SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
BI: p0854 = 0 signal
No control by PLC
BI: p0854 = 1 signal
Master ctrl by PLC.
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: This bit is used to initiate a response for the drives when the control fails (F07220). If there is no control available,
then binector input p0854 should be set to 1.
If a control is available, then STW1.10 must be set to 1 (PZD1) so that the received data is updated. This applies
regardless of the setting in p0854 and even in the case of free telegram configuration (p0922 = 999).
Description: Sets the signal source for the command "unconditionally open holding brake".
Dependency: Refer to: p0858
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: The signal via BI: p0858 (unconditionally close holding brake) has a higher priority than via BI: p0855 (uncondition-
ally open holding brake).
Description: Sets the signal source for the command "enable speed controller" (r0898.12).
0 signal: Set the I component and speed controller output to zero.
1 signal: Enable speed controller.
Dependency: Refer to: r0898
Note: If "enable speed controller" is withdrawn, then an existing brake will be closed.
If "speed controller enable" is withdrawn, the pulses are not suppressed.
Description: Sets the monitoring time for the power unit.
The monitoring time is started after an 0/1 edge of the ON/OFF1 command. If the power unit does not return a
READY signal within the monitoring time, fault F07802 is output.
Dependency: Refer to: F07802, F30027
Notice: The maximum time to pre-charge the DC link is monitored in the power unit and cannot be changed. The maximum
pre-charging duration depends on the power unit.
The monitoring time for the pre-charging is started after the ON command (BI: p0840 = 0/1 signal). Fault F30027 is
output when the maximum pre-charging duration is exceeded.
p0855[0...n] BI: Unconditionally open holding brake / Uncond open brake
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 2701
Min Max Factory setting
- - 0
p0856[0...n] BI: Speed controller enable / n_ctrl enable
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 2701
Min Max Factory setting
- - 1
p0857 Power unit monitoring time / PU t_monit
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8760, 8864, 8964
Min Max Factory setting
100.0 [ms] 60000.0 [ms] 10000.0 [ms]