1.4 Frequently required parameters
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
14 Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
1.4 Frequently required parameters
Parameters that in many cases help
Table 1- 1 How to switch to commissioning mode or restore the factory setting
Parameter Description
p0010 Commissioning parameters
0: Ready (factory setting)
1: Carry out basic commissioning
3: Perform motor commissioning
5: Technological applications and units
15: Define number of data records
30: Factory setting - initiate restore factory settings
Table 1- 2 How to determine the firmware version of the Control Unit
Parameter Description
r0018 The firmware version is displayed:
Table 1- 3 How to select the command and setpoint sources for the inverter
Parameter Description
p0015 Additional information is available in the section Selecting the interface assignments (Page 48).
Table 1- 4 This is how you parameterize the up and down ramps
Parameter Description
p1080 Minimum speed
0.00 [rpm] factory setting
p1082 Maximum speed
1500.000 [rpm] factory setting
p1120 Rampup time
10.00 [s]
p1121 Rampdown time
10.00 [s]