing Control Unit Installing the Control Unit on an IP20 Power Module Plugging on the CU Removing the CU To gain access to the terminal strips, open the top and bottom front doors to the right. The terminal strips use spring-loaded terminals. Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 44 Operating Instructions, 01/2011, FW 4.
Installing 3.4 Installing Control Unit IP55 Power Modules Figure 3-8 DQG 3OXJJLQJ RQ WKH &8 5HPRYH &8 IRU )6$ WR )6& IRU )6' WR )6) WKH XQODWFKLQJ EXWWRQ LV DFFHVVLEOH IURP WKH WRS Locate the CU on the PM You will find a detailed description in the associated Hardware Installation Manual. Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN Operating Instructions, 01/2011, FW 4.
Installing 3.4 Installing Control Unit 3.4.
Installing 3.4 Installing Control Unit 3.4.
Installing 3.4 Installing Control Unit 3.4.3 Selecting the interface assignments The inverter offers multiple predefined settings for its interfaces. One of these predefined settings matches your particular application Proceed as follows: 1. Wire the inverter corresponding to your application. 2. Carry-out the basic commissioning, see Section Commissioning (Page 53). In the basic commissioning, select the macro (the predefined settings of the interfaces) that matches your particular wiring. 3.
Installing 3.
Installing 3.4 Installing Control Unit Two- or three-wire control Macro 12 is the factory setting for the converter equipped with the Control Units CU230P-2 HVAC and CU230P-2 CAN.
Installing 3.4 Installing Control Unit Communication with a higher-level control via CANopen 0DFUR )LHOGEXV &$1RSHQ S %DXG UDWH ', ', ', ', ', ', $, $, )DXOW '2 $ODUP '2 $FNQRZOHGJH 6SHHG 9 9 &XUUHQW 9 9 $2 $2 &$1RSHQ N%DXG 3.4.4 Wiring terminal strips Solid or flexible cables are permitted as signal lines.
Installing 3.4 Installing Control Unit Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 52 Operating Instructions, 01/2011, FW 4.
4 Commissioning You must commission the inverter after installation has been completed. To do this, using Section "Preparing for commissioning (Page 56)" you must clarify whether the motor can be operated with the inverter factory settings or an additional adaptation of the inverter is required. The two commissioning options are shown in the following diagram.
Commissioning NOTICE For the basic commissioning, you determine the function of the interfaces for your inverter via predefined settings (p0015). If you subsequently select a different predefined setting for the function of the interfaces, then all BICO interconnections that you changed will be lost. Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 54 Operating Instructions, 01/2011, FW 4.
Commissioning 4.1 Restoring the factory setting 4.1 Restoring the factory setting There are cases where something goes wrong when commissioning a drive system e.g.: ● The line voltage was interrupted during commissioning and you were not able to complete commissioning. ● You got confused when setting the parameters and you can no longer understand the individual settings that you made.
Commissioning 4.2 Preparing for commissioning 4.
Commissioning 4.2 Preparing for commissioning NOTICE Information about installation The rating plate data that you enter must correspond to the connection type of the motor (star connection [Y]/delta connection [Δ]), i.e. for a delta motor connection, the delta rating plate data must be entered.
Commissioning 4.2 Preparing for commissioning 4.2.1 Inverter factory setting Factory settings of additional important parameters Parameter Factory setting Meaning of the factory setting Name of the parameter and comments p0010 0 Ready to be entered Drive, commissioning parameter filter p0100 0 Europe [50 Hz] IEC/NEMA motor standard • IEC, Europe • NEMA, North America Note: This parameter cannot cannot be changed in FW4.3.
Commissioning 4.2 Preparing for commissioning 4.2.2 Defining requirements for the application What type of control is needed for the application? [P1300] A distinction is made between V/f open-loop control and vector closed-loop control. ● The V/f open-loop control is the simplest operating mode for an inverter. For example, it is used for applications involving pumps, fans or motors with belt drives.
Commissioning 4.3 Commissioning with factory settings 4.3 Commissioning with factory settings Prerequisites for using the factory settings In simple applications, commissioning can be carried out just using the factory settings. Check which factory settings can be used and which functions need to be changed. During this check you will probably find that the factory settings only require slight adjustment: 1.
Commissioning 4.3 Commissioning with factory settings 4.3.1 Wiring examples for the factory settings Many applications function using the factory settings The following wiring can be used for Control Units which receive their commands and setpoints via control terminals (CU230P-2 HVAC and CU230P-2 CAN) to use the factory setting.
Commissioning 4.
Commissioning 4.4 Commissioning with the BOP-2 4.4 Commissioning with the BOP-2 The "Basic Operator Panel-2" (BOP-2) is an operation and display instrument of the converter. For commissioning, it is directly plugged onto the converter Control Unit.
Commissioning 4.4 Commissioning with the BOP-2 4.4.1 Menu structure 021,725 OK ESC &21752/ OK ESC ',$*126 OK ESC 63 6(732,17 $&.1 $// 92/7 287 -2* )$8/76 '& /1.
Commissioning 4.4 Commissioning with the BOP-2 4.4.2 Freely selecting and changing parameters Use BOP-2 to change your inverter settings, by selecting the appropriate parameter number and changing the parameter value. Parameter values can be changed in the "PARAMS" menu and the "SETUP" menu.
Commissioning 4.4 Commissioning with the BOP-2 4.4.3 Basic commissioning Menu Remark 6(783 ESC Set all of the parameters of the menu "SETUP". In the BOP-2, select the menu "SETUP". OK 5(6(7 OK &75/ 02' OK S (85 86$ S Select the motor control mode.
Commissioning 4.4 Commissioning with the BOP-2 Identifying motor data If you select the MOT ID (p1900) during basic commissioning, alarm A07991 will be issued once basic commissioning has been completed. To enable the converter to identify the data for the connected motor, you must switch on the motor (e.g. via the BOP-2). The converter switches off the motor after the motor data identification has been completed.
Commissioning 4.5 Commissioning with STARTER 4.5 Commissioning with STARTER Preconditions You require the following to commission the converter using STARTER: ● A pre-installed drive (motor and converter) ● A computer with Windows XP, Vista or Windows 7, which is connected to the converter via the USB cable and on which STARTER V4.2 or higher has been installed. You can find updates for STARTER in the Internet under: Update or download path for STARTER (http://support.automation.siemens.
Commissioning 4.5 Commissioning with STARTER 4.5.1 Adapting the USB interface Switch on the converter supply voltage and start the STARTER commissioning software. If you are using STARTER for the first time, you must check whether the USB interface is correctly set. To do this, click in STARTER on (accessible participants). Case 1 shows the procedure if no settings are required. In case 2, a description is provided on how you can adapt the interface.
Commissioning 4.5 Commissioning with STARTER 4.5.2 Generating a STARTER project Creating a STARTER project using project wizards • Using "Project / New with wizard" create a new project. • To start the wizard, click on "Search online for drive units ...". • The wizard guides you through all of the settings that you need for your project. 4.5.3 Go online and perform the basic commissioning Going online • ① Select your project and go online: .
Commissioning 4.5 Commissioning with STARTER Wizard for basic commissioning The wizard guides you step-by-step through the basic commissioning. • In the first step of the wizard, select the control mode. If you are not certain which control mode you require for your particular application, then select U/f control for the time being. Help on how to select the control mode is provided in Chapter Motor control (Page 204).
Commissioning 4.5 Commissioning with STARTER • In the next step, we recommend the setting "Calculate motor data only". • ① In the next step, set the check mark for "RAM to ROM (save data in drive)" in order to save your data in the converter so that it is not lost when the power fails. • ② If you exit the wizard, the converter outputs alarm A07791. You must now switch-on the motor to start motor data identification.
Commissioning 4.5 Commissioning with STARTER • ① Open by double-clicking on the control panel in STARTER. • ② Fetch the master control for the converter • ③ Set the "Enable signals" • ④ Switch on the motor. The converter now starts to identify the motor data. This measurement can take several minutes. After the measurement the converter switches off the motor. • Relinquish the master control after the motor data identification.
Commissioning 4.5 Commissioning with STARTER 4.5.4 Making additional settings After the basic commissioning, you can adapt the inverter to your application as described in the Commissioning (Page 53). STARTER offers two options: 1. Change the settings using the appropriate screen forms - our recommendation. ① Navigation bar: For each inverter function, select the corresponding screen form. ② tabs: Switch between screen forms.
Commissioning 4.5 Commissioning with STARTER 4.5.5 Trace function for optimizing the drive Description The trace function is used for converter diagnostics and helps to optimize the behavior of the drive. Start the function in the navigation bar using "... Control_Unit/Commissioning/Device trace". In two settings that are independent of one another, using you can interconnect eight signals each.
Commissioning 4.5 Commissioning with STARTER Trigger You can create your own start condition (trigger) for the trace. With the factory setting button (Start Trace). Using the (default setting) the trace starts as soon as you press the button , you can define another trigger to start the measurement. Using pretrigger, set the time for the recording before the trigger is set. As a consequence, the trigger condition traces itself.
Commissioning 4.5 Commissioning with STARTER Display options In this area, you can set how the measurement results are displayed. ● Repeat measurement: This means that you place the measurements, which you wish to perform at different times, one above one another ● Arrange curves in tracks This means that you define as to whether all measured values are to be displayed with a common zero line – or whether each measured value is displayed with its own zero line.
Commissioning 4.6 Data backup and standard commissioning 4.6 Data backup and standard commissioning External data backup After commissioning, your settings are saved in the inverter so that they are protected against power failure. Further, we recommend that you externally save the parameter settings so that in the case of a defect, you can simply replace the Power Module or Control Unit (see also Overview of replacing converter components (Page 281)).
Commissioning 4.6 Data backup and standard commissioning 4.6.
Commissioning 4.6 Data backup and standard commissioning If you wish to transfer the parameter setting from the inverter on to a memory card (Upload), you have two options: Automatic upload 6,1$0,&6 &8 30 6,1$0,&6 1. Insert an empty memory card into the inverter. 2. Then switch-on the inverter power supply again. After it has been switched-on, the inverter copies the modified parameters to the memory card 6,1$0,&6 The inverter power supply has been switched off.
Commissioning 4.6 Data backup and standard commissioning 4.6.1.2 Transferring the setting from the memory card If you wish to transfer the parameter setting from a memory card into the inverter (download), you have two options: Automatic download 1. Insert the memory card into the inverter. 2. Then switch-on the inverter power supply. 6,1$0,&6 The inverter power supply has been switched off.
Commissioning 4.6 Data backup and standard commissioning 4.6.1.3 Safely remove the memory card CAUTION The file system on the memory card can be destroyed if the memory card is removed while the inverter is switched on without first requesting and confirming this using the "safe removal" function. The memory card will then no longer function. Procedure with STARTER or BOP-2: 1. Set p9400 to 2. 2. Check the value of parameter p9400. If it is permissible to remove the memory card, p9400 is set to 3. 3.
Commissioning 4.6 Data backup and standard commissioning 4.6.2 Backing up and transferring settings using STARTER Backing up the inverter settings on PC/PG (upload) 1. Go online with STARTER: . 2. Click on the button "Load project to PG": 3. To save data in the PG (computer), click on . . Transferring settings from the PC/PG into the inverter (download) 1. Go online with STARTER. 2. Click on the button "Load project to target system": . 3.
Commissioning 4.6 Data backup and standard commissioning Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 84 Operating Instructions, 01/2011, FW 4.
5 Adapting the terminal strip 5.1 Preconditions Before you adapt the inputs and outputs of the inverter, you should have completed the basic commissioning, see Chapter Commissioning (Page 53) . In the basic commissioning, select an assignment of the inverter interfaces from several predefined configurations, see Section Preparing for commissioning (Page 56).
Adapting the terminal strip 5.2 Digital inputs 5.2 Digital inputs Digital input terminals Changing the function of the digital input Interconnect the status parameter of the digital input with a binector input of your choice. BI: pxxxx ', ', ', ', ', ', r0722.0 r0722.1 r0722.2 r0722.3 r0722.4 r0722.5 Table 5- 1 Binector inputs are designated with "BI" in the parameter list of the List Manual.
Adapting the terminal strip 5.2 Digital inputs Advanced settings You can debounce the digital input signal using parameter p0724. For more information, see the parameter list and the function block diagrams 2220 ff of the List Manual. Analog inputs as digital inputs When required, you can use the analog inputs as additional digital inputs. Terminals of the additional digital inputs $, $, $, $, ', ', BI: pxxxx r0722.
