Technical data

CU230P-2 Control Units, Getting Started
26 A5E02484096, 05/2009
Commissioning step Type 1 2
Setting values for the fixed frequencies
In order to enter a setpoint via the fixed frequencies, you must now assign digital inputs DI3, DI4
and DI5 to frequencies. You can switch-in the fixed frequencies either individually or together (the
values are added).
To set the fixed frequencies, go the menu by selecting "Menu / Parameter / Search by number" to
select individual parameters. There, select parameter p1001 (enter 01001). Select the parameter
with OK, with an additional OK, change into the value level and enter the required value using the
navigation wheel and confirm this with OK. Select and change parameters p1002 and 1003 one
after the other (factory setting = 0). After making the setting, press the ESC key until you reach the
status display. The value in p1001 is the fixed frequency for DI3, p1002 for DI4, p1003 for DI5.
Selection X
If you did not select motor data identification, then commissioning has now been completed and
you can start the motor by issuing an ON command.
If you have selected a variant of the motor data identification, then this is started with the next ON
command. In this case, commissioning has been completed after the motor data identification.
Information X X
Note
If you do not make an entry for longer than 60 seconds, the IOP exits the Commissioning Wizards and returns to the status
display with the settings that you have made.
4.4 Restoring the factory settings using the IOP
The inverter is reset to the delivery condition by restoring the parameters to the factory setting.
Note
The reset operation is not applied to parameters p0014, p0100, p0201, p0205 or the communication parameters. Motor
parameters p0300 ... p0311 are suitably preassigned for the power unit.
Reset is selected using the navigation wheel on the IOP via "Menus/Parameters/Restore drives to factory setting" and then
started by pressing "OK".
After the reset, the display first jumps into the parameter window from where the reset was started. You can return to the
status display by pressing the "ESC" key twice.
4.5 Additional setting options for the inputs and outputs
Adapting the functions of the input and output terminals
The functions of the individual terminals can be adapted using interconnection and adjustable parameters. The number
ranges for the individual inputs and outputs are subsequently listed. In the IOP, you can call the individual parameters via
"Menu/Parameter/Search by number" and then you will obtain information texts by pressing the "INFO" button.
Parameters to change the functions of the inputs and outputs
Digital inputs:
p0701 to p0724
Digital outputs:
p0730 to p0748
Analog inputs:
r0751 to p0762
Analog outputs:
p0771 p0785
If you use Starter, then you can make the changes using the "Inputs and outputs" menu.