Description: Displays the actual output of the Isq current controller (torque/force generating current, PI controller).
The value contains the proportional and integral components of the PI controller.
Description: Displays the integral component of the Isq current controller (torque/force-generating current, PI controller).
Description: Displays the actual output of the Isd current controller (flux-generating current, PI controller).
The value contains the proportional and integral components of the PI controller.
Description: Displays the integral component of the Isd current controller (flux-generating current, PI controller).
Description: Displays the limit value for the integral component of the Isd current controller.
Description: Sets the scaling of the quadrature arm decoupling
r1718 CO: Isq controller output / Isq_ctrl outp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_1 Unit selection: p0505 Func. diagram: 6714
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r1719 Isq controller integral component / Isq_ctrl I_comp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_1 Unit selection: p0505 Func. diagram: 6714
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r1723 CO: Isd controller output / Isd_ctrl outp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_1 Unit selection: p0505 Func. diagram: 6714
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r1724 Isd controller integral component / Isd_ctrl I_comp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_1 Unit selection: p0505 Func. diagram: 6714
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r1725 Isd controller integral component limit / Isd_ctrl I_limit
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_1 Unit selection: p0505 Func. diagram: 6714
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p1726[0...n] Quadrature arm decoupling scaling / Transv_decpl scal
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6714
Min Max Factory setting
0.0 [%] 200.0 [%] 75.0 [%]