Adapting the terminal strip 5.3 Digital outputs 5.3 Digital outputs Digital output terminals Changing the function of the digital output p0730 BO: ryyxx.n p0731 p0732 '2 1& '2 12 '2 &20 Interconnect the digital output with a binector output of your choice. Binector outputs are designated with "BO" in the parameter list of the List Manual.
Adapting the terminal strip 5.4 Analog inputs 5.4 Analog inputs Analog input terminals $, $, $, $, $, *1' $, *1' , 8 Changing the function of the analog input p0756[0] CI: pyyyy r0755[0] , 8 p0756[1] r0755[1] , 7(03 p0756[2] 1. Define the analog input type using parameter p0756 and the switch on the inverter (e.g. voltage input -10 V … 10 V or current input 4 mA … 20 mA). 2. Interconnect parameter p0755 with a connector input of your choice (e.g.
Adapting the terminal strip 5.4 Analog inputs In addition, you must also set the switch belonging to the analog input. You will find , 8 • the DIP switch for AI0 and AI1 (current / voltage) on the Control Unit behind the lower front door. $, 7HPS , • the DIP switch for AI2 (temperature / current) on the Control Unit behind the upper front door. $, $, If you change the analog input type using p0756, then the inverter automatically selects the appropriate scaling of the analog input.
Adapting the terminal strip 5.4 Analog inputs You must define your own characteristic if none of the default types match your particular application. Example The inverter should convert a 6 mA … 12 mA signal into the value range -100 % … 100 % via analog input 0. The wire break monitoring of the inverter should respond when 6 mA is fallen below. Parameter Description p0756[0] = 3 Analog input type Define analog input 0 as current input with wire break monitoring.
Adapting the terminal strip 5.4 Analog inputs Define the significance of the analog input You define the analog input function by interconnecting a connector input of your choice with parameter p0755. Parameter p0755 is assigned to the particular analog input via its index, e.g. parameter p0755[0] is assigned to analog input 0.
Adapting the terminal strip 5.5 Analog outputs 5.5 Analog outputs Analog output terminals Changing the function of the analog output p0776[0] p0771[0] $2 *1' CO: rxxyy p0776[1] p0771[1] $2 *1' 1. Define the analog output type using parameter p0776 (e.g. voltage output -10 V … 10 V or current output 4 mA … 20 mA). 2. Interconnect parameter p0771 with a connector output of your choice (e.g. the actual speed).
Adapting the terminal strip 5.5 Analog outputs Parameters p0777 … p0780 are assigned to an analog output via their index, e.g. parameters p0777[0] … p0770[0] belong to analog output 0. Table 5- 8 Parameters for the scaling characteristic Parameter Description p0777 X coordinate of the 1st characteristic point [% of P200x] P200x are the parameters of the reference variables, e.g. P2000 is the reference speed.
Adapting the terminal strip 5.5 Analog outputs Defining the analog output function You define the analog output function by interconnecting parameter p0771 with a connector output of your choice. Parameter p0771 is assigned to the particular analog input via its index, e.g. parameter p0771[0] is assigned to analog output 0.
Adapting the terminal strip 5.5 Analog outputs Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 96 Operating Instructions, 01/2011, FW 4.
6 Configuring the fieldbus Before you connect the inverter to the field bus, you should have completed the basic commissioning, see Chapter Commissioning (Page 53) Fieldbus interfaces of the Control Units The Control Units are available in different versions for communication with higher-level controls with the subsequently listed fieldbus interfaces: Fieldbus Profile Control Unit Interface PROFIBUS DP (Page 98) PROFIdrive PROFIsafe CU230P-2 DP SUB D socket USS (Page 119) - CU230P-2 HVAC RS485
Configuring the fieldbus 6.1 Communication via PROFIBUS 6.1 Communication via PROFIBUS Permissible cable lengths, routing and shielding the PROFIBUS cable Information can be found in the Internet (http://www.automation.siemens.com/net/html_76/support/printkatalog.htm).
Configuring the fieldbus 6.1 Communication via PROFIBUS 6.1.2 Setting the address You can set the inverter's PROFIBUS address using either DIP switches on the Control Unit or parameter p0918. Valid PROFIBUS addresses: 1 … 125 Invalid PROFIBUS addresses: 0, 126, 127 If you have specified a valid address using DIP switches, this address will always be the one that takes effect and p0918 cannot be changed. If you set all DIP switches to "OFF" (0) or "ON" (1), then p0918 defines the address.
Configuring the fieldbus 6.1 Communication via PROFIBUS 6.1.3 Basic settings for communication Table 6- 1 The most important parameters Parameter Description p0015 Macro drive device Select the I/O configuration via PROFIBUS DP (e.g.
Configuring the fieldbus 6.1 Communication via PROFIBUS 6.1.4 Cyclic communication The PROFIdrive profile defines different telegram types. Telegrams contain the data for cyclic communication with a defined meaning and sequence. The inverter has the telegram types listed in the table below.
Configuring the fieldbus 6.1 Communication via PROFIBUS Table 6- 5 Telegram status in the inverter Process data item Control ⇒ inverter Status of the received word Bits 0…15 in the received word Defining the word to be sent Status of the sent word PZD01 r2050[0] r2090.0 … r2090.15 p2051[0] r2053[0] PZD02 r2050[1] r2091.0 … r2091.15 p2051[1] r2053[1] PZD03 r2050[2] r2092.0 … r2092.15 p2051[2] r2053[2] Inverter ⇒ control PZD04 r2050[3] r2093.0 … r2093.
Configuring the fieldbus 6.1 Communication via PROFIBUS Control word 1 (STW1) Control word 1 (bits 0 … 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11 … 15 specific to inverter). Table 6- 6 Bit Value Control word 1 and interconnection with parameters in the inverter Significance Telegram 20 0 Comments P No. p0840[0] = r2090.0 All other telegrams 0 OFF1 Motor brakes with the ramp-down time p1121 at standstill (f < fmin) the motor is switched off.
Configuring the fieldbus 6.1 Communication via PROFIBUS Status word 1 (ZSW1) Status word 1 (bits 0 to 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11 to 15 for SINAMICS G120 only). Table 6- 7 Bit Value Status word 1 and interconnection with parameters in the inverter Significance Telegram 20 Comments P No. All other telegrams 0 1 Ready for switching on Power supply switched on; electronics initialized; pulses locked. p2080[0] = r0899.
Configuring the fieldbus 6.1 Communication via PROFIBUS 6.1.4.2 Control and status word 3 The control and status words fulfill the specifications of PROFIdrive profile version 4.1 for "speed control" mode. Control word 3 (STW3) Control word 3 has the following default assignment. You can change the assignment with BICO technology. Table 6- 8 Bit Value Control word 3 and interconnection with parameters in the converter Meaning Comments BICO interconnection Selects up to 16 different fixed setpoints.
Configuring the fieldbus 6.1 Communication via PROFIBUS Status word 3 (ZSW3) Status word 3 has the following standard assignment. You can change the assignment with BICO technology. Table 6- 9 Status word 3 and interconnection with parameters in the converter Bit Value Meaning Description P No.
Configuring the fieldbus 6.1 Communication via PROFIBUS 6.1.4.3 Data structure of the parameter channel Parameter channel You can write and read parameter values via the parameter channel, e.g. in order to monitor process data. The parameter channel always comprises four words. $EEUHYLDWLRQV 3DUDPHWHU FKDQQHO 3.( 3:( ,1' VW QG UG DQG WK ZRUG ZRUG ZRUG Figure 6-1 3.
Configuring the fieldbus 6.
Configuring the fieldbus 6.1 Communication via PROFIBUS If the response identifier is 7 (request cannot be processed), one of the error numbers listed in the following table will be saved in parameter value 2 (PWE2). Table 6- 12 Error numbers for the response "Request cannot be processed" No.
Configuring the fieldbus 6.1 Communication via PROFIBUS Parameter index (IND) 3DUDPHWHU FKDQQHO 3.( VW ZRUG 3:( UG DQG WK ZRUG ,1' QG ZRUG 6XELQGH[ ,1' Figure 6-3 3DJH LQGH[ Structure of the parameter index (IND) ● For indexed parameters, select the index of the parameter by transferring the appropriate value between 0 and 254 to the subindex within a job. ● The page index is used to switch over the parameter numbers.
Configuring the fieldbus 6.
Configuring the fieldbus 6.1 Communication via PROFIBUS 6.1.4.4 Slave-to-slave communication With "Slave-slave communication" ( also called "Data Exchange Broadcast") it is possible to quickly exchange data between inverters (slaves) without the master being directly involved, for instance to use the actual value of one inverter as setpoint for other inverters.
Configuring the fieldbus 6.1 Communication via PROFIBUS 6.1.5 Acyclic communication As from performance level DP-V1, PROFIBUS communications offer acyclic data communications apart from cyclic communications. You can parameterize and troubleshoot (diagnostics) the inverter via acyclic data transfer. Acyclic data is transferred in parallel with cyclic data transfer but with a lower priority.
Configuring the fieldbus 6.1 Communication via PROFIBUS Table 6- 16 Converter response to a read request Data block Byte n Bytes n + 1 n Header Reference (identical to a read request) 01 hex: Converter has executed the read request. 81 hex: Converter was not able to completely execute the read request.
Configuring the fieldbus 6.1 Communication via PROFIBUS Changing parameter values Table 6- 17 Request to change parameters Data block Byte n Bytes n + 1 n Header Reference 01 hex ... FF hex 02 hex: Change request 0 01 hex Number of parameters (m) 01 hex ... 27 hex 2 Number of indices 4 Address, parameter 1 10 hex: Parameter value 00 hex ... EA hex (00 hex and 01 hex have the same significance) Parameter number 0001 hex ... FFFF hex 6 Number of the 1st index 0001 hex ...
Configuring the fieldbus 6.
Configuring the fieldbus 6.
Configuring the fieldbus 6.2 Communication via RS485 6.2 Communication via RS485 6.2.1 Integrating inverters into a bus system via the RS485 interface Connecting to a network via RS485 Connect the inverter to your fieldbus via the RS485 interface. Position and assignment of the RS485 interface can be found in section Interfaces, connectors, switches, control terminals, LEDs on the CU (Page 46). This connector has short-circuit proof, isolated pins.
Configuring the fieldbus 6.2 Communication via RS485 6.2.2 Communication via USS Using the USS protocol (protocol of the universal serial interface), users can set up a serial data connection between a higher-level master system and several slave systems (RS 485 interface). Master systems include programmable logic controllers (e.g. SIMATIC S7-200) or PCs. The inverters are always slaves on the bus system.
Configuring the fieldbus 6.2 Communication via RS485 6.2.2.
Configuring the fieldbus 6.2 Communication via RS485 Description Telegrams with both a variable and fixed length can be used. This can be selected using parameters p2022 and p2023 to define the length of the PZD and the PKW within the net data. STX 1 byte LGE 1 byte ADR 1 byte Net data (example) PKW 8 bytes (4 words: PKE + IND + PWE1 + PWE2) PZD 4 bytes (2 words: PZD1 + PZD2) BCC 1 byte Start delay The start delay must be maintained before a new master telegram is started.
Configuring the fieldbus 6.2 Communication via RS485 ADR The ADR range contains the address of the slave node (e.g. of the inverter). The individual bits in the address byte are addressed as follows: 7 6 Special telegram 5 4 3 Broadcast Mirror bit telegram 1 2 0 5 Address bits ● Bit 5 broadcast bit Bit 5 = 0: normal data exchange. Bit 5 = 1: Address (bits 0 … 4) is not evaluated (is not supported in SINAMICS G120!). ● Bit 6 mirror telegram Bit 6 = 0: normal data exchange.
Configuring the fieldbus 6.2 Communication via RS485 The length for the parameter channel is determined by parameter p2023 and the length for the process data is specified by parameter p2022. If the parameter channel or the PZD is not required, the appropriate parameters can be set to zero ("PKW only" or "PZD only"). It is not possible to transfer "PKW only" and "PZD only" alternatively. If both channels are required, they must be transferred together. 6.2.2.
Configuring the fieldbus 6.2 Communication via RS485 The following table includes the request ID for telegrams between the master → inverter.
Configuring the fieldbus 6.2 Communication via RS485 If the response ID = 7, then the inverter sends one of the error numbers listed in the following table in parameter value 2 (PWE2). Table 6- 23 Error numbers for the response "Request cannot be processed" No.
Configuring the fieldbus 6.2 Communication via RS485 Parameter index (IND) 3DUDPHWHU FKDQQHO 3.( VW ZRUG 3:( UG DQG WK ZRUG ,1' QG ZRUG 3DJH LQGH[ Figure 6-8 6XELQGH[ ,1' Structure of the parameter index (IND) ● For indexed parameters, select the index of the parameter by transferring the appropriate value between 0 and 254 to the subindex within a job. ● The page index is used to switch over the parameter numbers.
Configuring the fieldbus 6.2 Communication via RS485 Parameter value (PWE) You can vary the number of PWEs using parameter p2023. Parameter channel with fixed length Parameter channel with variable length P2023 = 4 P2023 = 127 A parameter channel with fixed length should contain 4 words as this setting is sufficient for all parameters (including double words). For a variable length of parameter channel, the master will only send the number of PWEs necessary for the task in the parameter channel.
Configuring the fieldbus 6.2 Communication via RS485 6.2.2.6 USS read request Example: Reading out alarm messages from the inverter. The parameter channel comprises four words (p2023 = 4).
Configuring the fieldbus 6.2 Communication via RS485 6.2.2.7 USS write job Example: Define digital input 2 as source for ON/OFF in CDS1 In this case, parameter p0840[1] (source, ON/OFF) must be assigned the value 722.2 (digital input 2). The parameter channel comprises four words (p2023 = 4).
Configuring the fieldbus 6.2 Communication via RS485 6.2.2.8 USS process data channel (PZD) Description Process data (PZD) is exchanged between the master and slave in this telegram range. Depending on the direction of transfer, the process data channel contains request data for the slave or response data to the master. The request contains control words and setpoints for the slaves, while the response contains status words and actual values for the master.
Configuring the fieldbus 6.2 Communication via RS485 The telegram runtime is longer than just purely adding all of the character runtimes (=residual runtime). You must also take into consideration the character delay time between the individual characters of the telegram.
Configuring the fieldbus 6.2 Communication via RS485 Telegram monitoring of the master With your USS master, we recommend that the following times are monitored: • Response delay: Response time of the slave to a request from the master The response delay must be < 20 ms, but longer than the start delay • Telegram runtime: Transmission time of the response telegram sent from the slave Telegram monitoring of the converter The converter monitors the time between two requests of the master.
Configuring the fieldbus 6.2 Communication via RS485 6.2.3 Communication over Modbus RTU Overview of communication using Modbus The Modbus protocol is a communication protocol with linear topology based on a master/slave architecture. Modbus offers three transmission modes: ● Modbus ASCII Data is transferred in ASCII code. The data can therefore be read directly by humans, however, the data throughput is lower in comparison to RTU.
Configuring the fieldbus 6.2 Communication via RS485 6.2.3.1 Setting the address You can set the inverter's Modbus RTU address using either DIP switches on the Control Unit or parameter p2021. Valid Modbus RTU addresses: 1 … 247 Invalid Modbus RTU addresses: 0 If you have specified a valid address using DIP switches, this address will always be the one that takes effect and p2021 cannot be changed. If you set all DIP switches to "OFF" (0) or "ON" (1), then p2021 defines the address.
Configuring the fieldbus 6.2 Communication via RS485 6.2.3.3 Modbus RTU telegram Description For Modbus, there is precisely one master and up to 247 slaves. Communication is always triggered by the master. The slaves can only transfer data at the request of the master. Slave-to-slave communication is not possible. The Control Unit always operates as slave. The following figure shows the structure of a Modbus RTU telegram.
Configuring the fieldbus 6.2 Communication via RS485 6.2.3.4 Baud rates and mapping tables Permissible baud rates and telegram delay The Modbus RTU telegram requires a pause for the following cases: ● Start detection ● Between the individual frames ● End detection Minimum duration: Processing time for 3.5 bytes (can be set via p2024[2]). A character delay time is also permitted between the individual bytes of a frame. Maximum duration: Processing time for 1.5 bytes (can be set via p2024[1]).
Configuring the fieldbus 6.2 Communication via RS485 The valid holding register addressing range extends from 40001 to 40522. Access to other holding registers generates the fault "Exception Code". The registers 40100 to 40111 are described as process data. A telegram monitoring time can be activated in p2040 for these registers. Note R"; "W"; "R/W" in the column Modbus access stands for read (with FC03); write (with FC06); read/write. Table 6- 30 Modbus Reg. No.
Configuring the fieldbus 6.2 Communication via RS485 Modbus Reg. No. Description Modbus access Unit Scaling factor On/Off text Data / parameter or value range Converter identification 40300 Powerstack number R -- 1 40301 Converter firmware R -- 0.0001 0 … 32767 r0200 0.00 … 327.67 r0018 Converter data 40320 Rated power of the power unit R kW 100 0 … 327.67 r0206 40321 Current Limit R/W % 10 10.0 … 400.0 p0640 40322 Rampup time R/W s 100 0.00 … 650.
Configuring the fieldbus 6.2 Communication via RS485 Modbus Reg. No. Description Modbus access Unit Scaling factor On/Off text Data / parameter or value range Technology controller adjustment 40510 Time constant for actual value filter of the technology controller R/W -- 100 0.00 … 60.0 p2265 40511 Scaling factor for actual value of the technology controller R/W % 100 0.00 … 500.00 p2269 40512 Proportional amplification of the technology controller R/W -- 1000 0.000 … 65.
Configuring the fieldbus 6.2 Communication via RS485 Table 6- 31 Structure of a read request for slave number 17 Example 11 03 00 6D 00 02 xx xx h h h h h h h h Byte 0 1 2 3 4 5 6 7 Description Slave address Function code Register start address "High" (register 40110) Register start address "Low" No.
Configuring the fieldbus 6.2 Communication via RS485 Table 6- 33 Structure of a write request for slave number 17 Example 11 06 00 63 55 66 xx xx h h h h h h h h Byte 0 1 2 3 4 5 6 7 Description Slave address Function code Register start address "High" (write register 40100) Register start address "Low" Register data "High" Register data "Low" CRC "Low" CRC "High" The response returns the register address (bytes 2 and 3) and the value (bytes 4 and 5) that was written to the register.
Configuring the fieldbus 6.2 Communication via RS485 Logical error If the slave detects a logical error within a request, it responds to the master with an "exception response". In the response, the highest bit in the function code is set to 1. If the slave receives, for example, an unsupported function code from the master, the slave responds with an "exception response" with code 01 (Illegal function code).
Configuring the fieldbus 6.2 Communication via RS485 6.2.4 Communication via BACnet MS/TP BACnet properties In BACnet, components and systems are considered to be black boxes which contain a number of objects. BACnet objects only define behavior outside the device, internal functions are not determined by BACnet. Each component is represented by a series of object types and their instances. Each BACnet device has precisely one BACnet device object.
Configuring the fieldbus 6.2 Communication via RS485 6.2.4.1 Setting the address You can define the MAC ID of the inverter using DIP switches on the Control Unit or using p2021. Valid BACnet addressing range: 1 … 127 If you specify the address using the DIP switch, then this address is always effective and p2021 cannot be changed. If you want to specify the address using p2021, we recommend setting all the DIP switches to "OFF" (0).
Configuring the fieldbus 6.2 Communication via RS485 P no. Parameter name p2026 Setting of the COV_Increment (COV = Change of values) 0 … 4194303.000, factory setting = 0.100 COV_Increment: Value change of the "Present Value" of an object instance where an UnConfirmedCOVNotification or ConfirmedCOVNotification should be transferred from the server.
Configuring the fieldbus 6.
Configuring the fieldbus 6.
Configuring the fieldbus 6.2 Communication via RS485 Table 6- 40 Binary input objects Instance ID Object name Description Possible values Text active / text inactive Access type Parameter BI0 DI0 ACT State of DI 0 ON/OFF ON/OFF R r0722.0 BI1 DI1 ACT State of DI 1 ON/OFF ON/OFF R r0722.1 BI2 DI2 ACT State of DI 2 ON/OFF ON/OFF R r0722.2 BI3 DI3 ACT State of DI 3 ON/OFF ON/OFF R r0722.3 BI4 DI4 ACT State of DI 4 ON/OFF ON/OFF R r0722.
Configuring the fieldbus 6.2 Communication via RS485 Instance ID Object name Description Possible values Text active Text Access inactive type Parameter BV8 AT SETPOINT Setpoint reached YES/NO YES NO R r0052.8 BV9 AT MAX FREQ Maximum speed reached YES/NO YES NO R r0052.10 BV10 DRIVE READY Inverter ready YES/NO YES NO R r0052.
Configuring the fieldbus 6.2 Communication via RS485 Table 6- 44 Analog value objects Instance ID Object name Description Unit Area Access Parameter type AV0 OUTPUT FREQ_Hz Output frequency (Hz) Hz -327.68 … 327.67 R r0024 AV1 OUTPUT FREQ_PCT Output frequency (%) % -100.0 … 100.0 R HIW AV2 OUTPUT SPEED Motor speed RPM -16250 … 16250 R r0022 AV3 DC BUS VOLT DC link voltage.
Configuring the fieldbus 6.2 Communication via RS485 Instance ID Object name Description Unit Area Access Parameter type AV34 CUR LIM Current limit A 0.00 … 10000.
Configuring the fieldbus 6.3 Communication over CANopen 6.3 Communication over CANopen Connecting an inverter to a CAN bus Connect the inverter to the fieldbus via the 9-pin SUB-D pin connector. The connections of this pin connector are short-circuit proof and isolated. If the inverter forms the first or last slave in the CANopen network, then you must switch-in the bus terminating resistor.
Configuring the fieldbus 6.3 Communication over CANopen 6.3.1 CANopen functionality of the converter CANopen is a CAN-based communication protocol with linear topology that operates on the basis of communication objects (COB).
Configuring the fieldbus 6.3 Communication over CANopen 6.3.2 Commissioning CANopen 6.3.2.1 Setting the node ID and baud rate In the converter you must set the node ID and the baud rate to permit communication. CAUTION Changes made to the node ID or baud rate only become effective after switching off and on again. It is particularly important that any external 24 V supply is switched off. Note that before turning off, you must save the changes using RAM -> ROM ( ).
Configuring the fieldbus 6.3 Communication over CANopen 6.3.2.2 Monitoring the communication and response of the inverter The communication monitoring can be used via both node guarding and heartbeat protocol (heartbeat producer). Node guarding The master sends monitoring queries to the slaves via the node guarding protocol. If the converter does not receive a Node Guarding protocol within the Life Time, then it outputs fault (F08700). Life Time = Guard time (p8601.0) * Life Time Factor (p8604.
Configuring the fieldbus 6.3 Communication over CANopen 6.3.2.3 SDO services You can access the object directory of the connected drive unit using the SDO services. An SDO connection is a peer-to-peer coupling between an SDO client and a server. The drive unit with its object directory is an SDO server. The identifiers for the SDO channel of a drive unit are defined according to CANopen as follows.
Configuring the fieldbus 6.3 Communication over CANopen Structure of the SDO protocols The SDO services use the appropriate protocol depending on the task. The basic structure is shown below: Header information n user data Byte 0 Byte 1 und 2 Byte 3 Byte 4 ...
Configuring the fieldbus 6.3 Communication over CANopen SDO abort codes Table 6- 45 SDO abort codes Abort code Description 0503 0000h Toggle bit not alternated. Toggle bit has not changed 0504 0000h SDO protocol timed out. Timeout for SDO protocol 0504 0001h Client/server command specifier not valid or unknown. Client/server command not valid or unknown 0504 0005h Out of memory. Memory overflow 0601 0000h Unsupported access to an object.
Configuring the fieldbus 6.3 Communication over CANopen 0607 0012h Data type does not match, length of service parameter too high. Data type is not correct, service parameter is too long 0607 0013h Data type does not match, length of service parameter too low. Data type is not correct, service parameter is too short 0609 0011h Subindex does not exist Subindex does not exist 0609 0030h Value range of parameter exceeded (only for write access).
Configuring the fieldbus 6.3 Communication over CANopen Not all of the parameters can be directly addressed via this range. This is the reason that in CAN, an inverter parameter always comprises two parameters from the inverter; these are the offset specified using parameter p8630[2] and the parameter itself.
Configuring the fieldbus 6.3 Communication over CANopen 6.3.2.5 PDO and PDO services Process data objects (PDO) For CANopen, (real-time) transfer of process data is realized using "Process Data Objects" (PDO). There are send and receive PDO. With the G120 inverter, eight send PDO (TPDO) and eight receive PDO (RPDO) are transferred. A PDO is defined by the PDO communication parameter and the PDO mapping parameter. The PDO must be linked with the objects of the object dictionary which contain process data.
Configuring the fieldbus 6.3 Communication over CANopen The structure of this communication and mapping parameter is listed in the following tables.
Configuring the fieldbus 6.3 Communication over CANopen Synchronous data transmission In order for the devices on the CANopen bus to remain synchronized during transmission, a synchronization object (SYNC object) must be transmitted at periodic intervals. Each PDO that is transferred as a synchronous object must be assigned a transmission type 1 ... n. The following is applicable: ● Transmission type 1: the PDO is transferred in every SYNC cycle.
Configuring the fieldbus 6.3 Communication over CANopen PDO services The PDO services can be subdivided as follows: ● Write PDO ● Read PDO ● SYNC service Write PDO The "Write PDO" service is based on the "push" model. The PDO has exactly one producer. There can be no consumer, one consumer, or multiple consumers. Via Write PDO, the producer of the PDO sends the data of the mapped application object to the individual consumer. Read PDO The "Read PDO" service is based on the "pull" model.
Configuring the fieldbus 6.3 Communication over CANopen 6.3.2.6 Predefined connection set When integrating the converter via the predefined connection set, the converter is interconnected so that the motor can be switched-on via the control and a setpoint can be entered without having to make any additional settings or requiring CANopen know-how. The converter returns the status word and the speed actual value to the control. In the factory, the converter is set to free PDO mapping.
Configuring the fieldbus 6.3 Communication over CANopen 6.3.2.7 Free PDO mapping Using the free PDO mapping, you can interconnect additional process data from the object directory corresponding to the requirements of your particular system for the PDO service. In the factory, the converter is set to free PDO mapping. If your converter has been changed over to the Predefined Connection Set, you must change over to free PDO mapping, see Section PDO and PDO services (Page 161).
Configuring the fieldbus 6.3 Communication over CANopen 6.3.3 Other CANopen functions 6.3.3.1 Network management (NMT service) Network management (NMT) is node-oriented and has a master-slave topology. The NMT services can be used to initialize, start, monitor, reset, or stop nodes. Two data bytes follow each NMT service. All NMT services have the COB ID = 0. This cannot be changed.
Configuring the fieldbus 6.3 Communication over CANopen The NMT recognizes the following transitional states: ● Start Remote Node: command for switching from the "Pre-Operational" communication status to "Operational". The drive can only transmit and receive process data (PDO) in "Operational" status. ● Stop Remote Node command for switching from "Pre-Operational" or "Operational" to "Stopped". The node can only process NMT commands in the "Stopped" status.
Configuring the fieldbus 6.
Configuring the fieldbus 6.3 Communication over CANopen 6.3.4 Object directories RPDO configuration objects The following tables list the communication and mapping parameters together with the indices for the individual RPDO configuration objects. The configuration objects are established via SDO.
Configuring the fieldbus 6.3 Communication over CANopen OD Index (hex) SubIndex (hex) 1407 SINAMICS parameters Data type Predefined connection set Can be read/ written to Unsigned8 2 R Receive PDO 8 communication parameter 0 Largest subindex supported 1 COB ID used by PDO p8707.0 Unsigned32 8000 06DF hex R/W 2 Transmission type p8707.
Configuring the fieldbus 6.3 Communication over CANopen OD Index (hex) SubIndex (hex) 1603 Name of the object SINAMICS parameters Data type Predefined connection set Can be read/ written to Unsigned8 0 R Receive PDO 4 mapping parameter 0 Number of mapped application objects in PDO 1 PDO mapping for the first application object to be mapped p8713.0 Unsigned32 0 R/W 2 PDO mapping for the second application object to p8713.
Configuring the fieldbus 6.3 Communication over CANopen OD Index (hex) SubIndex (hex) 1607 Name of the object SINAMICS parameters Data type Predefined connection set Can be read/ written to Unsigned8 0 R Receive PDO 8 mapping parameter 0 Number of mapped application objects in PDO 1 PDO mapping for the first application object to be mapped p8717.0 Unsigned32 0 R/W 2 PDO mapping for the second application object to p8717.
Configuring the fieldbus 6.3 Communication over CANopen OD Index (hex) SubIndex (hex) 1803 Object name SINAMICS parameters Data type Predefined connection set Can be read/ written to Unsigned8 5 R Transmit PDO 4 communication parameter 0 Largest subindex supported 1 COB ID used by PDO p8723.0 Unsigned32 C000 06DF hex R/W 2 Transmission type p8723.1 Unsigned8 FE hex R/W 3 Inhibit time p8723.2 Unsigned16 0 R/W 4 Reserved p8723.3 Unsigned8 --- R/W 5 Event timer p8723.
Configuring the fieldbus 6.3 Communication over CANopen Table 6- 52 OD Index (hex) TPDO configuration objects - mapping parameters SubIndex (hex) 1A00 Object name Predefined connection set Can be read/ written to Unsigned8 1 R SINAMICS Data type parameters Transmit PDO 1 mapping parameter 0 Number of mapped application objects in PDO 1 PDO mapping for the first application object to be mapped p8730.
Configuring the fieldbus 6.3 Communication over CANopen OD Index (hex) SubIndex (hex) 1A04 Object name Predefined connection set Can be read/ written to Unsigned8 0 R SINAMICS Data type parameters Transmit PDO 5 mapping parameter 0 Number of mapped application objects in PDO 1 PDO mapping for the first application object to be mapped p8734.0 Unsigned32 0 R/W 2 PDO mapping for the second application object to be mapped p8734.
Configuring the fieldbus 6.3 Communication over CANopen 6.3.4.1 Free objects You can interconnect any process data objects of the received and transmit buffer using receive and transmit double words.
Configuring the fieldbus 6.3 Communication over CANopen 6.3.4.2 Objects in drive profile DSP402 The following table lists the object directory with the index of the individual objects for the drives.
Configuring the fieldbus 6.3 Communication over CANopen 6.3.5 Configuration example The following example describes how you can integrate the converter into a CANopen bus system using STARTER in two steps. In the first step, the converter is integrated into the communication via the CAN bus using the Predefined Connection Set. In this case, the control word, the speed setpoint as well the status word and speed actual value are transferred.
Configuring the fieldbus 6.3 Communication over CANopen Integrate the current actual value and torque limit into the communication via the free PDO mapping In order to integrate the current actual value and torque limit into the communication, you must switch over from the Predefined Connection Set to the free PDO mapping. The current actual value and torque limit are integrated as free objects. In the example, the actual current value is transferred in TPDO1 and the torque limit in RPDO1, i.e.
Configuring the fieldbus 6.3 Communication over CANopen 4.
Configuring the fieldbus 6.3 Communication over CANopen Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 182 Operating Instructions, 01/2011, FW 4.
7 Functions Before you set the inverter functions, you should have completed the following commissioning steps: ● Commissioning (Page 53) ● If necessary: Adapting the terminal strip (Page 85) ● If necessary: Configuring the fieldbus (Page 97) Overview of the inverter functions ,QWHUIDFHV 6HWSRLQW VRXUFHV $QDORJ LQSXWV )LHOGEXV )L[HG VHWSRLQWV 0RWRUL]HG SRWHQWLR PHWHU -RJ PRGH ~ 6HWSRLQW SURFHVVLQJ = 5DPS IXQFWLRQ JHQHUDWRU /LPLWDWLRQ 0RWRU FRQWURO &RPPDQG VRXUFHV ,QYHUWHU FRQWURO
Functions 7.1 Overview of the inverter functions Functions relevant to all applications Functions required in special applications only The functions that you require in your application are shown in a dark color in the function overview above. The functions whose parameters you only need to adapt when actually required are shown in white in the function overview above.
Functions 7.2 Inverter control 7.2 Inverter control If you are controlling the inverter using digital inputs, you use parameter p0015 during basic commissioning to define how the motor is switched on and off and how it is changed over from clockwise to counter-clockwise rotation. Five different methods are available for controlling the motor. Three of the five methods just require two control commands (two-wire control). The other two methods require three control commands (three-wire control).
Functions 7.2 Inverter control 7.2.1 Two-wire control: method 1 You switch the motor on and off using a control command (ON/OFF1). while the other control command reverses the motor direction of rotation. 21 2)) W 5HYHUVLQJ W 6HWSRLQW 0RWRU VSHHG &ORFNZLVH URWDWLRQ &RXQWHU FORFNZLVH URWDWLRQ W ,QYHUWHG VHWSRLQW Figure 7-2 Two-wire control, method 1 Table 7- 2 Function table 2)) 2)) ON/OFF1 Reversing 0 0 OFF1: The motor stops. 0 1 OFF1: The motor stops.
Functions 7.2 Inverter control 7.2.2 Two-wire control, method 2 You switch the motor on and off using a control command (ON/OFF1) and at the same time select clockwise motor rotation. You also use the other control command to switch the motor on and off, but in this case you select counter-clockwise rotation for the motor. The inverter only accepts a new control command when the motor is at a standstill.
Functions 7.2 Inverter control 7.2.3 Two-wire control, method 3 You switch the motor on and off using a control command (ON/OFF1) and at the same time select clockwise motor rotation. You also use the other control command to switch the motor on and off, but in this case you select counter-clockwise rotation for the motor. Unlike method 2, the inverter will accept the control commands at any time, regardless of the motor speed.
Functions 7.2 Inverter control 7.2.4 Three-wire control, method 1 With one control command, you enable the two other control commands. You switch the motor off by canceling the enable (OFF1). You switch the motor's direction of rotation to clockwise rotation with the positive edge of the second control command. If the motor is still switched off, switch it on (ON). You switch the motor's direction of rotation to counter-clockwise rotation with the positive edge of the third control command.
Functions 7.2 Inverter control 7.2.5 Three-wire control, method 2 With one control command, you enable the two other control commands. You switch the motor off by canceling the enable (OFF1). You switch on the motor with the positive edge of the second control command (ON). The third control command defines the motor's direction of rotation (reversing).
Functions 7.2 Inverter control 7.2.6 Switching over the inverter control (command data set) In several applications, the inverter must be able to be operated from different, higher-level control systems. Example: Switchover from automatic to manual operation A motor is switched on and off and its speed varied either from a central control system via a fieldbus or from a local control box.
Functions 7.2 Inverter control You select the command data set using parameter p0810. To do this, you must interconnect parameter p0810 with a control command of your choice, e.g. a digital input. &RPPDQG GDWD VHW 3DUDPHWHU ZLWK LQGH[ > @ &RQWURO ZRUG %LW 352),%86 p0840[0] r2090.0 p2103[0] r2090.7 21 2)) $FNQRZOHGJH ,QYHUWHU FRQWURO p0854[0] &RQWURO 3/& r2090.10 &'6 p1036[0] 023 GRZQ r2090.
Functions 7.2 Inverter control Advanced settings If you require more than two command data sets, then define the number of command data sets (2, 3 or 4) using parameter p0170.
Functions 7.3 Command sources 7.3 Command sources The command source is the interface via which the inverter receives its control commands. When commissioning, you define this using macro 15 (p0015). Note The "Get master control" or "Manual/Auto changeover" function can also be used to specify commands and setpoints via STARTER or the Operator Panel. Change command source If you subsequently change the command source using macro 15, then you must carry out commissioning again.
Functions 7.4 Setpoint sources 7.4 Setpoint sources The setpoint source is the interface via which the inverter receives its setpoint. The following options are available: ● Motorized potentiometer simulated in the inverter. ● Inverter analog input. ● Setpoints saved in the inverter: – Fixed setpoints – Jog ● Inverter fieldbus interface. Depending on the parameterization, the setpoint in the inverter has one of the following meanings: ● Speed setpoint for the motor. ● Torque setpoint for the motor.
Functions 7.4 Setpoint sources 7.4.2 Motorized potentiometer as setpoint source The 'motorized potentiometer' (MOP) function simulates an electromechanical potentiometer for entering setpoints. You can continuously adjust the motorized potentiometer (MOP) using the control signals "raise" and "lower". The control signals are received via the digital inputs of the inverter or from the operator panel that has been inserted. Typical applications ● Entering the speed setpoint during the commissioning phase.
Functions 7.
Functions 7.4 Setpoint sources Example of parameterization of the motorized potentiometer Table 7- 18 7.4.3 Implementing a motorized potentiometer using digital inputs Parameter Description p0015 = 9 Macro drive unit: Configure inverter on MOP as the setpoint source • The motor is switched on and off via digital input 0. • The MOP setpoint is increased via digital input 1. • The MOP setpoint is decreased via digital input 2.
Functions 7.4 Setpoint sources The various fixed setpoints can be selected in two ways: 1. Direct selection: Precisely one fixed speed setpoint is assigned to each selection signal (e.g. a digital input). As several selection signals are selected, the associated fixed speed setpoints are added together to from a total setpoint. Direct selection is particularly well suited to controlling the motor using the inverter's digital inputs. 2.
Functions 7.4 Setpoint sources Example: Selecting two fixed speed setpoints using digital input 2 and digital input 3 The motor is to run at two different speeds: ● The motor is switched on with digital input 0 ● When digital input 2 is selected, the motor is to run at a speed of 300 rpm. ● When digital input 3 is selected, the motor is to accelerate to a speed of 2000 rpm. ● When digital input 1 is selected, the motor should go into reverse Table 7- 21 7.4.
Functions 7.4 Setpoint sources Table 7- 22 Parameters for the "Jog" function Parameter Description p1055 Signal source for jogging 1 - jog bit 0 (factory setting: 0) If you wish to jog via a digital input, then set p1055 = 722.x p1056 Signal source for jogging 2 - jog bit 1 (factory setting: 0) If you wish to jog via a digital input, then set p1056 = 722.x 7.4.
Functions 7.5 Setpoint calculation 7.5 Setpoint calculation The setpoint processing modifies the speed setpoint, e.g. it limits the setpoint to a maximum and minimum value and using the ramp-function generator prevents the motor from executing speed steps. 3RVLWLYH /LPLWDWLRQ 5DPSXS WLPH 5DPS GRZQ WLPH 6SHHG VHWSRLQW IRU PRWRU FRQWURO 6SHHG VHWSRLQW IURP VHWSRLQW VRXUFH 5DPS IXQFWLRQ JHQHUDWRU QHJDWLYH /LPLWDWLRQ Figure 7-10 7.5.
Functions 7.5 Setpoint calculation 7.5.2 Ramp-function generator The ramp-function generator in the setpoint channel limits the speed of changes to the speed setpoint. The ramp-function generator does the following: ● The soft acceleration and braking of the motor reduces the stress on the mechanical system of the driven machine. ● Acceleration and braking distance of the driven machine (e.g. a conveyor belt) are independent of the motor load.
Functions 7.6 Motor control 7.6 0 Motor control For induction motors, there are two different open-loop control or closed-loop control techniques: ● Open-loop control with V/f-characteristic (V/f control) ● Field-oriented control (vector control) Criteria for selecting either V/f control or vector control V/f control is perfectly suitable for almost any application in which the speed of induction motors is to be changed.
Functions 7.
Functions 7.6 Motor control 7.6.1 V/f control V/f control sets the voltage at the motor terminals on the basis of the specified speed setpoint. The relationship between the speed setpoint and stator voltage is calculated using characteristic curves. The required output frequency is calculated on the basis of the speed setpoint and the number of pole pairs of the motor (f = n * number of pole pairs / 60, in particular: fmax = p1082 * number of pole pairs / 60).
Functions 7.6 Motor control 7.6.1.2 Additional characteristics for the V/f control In addition to linear and square-law characteristics, there are the following additional versions of the V/f control that are suitable for special applications. Linear V/f characteristic with Flux Current Control (FCC) (P1300 = 1) Voltage losses across the stator resistance are automatically compensated. This is particularly useful for small motors since they have a relatively high stator resistance.
Functions 7.6 Motor control V/f control for drives requiring a precise frequency (textile industry) (p1300 = 5), V/f control for drives requiring a precise frequency and FCC (p1300 = 6) These characteristics require the motor speed to remain constant under all circumstances. This setting has the following effects: ● When the maximum current limit is reached, the stator voltage is reduced but not the speed. ● Slip compensation is locked.
Functions 7.6 Motor control Note Only increase the voltage boost in small steps until satisfactory motor behavior is reached. Excessively high values in p1310 ... p1312 can cause the motor to overheat and switch off (trip) the inverter due to overcurrent . Table 7- 25 Optimizing the starting characteristics for a linear characteristic Parameter Description P1310 Permanent voltage boost (factory setting 50 %) The voltage boost is active from standstill up to the rated speed.
Functions 7.6 Motor control 7.6.2 Vector control 7.6.2.1 Properties of vector control Using a motor model, the vector control calculates the load and the motor slip. As a result of this calculation, the inverter controls its output voltage and frequency so that the motor speed follows the setpoint, independent of the motor load. Vector control is possible without directly measuring the motor speed. This closed-loop control is also known as sensorless vector control. 7.6.2.
Functions 7.6 Motor control 7.6.2.3 Torque control Torque control is part of the vector control and normally receives its setpoint from the speed controller output. By deactivating the speed controller and directly entering the torque setpoint, the closed-loop speed control becomes closed-loop torque control. The inverter then no longer controls the motor speed, but the torque that the motor generates.
Functions 7.7 Protection functions 7.7 Protection functions The frequency inverter offers protective functions against overtemperature and overcurrent for both the frequency inverter as well as the motor. Further, the frequency inverter protects itself against an excessively high DC link voltage when the motor is regenerating. 7.7.
Functions 7.7 Protection functions 7.7.2 Motor temperature monitoring using a temperature sensor You can use one of the following sensors to protect the motor against overtemperature: ● PTC sensor ● KTY 84 sensor ● ThermoClick sensor The motor's temperature sensor is connected to the Control Unit. Temperature measurement via PTC The PTC sensor is connected to terminals 14 and 15. ● Overtemperature: The threshold value to switch over to an alarm or fault is 1650 Ω.
Functions 7.
Functions 7.7 Protection functions 7.7.3 Protecting the motor by calculating the motor temperature The temperature calculation is only possible in the vector control mode (P1300 ≥ 20) and functions by calculating a thermal motor model.
Functions 7.7 Protection functions Settings You only have to change the factory settings of the Imax controller if the drive tends to oscillate when it reaches the current limit or it is shut down due to overcurrent. Table 7- 30 Imax controller parameters Parameter Description P0305 Rated motor current P0640 Motor current limit P1340 Proportional gain of the Imax controller for speed reduction P1341 Integral time of the Imax controller for speed reduction r0056.
Functions 7.7 Protection functions There are two different groups of parameters for the VDCmax controller, depending on whether the motor is being operated with U/f control or vector control.
Functions 7.8 Status messages 7.8 Status messages Information about the inverter state (alarms, faults, actual values) can be output via inputs and outputs and also via the communication interface. Details on evaluating the inverter state via inputs and outputs are provided in Section Adapting the terminal strip (Page 85). The evaluation of the inverter state via the communication interface is realized using the inverter status word.
Functions 7.9 Application-specific functions 7.9 Application-specific functions The inverter offers a series of functions that you can use depending on your particular application, e.g.: ● Unit changeover ● Braking functions ● Automatic restart and flying restart ● Basic process control functions ● Logical and arithmetic functions using function blocks that can be freely interconnected Please refer to the following sections for detailed descriptions.
Functions 7.9 Application-specific functions Note Restrictions for the unit changeover function • The values on the rating plate of the inverter or motor cannot be displayed as percentage values. • Using the unit changeover function a multiple times (for example, percent → physical unit 1 → physical unit 2 → percent) may lead to the original value being changed by one decimal place as a result of rounding errors.
Functions 7.9 Application-specific functions The parameters listed below are affected by the changeover. Table 7- 32 P no.
Functions 7.9 Application-specific functions 7.9.1.3 Changing over process variables for the technology controller Note We recommend that the units and reference values of the technology controller are coordinated and harmonized with one another during commissioning. Subsequent modification in the reference variable or the unit can result in incorrect calculations or displays.
Functions 7.9 Application-specific functions 7.9.1.4 Changing of the units with STARTER The converter must be in the offline mode in order to change over the units. STARTER shows whether you change settings online in the converter or change offline in the PC ( / ). You switch over the mode using the adjacent buttons in the menu bar. *R RIIOLQH GLVFRQQHFW (VWDEOLVK WKH RQOLQH FRQQHFWLRQ Procedure ● Go to the "Units" tab in the configuration screen form to change over the units.
Functions 7.9 Application-specific functions ● Go online. In this case, the converter detects that other units or process variables have been set offline than are actually in the converter; the converter displays this in the following screen form: ● Accept these settings in the converter. Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 224 Operating Instructions, 01/2011, FW 4.
Functions 7.9 Application-specific functions 7.9.2 Braking functions of the converter 7.9.2.1 Comparison of electrical braking methods Regenerative power If an induction motor electrically brakes the connected load and the mechanical power exceeds the electrical losses, then it operates as a generator. The motor converts mechanical power into electrical power.
Functions 7.9 Application-specific functions Main features of the braking functions DC braking The motor converts the regenerative power into heat.
Functions 7.9 Application-specific functions The inverter feeds the regenerative power back into the line supply. /LQH • Advantages: Constant braking torque; the regenerative power is not converted into heat, but is regenerated into the line supply; can be used in all applications; continuous regenerative operation is possible - e.g.
Functions 7.9 Application-specific functions 7.9.2.2 DC braking DC braking is used for applications without regenerative feedback into the line supply, where the motor can be more quickly braked by impressing a DC current than along a braking ramp. Typical applications for DC braking include: ● Centrifuges ● Saws ● Grinding machines ● Conveyor belts Whether DC braking or ramp-down with an OFF1 command is more effective depends on the motor properties.
Functions 7.9 Application-specific functions The following operating modes are available for DC braking.
Functions 7.9 Application-specific functions Activating DC braking independent of the speed using a control command DC braking starts independent of the motor speed, as soon as the control command for braking (e.g. via DI3: P1230 = 722.3) is issued. If the braking command is revoked, the inverter returns to normal operation and the motor accelerates to its setpoint. Note: The value of p1230 is displayed in r1239.11.
Functions 7.9 Application-specific functions DC braking parameters Table 7- 34 Parameters for configuring DC braking Parameter Description p1230 Activate DC braking (BICO parameter) The value for this parameter (0 or 1) can be either entered directly or specified by means of an interconnection with a control command.
Functions 7.9 Application-specific functions 7.9.2.3 Compound braking Compound braking is typically used for applications in which the motor is normally operated at a constant speed and is only braked down to standstill in longer time intervals, e.g.
Functions 7.9 Application-specific functions Parameterizing compound braking Table 7- 37 Parameters to enable and set compound braking Parameter Description P3856 Compound braking current (%) With the compound braking current, the magnitude of the DC current is defined, which is additionally generated when stopping the motor for operation with V/f control to increase the braking effect.
Functions 7.9 Application-specific functions 7.9.2.4 Dynamic braking Dynamic braking is typically used in applications in which dynamic motor behavior is required at different speeds or continuous direction changes, e.g.: ● Horizontal conveyors ● Vertical and inclined conveyors ● Hoisting gear Principle of operation The inverter controls the braking chopper depending on its DC link voltage. The DC link voltage increases as soon as the inverter absorbs the regenerative power when braking the motor.
Functions 7.9 Application-specific functions ● Evaluate the braking resistor's temperature monitoring (terminals T1 and T2) such that the motor is switched off when the resistor experiences overtemperature. You can do this in the following two ways: – Use a contactor to disconnect the converter from the line as soon as the temperature monitoring responds. – Connect the contact of the temperature monitoring function of the braking resistor with a free digital input of your choice on the converter.
Functions 7.9 Application-specific functions 7.9.2.5 Braking with regenerative feedback to the line Regenerative braking is typically used in applications where braking energy is generated either frequently or for longer periods of time, e.g.: ● Centrifuges ● Unwinders ● Cranes and hoisting gear Pre-requisite for regenerative braking is the Power Module PM250 or PM260.
Functions 7.9 Application-specific functions 7.9.3 Automatic restart and flying restart 7.9.3.1 Flying restart – switching on while the motor is running If you switch on the motor while it is still running, then with a high degree of probability, a fault will occur due to overcurrent (overcurrent fault F07801). Examples of applications involving an unintentionally rotating motor directly before switching on: ● The motor rotates after a brief line interruption. ● A flow of air turns the fan impeller.
Functions 7.9 Application-specific functions Table 7- 40 Advanced settings Parameter Description P1201 Flying restart enable signal source (factory setting: 1) Defines a control command, e.g. a digital input, through which the flying restart function is enabled. P1202 Flying restart search current (Factory setting for Power Module PM230: 90 %.
Functions 7.9 Application-specific functions 7.9.3.2 Automatic switch-on The automatic restart includes two different functions: 1. The inverter automatically acknowledges faults. 2. After a fault occurs or after a power failure, the inverter automatically switches-on the motor again. This automatic restart function is primarily used in applications where the motor is controlled locally via the inverter's inputs.
Functions 7.9 Application-specific functions ● Set the parameters of the automatic restart function. The method of operation of the parameters is explained in the following diagram and in the table.
Functions 7.
Functions 7.9 Application-specific functions Parameter Explanation p1213[0] Automatic restart monitoring time for restart (factory setting: 60 s) This parameter is only effective for the settings p1210 = 4, 6, 14, 16, 26. With this monitoring function, you limit the time in which the inverter may attempt to automatically switch-on the motor again. The monitoring function starts when a fault is identified and ends with a successful start attempt.
Functions 7.9 Application-specific functions 7.9.4 PID technology controller The technology controller permits all types of simple process controls to be implemented. You can use the technology controller for e.g. pressure controllers, level controls or flow controls.
Functions 7.9 Application-specific functions 7.9.5 Load torque monitoring (system protection) In many applications, it is advisable to monitor the motor torque: ● Applications where the load speed can be indirectly monitored by means of the load torque. For example, in fans and conveyor belts too low a torque indicates that the drive belt is torn. ● Applications that are to be protected against overload or locking (e.g. extruders or mixers).
Functions 7.9 Application-specific functions Table 7- 43 Parameterizing the monitoring functions Parameter Description No-load monitoring P2179 Current limit for no-load detection If the converter current is below this value, the message "no load" is output.
Functions 7.9 Application-specific functions 7.9.6 Load failure monitoring via digital input Using this function, the inverter monitors the load failure of the driven machine, e.g. for fans or conveyor belts.
Functions 7.9 Application-specific functions 7.9.7 Real time clock (RTC) The real time clock is the basis for time-dependent process controls, e.g.: ● To reduce the temperature of a heating control during the night ● Increase the pressure of a water supply at certain times during the day Real time clock: Format and commissioning The real time clock starts as soon as the Control Unit power supply is switched on for the first time.
Functions 7.9 Application-specific functions Accept the real time clock in the alarm and fault buffer Using the real time clock, you can track the sequence of alarms and faults over time. When an appropriate message occurs, the real time clock is converted into the UTC time format (Universal Time Coordinated): Date, time ⇒ 01.01.
Functions 7.9 Application-specific functions 7.9.8 Time switch (DTC) The "time switch" (DTC) function, along with the real time clock in the inverter, offers the option of controlling when signals are switched on and off. Examples: ● Day/night switching of a temperature control ● Switching a process control from weekday to weekend. Principle of operation of the time switch (DTC) The inverter has three independent parameterizable time switches.
Functions 7.9 Application-specific functions 7.9.9 Temperature sensing using temperature-dependent resistors Analog input AI 2 Analog input AI 2 can be used as a current input or resistance input for a temperature sensor. Both the DIP switch and parameter p0756.2 must be set accordingly for this purpose. ● P0756.2 = 2 or 3 -> options for setting as current input ● P0756.
Functions 7.9 Application-specific functions Note If a temperature sensor is used as an input for the PID controller, the scaling of the analog input must be adjusted. • Scaling example for NI1000: 0 °C (p0757) = 0 % (p0758); 100 °C (p0759) = 100 % (p0760) • Scaling example for PT1000: 0 °C (p0757) = 0 % (p0758); 100 °C (p0759) = 80 % (p0760) Please refer to the parameter list for more details.
Functions 7.9 Application-specific functions 7.9.10 Essential service mode The Essential Service Mode (ESM) function ensures that when required, the motor is operated for as long as possible so that, for example, smoke gases can be extracted or people affected by a fire can escape. Application example In order to improve air circulation in stairwells, frequently, a slight underpressure is generated using ventilation control. With this control, a fire would mean that smoke gases enter into the stairwell.
Functions 7.9 Application-specific functions You will find additional details on this in the List Manual in the function diagrams for essential service mode, setpoint channel and technology controller. When in the factory setting, if the setpoint is lost, the drive continues using the last recognized setpoint.
Functions 7.9 Application-specific functions Special features of the essential service mode ● The automatic restart function is internally activated – independent of the setting of p1210 – as soon as the essential service mode kicks in. This results in the inverter being restarted if a pulse inhibit (OFF2) occurs due to an internal fault. ● In the essential service mode, inverter shutdown due to faults is suppressed, with the exception of faults that would lead to the destruction of the inverter.
Functions 7.9 Application-specific functions Table 7- 45 Parameters that are required to set the essential service mode Parameter Description Setting the source for the essential service mode p3880 = 722.3 ESM activation (here, via DI3, high-active) Signal source for activating the essential service mode 722.x for high active, 723.
Functions 7.
Functions 7.9 Application-specific functions 7.9.11 Multi-zone control Multi-zone control is used to control quantities such as pressure or temperature via the technology setpoint deviation. The setpoints and actual values are fed in via the analog inputs as current (0 … 20 mA) or voltage (0 … 10 V) or as a percentage via temperaturedependent resistances (NI1000 / PT1000, 0 °C = 0 %; 100 °C = 100 %).
Functions 7.9 Application-specific functions Day and night switching Using a day/night changeover other setpoints can be entered for specific times. The day/night changeover control can be realized e.g. using an external signal via DI4 or using free blocks and the real time clock via p31025. Note When the multi-zone control is activated, the analog inputs are newly interconnected as sources for the setpoint and actual value of the technology controller (see table).
Functions 7.9 Application-specific functions Note Please note that when multi-zone control is activated, any BiCo interconnections present for analog inputs and for the technology controller's setpoint and actual value are cancelled and interconnected with the links defined in the factory. When you deactivate multi-zone control, the associated BiCo interconnections are cancelled. Example The temperature in a large office is measured at three points and transferred to the inverter using analog inputs.
Functions 7.9 Application-specific functions p0757.3 = 0 / p0758.3 = 0 Set lower value of the scaling characteristic p0759.3 = 100 / p0760.3 = 100 Set upper value of the scaling characteristic p31026.2 = 755.1 Temperature actual value 3 via temperature sensor with current output (0 mA … 20 mA) via analog input 1 p0756.1 = 2 Select analog input type (current input 0 … 20 mA) p0757.1 = 0 / p0758.1 = 0 Set lower value of the scaling characteristic (0 mA ≙ 0 °C) p0759.1 = 20 / p0760.
Functions 7.9 Application-specific functions 7.9.12 Cascade control The cascade control function is used in applications that require between one and four motors to be run at the same time depending on load, so that e.g. highly variable pressure ratios or flow volumes can be corrected.
Functions 7.9 Application-specific functions To avoid frequent activation/deactivation of the uncontrolled motors, a time can be specified in p2377 which must have elapsed before a further motor can be activated/deactivated. After the time set in p2377 has elapsed, a further motor will be activated immediately if the PID deviation is greater than the value set in p2376.
Functions 7.9 Application-specific functions Controlling the activation and deactivation of motors Use p2371 to determine the order of activation/deactivation for the individual external motors.
Functions 7.9 Application-specific functions Parameters to set and activate the cascade control: p0730 = r2379.0 Signal source for digital output 0 Control external motor 1 via DO 0 p0731 = r2379.1 Signal source for digital output 1 Control external motor 2 via DO 1 p0732 = r2379.
Functions 7.9 Application-specific functions 7.9.13 Bypass If the bypass is controlled by a higher-level control, the control must lock the contactors so they cannot switch on at the same time. If controlled by inverter, the digital outputs are used to activate two contactors via which the motor is powered. The inverter is provided with contactor position feedback via the digital inputs. This is evaluated. If using direct connection logic (high level = ON), both contactors should be NO contacts.
Functions 7.9 Application-specific functions When changing over to inverter operation, initially contactor K2 must be opened and after the de-excitation time, contactor K1 is closed. The inverter then captures the rotating motor and the motor is operated on the inverter. Bypass function when activating via a control signal (p1267.0 = 1) The status of the bypass contactors is evaluated when the inverter is switched on. If the automatic restart function is active (p1210 = 4) and an ON command (r0054.
Functions 7.9 Application-specific functions Bypass function is dependent on the speed (p1267.1 = 1) With this function, changeover to line operation is realized corresponding to the following diagram, if the setpoint lies above the bypass threshold. If the setpoint falls below the bypass threshold, the inverter captures the motor and the motor is fed from the inverter.
Functions 7.9 Application-specific functions General properties of the bypass function ● y ● Contactors K1 and K2 must be mutually interlocked so that they cannot close at the same time. Shutdown behavior in bypass operation ● If the motor is in the bypass mode, it cannot be shutdown with OFF 1. The motor coasts down after an OFF2 or OFF3.
Functions 7.9 Application-specific functions 7.9.14 Energy-saving mode The energy-saving mode is mainly used for pumps and fans. Typical applications include pressure and temperature controls. In the energy-saving mode, the inverter stops and starts the motor depending on the system conditions. The energy-saving mode can be activated via the technology controller (without external commands via terminals or bus interface) and via an external setpoint input.
Functions 7.9 Application-specific functions In the energy-saving mode, the motor is shut down; however, the speed setpoint and/or the technology controller deviation are/is monitored. ● For an external setpoint input (without technology controller) the speed setpoint is monitored and the motor is switched-on again as soon as the setpoint increases above the restart speed. The restart speed is calculated as follows: Restart speed = P1080 + p2390 + p2393.
Functions 7.9 Application-specific functions Energy-saving mode with setpoint input using the internal technology controller In this operating mode, the technology controller must be activated as the setpoint source (p2200) and used as the main setpoint (p2251). The function can be operated both with and without boost.
Functions 7.9 Application-specific functions Energy-saving mode with external setpoint input In this operating mode, the setpoint is specified by an external source (e.g. a temperature sensor); the technology setpoint can be used here as a supplementary setpoint.
Functions 7.9 Application-specific functions Adjustable parameters for the energy-saving mode function Table 7- 49 Main function parameters Parameter Description Via tech. setpoint Via external setpoint P1080 = … Minimum speed 0 (factory setting) … 19500 rpm. Lower limit of the motor speed is independent of the speed setpoint.
Functions 7.9 Application-specific functions Parameter Description Via tech. setpoint Via external setpoint P2393 = … Energy-saving mode restart speed (rpm), required in the case of external setpoint input. The motor starts as soon as the setpoint exceeds the restart speed.
Functions 7.9 Application-specific functions 7.9.15 Logical and arithmetic functions using function blocks Additional signal interconnections in the inverter can be established by means of free function blocks. Every digital and analog signal available via BICO technology can be routed to the appropriate inputs of the free function blocks. The outputs of the free function blocks are also interconnected to other functions using BICO technology.
Functions 7.
Functions 7.9 Application-specific functions Scaling examples ● Speed: Reference speed p2000 = 3000 rpm, actual speed 2100 rpm. As a consequence, the following applies to the scaled input quantity: 2,100 / 3,000 = 0.7. ● Temperature: Reference quantity is 100 °C. For an actual temperature of 120 °C, the input value is obtained from 120 °C / 100 °C = 1.2. Note Limits within the function blocks should be entered as scaled values.
Functions 7.9 Application-specific functions Example: AND operation An example of an AND logic operation, explained in detail, including the use of a time block is provided in the Extended scope for adaptation (Page 16)chapter. You can find additional information in the following manuals: ● Function Manual "Free Function Blocks" (http://support.automation.siemens.com/WW/view/en/35125827) ● Function Manual "Description of the Standard DCC Blocks" (http://support.automation.siemens.
Functions 7.10 Switchover between different settings 7.10 Switchover between different settings In several applications, the inverter must be able to be operated with different settings. Example: You connect different motors to one inverter. Depending on the particular motor, the inverter must operate with the associated motor data and the appropriate ramp-function generator.
Functions 7.10 Switchover between different settings Using parameter p0180 you can define the number of command data sets (2, 3 or 4).
8 Service and maintenance 8.1 Overview of replacing converter components In the event of a permanent function fault, you can replace the converter's Power Module or Control Unit independently of one another. In the following cases, you may immediately switch on the motor again after the replacement. Replacing the Power Module Replacement: Replacing the Control Unit with external backup of the settings, e.g.
Service and maintenance 8.2 Replacing the Control Unit 8.2 Replacing the Control Unit WARNING 230 V AC can be connected via the relay outputs DO 0 and DO 2 of the Control Unit. These terminals can carry 230 V AC independent of the voltage condition of the Power Module. Therefore please observe appropriate safety measures when working on the inverter. After commissioning has been completed, we recommend that you back up your settings on an external storage medium, e.g.
Service and maintenance 8.2 Replacing the Control Unit Procedure for replacing a Control Unit without a memory card ● Disconnect the line voltage of the Power Module and (if installed) the external 24 V supply or the voltage for the relay outputs DO 0 and DO 2 of the Control Unit. ● Remove the signal cables of the Control Unit. ● Remove the defective CU from the Power Module. ● Plug the new CU on to the Power Module. ● Reconnect the signal cables of the Control Unit. ● Connect up the line voltage again.
Service and maintenance 8.3 Replacing the Power Module 8.3 Replacing the Power Module Procedure for replacing a Power Module ● Disconnect the Power Module from the line supply. ● If being used, switch off the 24 V supply of the Control Unit. DANGER Risk of electrical shock! Hazardous voltage is still present for up to 5 minutes after the power supply has been switched off.
Alarms, faults and system messages 9 The converter has the following diagnostic types: ● LED The LED at the front of the converter immediately informs you about the most important converter states right at the converter. ● Alarms and faults The converter signals alarms and faults via the fieldbus, the terminal strip (when appropriately set), on a connected operator panel or STARTER. Alarms and faults have a unique number. If the converter no longer responds Due to faulty parameter settings, e.g.
Alarms, faults and system messages 9.1 Operating states indicated on LEDs 9.1 Operating states indicated on LEDs The LED RDY (Ready) is temporarily orange after the power supply voltage is switched-on. As soon as the color of the LED RDY changes to either red or green, the LEDs signal the inverter state.
Alarms, faults and system messages 9.
Alarms, faults and system messages 9.2 Alarms 9.
Alarms, faults and system messages 9.
Alarms, faults and system messages 9.2 Alarms If the alarm history is filled up to index 63, each time a new alarm is accepted in the alarm history, the oldest alarm is deleted.
Alarms, faults and system messages 9.3 Faults 9.3 Faults A fault displays a severe fault during operation of the inverter. The inverter signals a fault as follows: ● at the Operator Panel with Fxxxxx ● at the Control Unit using the red LED RDY ● in bit 3 of the status word 1 (r0052) ● via STARTER To delete a fault message, you need to remedy the cause of the fault and acknowledge the fault. Every fault has a clear fault code and also a fault value.
Alarms, faults and system messages 9.3 Faults The fault buffer can accept up to eight actual faults. The next to last fault is overwritten if an additional fault occurs after the eighth fault.
Alarms, faults and system messages 9.
Alarms, faults and system messages 9.
Alarms, faults and system messages 9.
Alarms, faults and system messages 9.4 List of alarms and faults 9.4 List of alarms and faults Axxxxx Alarm Fyyyyy: Fault Table 9- 9 Number Faults, which can only be acknowledged by switching the inverter off and on again (power on reset) Cause Remedy F01000 Software fault in CU Replace CU. F01001 Floating Point Exception Switch CU off and on again. F01015 Software fault in CU Upgrade firmware or contact technical support.
Alarms, faults and system messages 9.4 List of alarms and faults Table 9- 10 The most important alarms and faults Number Cause Remedy F01018 Power-up aborted more than once 1. Switch the module off and on again. 2. After this fault has been output, the module is booted with the factory settings. 3. Recommission the converter.
Alarms, faults and system messages 9.4 List of alarms and faults Number Cause Remedy F07011 Motor overtemperature Reduce the motor load. Check ambient temperature. Check the wiring and connection of the sensor. A07012 I2t Motor Module overtemperature Check and if necessary reduce the motor load. Check the motor's ambient temperature. Check thermal time constant p0611. Check overtemperature fault threshold p0605. A07015 Motor temperature sensor alarm Check that the sensor is connected correctly.
Alarms, faults and system messages 9.4 List of alarms and faults Number Cause Remedy F07801 Motor overcurrent Check current limits (p0640). Vector control: Check current controller (p1715, p1717). U/f control: Check the current limiting controller (p1340 … p1346). Increase acceleration ramp (p1120) or reduce load. Check motor and motor cables for short circuit and ground fault. Check motor for star-delta connection and rating plate parameterization. Check power unit / motor combination.
Alarms, faults and system messages 9.4 List of alarms and faults Number Cause Remedy A07910 Motor overtemperature Check the motor load. Check the motor's ambient temperature. Check the KTY84 sensor. Check the overtemperatures of the thermal model (p0626 ... p0628). A07920 Torque/speed too low The torque deviates from the torque/speed envelope curve. A07921 Torque/speed too high • Check the connection between the motor and the load.
Alarms, faults and system messages 9.4 List of alarms and faults Number Cause Remedy F30005 I2t converter overload Check the rated currents of the motor and Power Module. Reduce current limit p0640. When operating with U/f characteristic: Reduce p1341. F30011 Line phase failure Check the converter's input fuses. Check the motor cables. F30015 Motor cable phase failure F30021 Ground fault Check the motor cables. Increase the ramp-up or ramp-down time (p1120).
Alarms, faults and system messages 9.4 List of alarms and faults Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN 302 Operating Instructions, 01/2011, FW 4.
10 Technical data NOTICE UL-certified fuses must be used In order that the system is in compliance with UL, UL certified fuses, circuit breakers or selfprotected combination motor controllers must be used. 10.
Technical data 10.1 Technical data for CU230P-2 Feature Data / explanation Motor temperature sensor PTC: Short-circuit monitoring < 20 Ω, overtemperature 1650 Ω KTY84: Short-circuit monitoring < 50 Ω, wire-break: > 2120 Ω ThermoClick sensor with dry contact USB interface Mini 5-pole USB Memory card (optional) MMC card Recommendation: 6SL3254-0AM00-0AA0 SD card Recommendation: 6SL3254-0AM00-0AA0 Dimensions (WxHxD) 73 mm × 199 mm × 65.5 mm Weight 0.
Technical data 10.2 Technical data, Power Modules 10.2 Technical data, Power Modules Permissible converter overload There are two different power data specifications for the Power Modules: "Low Overload" (LO) and "High Overload" (HO), depending on the expected load.
Technical data 10.2 Technical data, Power Modules Definitions • LO input current 100 % of the permissible input current for a load cycle according to Low Overload (LO base load input current). • LO output current 100 % of the permissible output current for a load cycle according to Low Overload (LO base load output current). • LO power Power of the inverter for LO output current.
Technical data 10.2 Technical data, Power Modules 10.2.1 Technical data, PM230 General data, PM230 - IP55 / UL Type 12 Feature Version Line voltage 3-ph. 380 V … 480 V AC ± 10 % The actual permissible line voltage depends on the installation altitude Input frequency 47 Hz … 63 Hz Power factor λ 0.9 Starting current Smaller than the input current Permissible short-circuit current Frame size A ... C: 42 kA Frame size D ...
Technical data 10.2 Technical data, Power Modules Performance dependent data, PM230 - IP55 / UL Type 12 Table 10- 2 PM230 frame size A, 3-ph. 380 V AC… 480 V, ± 10 % Order number Filter Class A 6SL3223-0DE13-7AA0 6SL3223-0DE15-5AA0 6SL3223-0DE17-5AA0 Filter Class B 6SL3223- 0DE13-7BA0 6SL3223- 0DE15-5BA0 6SL3223- 0DE17-5BA0 Values based on Low Overload ● LO power ● LO input current ● LO output current 0.37 kW 1.3 A 1.3 A 0.55 kW 1.8 A 1.7 A 0.75 kW 2.3 A 2.
Technical data 10.2 Technical data, Power Modules Table 10- 4 PM230 frame size A, 3-ph. 380 V AC… 480 V, ± 10 % Order number Filter Class A Filter Class B 6SL3223-0DE23-0AA0 6SL3223-0DE23-0BA0 Values based on Low Overload ● LO power ● LO input current ● LO output current 3 kW 8.0 A 7.7 A Values based on High Overload ● HO power ● HO input current ● HO output current 2.2 kW 6.1 A 5.
Technical data 10.2 Technical data, Power Modules Table 10- 6 PM230 frame size C, 3-ph. 380 V AC… 480 V, ± 10 % Order number Filter Class A 6SL3223-0DE31-1AA0 6SL3223-0DE31-1BA0 6SL3223-0DE31-5AA0 6SL3223-0DE31-5BA0 6SL3223-0DE31-8AA0 6SL3223-0DE31-8BA0 Values based on Low Overload ● LO power ● LO input current ● LO output current 11 kW 26.9 A 26 A 15 kW 33.1 A 32 A 18.5 kW 39.2 A 38 A Values based on High Overload ● HO power ● HO input current ● HO output current 7.5 kW 18.6 A 18 A 11 kW 26.
Technical data 10.2 Technical data, Power Modules Table 10- 8 PM230 frame size E, 3-ph. 380 V AC… 480 V, ± 10 % Order number Filter Class A 6SL3223-0DE33-7AA0 6SL3223-0DE33-7BA0 6SL3223-0DE34-5AA0 6SL3223-0DE34-5BA0 Values based on Low Overload ● LO power ● LO input current ● LO output current 37 kW 70 A 75 A 45 kW 84 A 90 A Values based on High Overload ● HO power ● HO input current ● HO output current 30 kW 56 A 60 A 37 kW 70 A 75 A 0.99 kW 100 A 39 l/s 1.
Technical data 10.2 Technical data, Power Modules 10.2.2 Technical data, PM240 Note The given input currents are valid for operation without a line reactor for a line voltage of 400 V with Vk = 1 % referred to the rated power of the inverter. If a line reactor is used, the specified values are reduced by a few percent. General data, PM240 - IP20 Feature Version Line voltage 3-ph. 380 V … 480 V AC ± 10 % The actual permissible line voltage depends on the installation altitude.
Technical data 10.2 Technical data, Power Modules Power-dependent data, PM240 - IP20 Table 10- 10 PM240 frame size A, 3-ph. 380 V AC… 480 V, ± 10 % 6SL3224-0BE13-7UA0 6SL3224-0BE15-5UA0 6SL3224-0BE17-5UA0 Values based on Low Overload ● LO power ● LO input current ● LO output current Order number Without filter 0.37 kW 1.6 A 1.3 A 0.55 kW 2.0 A 1.7 A 0.75 kW 2.5 A 2.2 A Values based on High Overload ● HO power ● HO input current ● HO output current 0.37 kW 1.6 A 1.3 A 0.55 kW 2.0 A 1.7 A 0.
Technical data 10.2 Technical data, Power Modules Table 10- 12 PM240 frame size B, 3-ph. 380 V AC… 480 V, ± 10 % Order number with filter without filter 6SL3224-0BE22-2AA0 6SL3224-0BE23-0AA0 6SL3224-0BE24-0AA0 6SL3224-0BE22-2UA0 6SL3224-0BE23-0UA0 6SL3224-0BE24-0UA0 Values based on Low Overload ● LO power ● LO input current ● LO output current 2.2 kW 7.6 A 5.9 A 3 kW 10.2 A 7.7 A 4 kW 13.4 A 10.2 A Values based on High Overload ● HO power ● HO input current ● HO output current 2.2 kW 7.6 A 5.
Technical data 10.2 Technical data, Power Modules Table 10- 14 PM240 frame size D, 3-ph. 380 V AC… 480 V, ± 10 % Order number with filter without filter 6SL3224-0BE31-5AA0 6SL3224-0BE31-5UA0 6SL3224-0BE31-8AA0 6SL3224-0BE31-8UA0 6SL3224-0BE32-2AA0 6SL3224-0BE32-2UA0 Values based on Low Overload ● LO power ● LO input current ● LO output current 18.5 kW 46 A 38 A 22 kW 53 A 45 A 30 kW 72 A 60 A Values based on High Overload ● HO power ● HO input current ● HO output current 15 kW 40 A 32 A 18.
Technical data 10.2 Technical data, Power Modules Table 10- 16 PM240 frame size F, 3-ph.
Technical data 10.2 Technical data, Power Modules Table 10- 18 PM240 frame size GX, 3-ph. 380 V AC… 480 V, ± 10 % Order number Without filter 6SL3224-0BE41-3UA0 6SL3224-0BE41-6UA0 6SL3224-0BE42-0UA0 Values based on Low Overload ● LO power ● LO input current ● LO output current 160 kW 297 A 302 A 200 kW 354 A 370 A 250 kW 442 A 477 A Values based on High Overload ● HO power ● HO input current ● HO output current 132 kW 245 A 250 A 160 kW 297 A 302 A 200 kW 354 A 370 A 3.9 kW 355 A 360 l/s 4.
Technical data 10.2 Technical data, Power Modules 10.2.3 Technical data, PM250 General data, PM250 - IP20 Feature Version Line voltage 3-ph. 380 V … 480 V AC ± 10 % The actual permissible line voltage depends on the installation altitude Input frequency 47 Hz … 63 Hz Modulation depth 93 % (the maximum output voltage is 93 % of the input voltage) Power factor λ 0.
Technical data 10.2 Technical data, Power Modules Power-dependent data, PM250 - IP20 Table 10- 19 PM250 frame size C, 3-ph. 380 V AC… 480 V, ± 10 % 6SL3225-0BE25-5AA0 6SL3225-0BE27-5AA0 6SL3225-0BE31-1AA0 Values based on Low Overload ● LO power ● LO input current ● LO output current Order number 7.5 kW 18.0 A 18.0 A 11.0 kW 25.0 A 25.0 A 15 kW 32.0 A 32.0 A Values based on High Overload ● HO power ● HO input current ● HO output current 5.5 kW 13.2 A 13.2 A 7.5 kW 19.0 A 19.0 A 11.0 kW 26.0 A 26.
Technical data 10.2 Technical data, Power Modules Table 10- 21 PM250 frame size E, 3-ph. 380 V AC… 480 V, ± 10 % Order number 6SL3225-0BE33-0AA0 6SL3225-0BE33-7AA0 Values based on Low Overload ● LO power ● LO input current ● LO output current 37 kW 70 A 75 A 45 kW 84 A 90 A Values based on High Overload ● HO power ● HO input current ● HO output current 30.0 kW 56 A 60 A 37.0 kW 70 A 75 A 1 kW 100 A 22 l/s 1.
Technical data 10.2 Technical data, Power Modules 10.2.4 Technical data, PM260 General data, PM260 - IP20 Feature Version Line voltage 3-ph. 660 V … 690 V AC ± 10% The permissible line voltage depends on the installation altitude The power units can also be operated with a minimum voltage of 500 V –10 %. In this case, the power is linearly reduced as required. Input frequency 47 Hz … 63 Hz Power factor λ 0.
Technical data 10.2 Technical data, Power Modules Power-dependent data, PM260 - IP20 Table 10- 23 PM260 frame size D, 3-ph. 660 V AC… 690 V, ± 10% (500 V - 10%) Order number with filter without filter 6SL3225- 0BH27-5AA1 6SL3225- 0BH27-5UA1 6SL3225- 0BH31-1AA1 6SL3225- 0BH31-1UA1 6SL3225- 0BH31-5AA1 6SL3225- 0BH31-5UA1 Values based on Low Overload ● LO power ● LO input current ● LO output current 11 kW 13 A 14 A 15 kW 18 A 19 A 18.
A Appendix A.1 Application examples A.1.1 Configuring communication in STEP 7 A.1.1.1 Task Using a suitable example, the following section provides information on how you connect an inverter to a higher-level SIMATIC control via PROFIBUS. What prior knowledge is required? In this example, it is assumed that readers know now to basically use an S7 control and the STEP 7 engineering tool and is not part of this description. A.1.1.
Appendix A.1 Application examples In order to configure the communication you also require the following software packages: Table A- 2 A.1.1.3 Software components Component Type (or higher) Order no. Qty SIMATIC STEP 7 V5.3 + SP3 6ES7810-4CC07-0YA5 1 STARTER V4.2 6SL3072-0AA00-0AG0 1 Creating a STEP 7 project PROFIBUS communication between the inverter and a SIMATIC control is configured using the SIMATIC STEP 7 and HW Config software tools.
Appendix A.1 Application examples When you add the SIMATIC 300, a window is displayed in which you can define the network. ● Create a PROFIBUS DP network. Figure A-2 A.1.1.4 Inserting a SIMATIC 300 station with PROFIBUS DP network Configuring communications to a SIMATIC control The inverter can be connected to a SIMATIC control in two ways: 1. Using the inverter GSD 2.
Appendix A.1 Application examples A.1.1.5 Inserting the inverter into the STEP 7 project ● Install the GSD of the converter in STEP 7 using HW Config (menu "Options - Install GSD files"). After the GSD has been installed, the converter appears under "PROFIBUS DP - additional field devices" in the hardware catalog of HW Config. ● Drag and drop the converter into the PROFIBUS network. Enter the PROFIBUS address set at the converter in HW Config.
Appendix A.1 Application examples Note regarding the universal module It is not permissible to configure the universal module with the following properties: ● PZD length 4/4 words ● Consistent over the complete length With these properties, the universal module has the same DP identifier (4AX) as the "PKW channel 4 words" and is therefore identified as such by the higher-level control. As a consequence, the control does not establish cyclic communication with the inverter.
Appendix A.1 Application examples A.1.2 STEP 7 program examples A.1.2.1 STEP 7 program example for cyclic communication 1HWZRUN &RQWURO ZRUG DQG VHWSRLQW &RQWURO ZRUG ( KH[ 6HWSRLQW KH[ / 7 / 7 1HWZRUN 8 1HWZRUN 8 1HWZRUN / 7 / 7 1HWZRUN : ( 0: : 0: $FNQRZOHGJH IDXOW ( 0 :ULWH SURFHVV GDWD 0: 3$: 0: 3$: In this example, inputs E0.0 and E0.6 are linked to the -bit ON/OFF1 or to the "acknowledge fault" bit of STW 1.
Appendix A.1 Application examples Table A- 3 HEX BIN E 0 1 1 7 4 0 Assignment of the control bits in the inverter to the SIMATIC flags and inputs Bit in STW1 Significance Bit in MW1 Bit in MB1 Bit in MB2 Inputs 0 ON/OFF1 1 ON/OFF2 8 0 E0.
Appendix A.1 Application examples A.1.2.2 STEP 7 program example for acyclic communication 2% &\FOLF FRQWURO SURJUDP 1HWZRUN 5HDGLQJ DQG ZULWLQJ SDUDPHWHUV UHDG SDUDPHWHUV 2 8 0 81 0 2 8 81 0 0 5 0 M9.0 Starts reading parameters M9.1 Starts writing parameters M9.2 displays the read process M9.3 displays the write process The number of simultaneous requests for acyclic communication is limited. More detailed information can be found in the http://support.
Appendix A.
Appendix A.
Appendix A.
Appendix A.1 Application examples A.1.3 Configuring slave-to-slave communication in STEP 7 Two drives communicate via standard telegram 1 with the higher-level control. In addition, drive 2 receives its speed setpoint directly from drive 1 (actual speed).
Appendix A.1 Application examples ① Activate the tab "Address configuration". ② Select line 1. ③ Open the dialog box in which you define the Publisher and the address area to be transferred. ① Select DX for direct data exchange ② Select the PROFIBUS address of drive 1 (publisher). ③ In the address field, select the start address specifying the data area to be received from drive 1. In the example, these are the status word 1 (PZD1) and the speed actual value with the start address 256.
Appendix A.2 Additional information on the inverter A.2 Additional information on the inverter A.2.1 Manuals for your inverter Table A- 6 Manuals for your converter Depth of the information Manual Contents Languages Download or order number + Getting Started Control Units CU230P-2; CU240B-2; CU240E-2 Installing the converter and commissioning.
Appendix A.2 Additional information on the inverter Table A- 7 Support when configuring and selecting the converter Manual or tool Contents Languages Download or order number Catalog D 11.1 Ordering data and technical information for the standard SINAMICS G converters English, German, Italian, French, Spanish Everything about SINAMICS G120 (www.siemens.
Appendix A.3 Mistakes and improvements A.3 Mistakes and improvements If you come across any mistakes when reading this manual or if you have any suggestions for how it can be improved, then please send your suggestions to the following address or by E-mail: Siemens AG Drive Technologies Motion Control Systems Postfach 3180 91050 Erlangen, Germany E-mail (mailto:documentation.standard.drives@siemens.
Index 8 87 Hz characteristic, 37 Regenerative, 236 Braking chopper, 234 Braking method, 227 Braking resistor, 234 Break loose torque, 15 Bus fault, 286 Bypass, 24, 265 A Acyclic data transfer, 113 Additional technology controller 0, 222 Additional technology controller 1, 222 Additional technology controller 2, 222 Adjustable parameters, 13 Alarm, 248, 285, 288 Alarm buffer, 248, 288 Alarm code, 288 Alarm history, 289 Alarm time, 248, 288 Alarm value, 288 Ambient temperature, 57, 215 Analog input, 47 Fun
Index Configuring support, 337 Configuring the fieldbus, 48 Configuring the interfaces, 48 Configuring the terminal strip, 48 Connectors, 16 Control Data Set, CDS, 191 Control mode, 15, 59 Control Units, 21 Control word, 102, 105 Control word 1, 103 Control word 3, 105 Controlling the motor, 185 Conveyor belt, 228 Conveyor systems, 71 Correction manual, 338 Counterclockwise, 185 Crane, 225, 236 D Data backup, 81, 83 Data exchange fieldbus, 97 Data set 47, 113, 332 Data transfer, 81, 83 Date, 247 DC brakin
Index H Hardware configuration, 324 Hardware Installation Manual, 336 Hoisting gear, 204, 225, 234, 236 Horizontal conveyor, 232 Horizontal conveyors, 204, 234 Hotline, 337 HW Config, 324 HW Config (hardware configuration), 324 I I2t monitoring, 212 Identifying motor data, 66, 72, 210, 211 Imax controller, 215 Inclined conveyors, 204, 225, 234 IND, 110, 126 Industry Mall, 337 Installation, 336 Interfaces, 22 Interlock, 18 Inverter control, 184 J Overview, 336 Maximum current controller, 215 Maximum spee
Index P Runtime group, 275 Page index, 110, 126 Parameter channel, 107, 123 IND, 110, 126 PKE, 107, 123 PWE, 110, 127 Parameter identifier, 107, 123 Parameter index, 110, 126 Parameter Manual, 336 parameter number Offset of, 110, 126 Parameter types, 13 PC Connection Kit, 22 PDO, 153 PID controller, 243 PKE, 107, 123 PKW (parameter, ID, value), 101 PLC functionality, 18 Power failure, 239 Power Module, 21, 25 Technical data, 312, 318, 321 Power on reset, 285 Pressure control, 243 Process industry, 49 Pro
Index T Z Technical data Power Module, 312, 318, 321 Technology controller, 105, 243 Telegram 20, 49 Telegram types, 101, 326 Temperature calculation, 215 Temperature measurement via KTY, 213 Temperature measurement via PTC, 213 Temperature monitoring, 212, 215 Temperature monitoring via ThermoClick, 213 Temperature sensor, 47 ThermoClick temperature sensor, 213 Three-wire control, 50, 185 Time, 249 Time control, 249 Time slices, 275 Time switch, 249 Torque monitoring Speed-dependent, 244, 245 TPDO, 159
Siemens AG Industry Sector Drive Technologies Motion Control Systems Postfach 3180 91050 ERLANGEN GERMANY We reserve the right to make technical changes. © Siemens AG 2011 www.siemens.