Description: Defines the maximum modulation depth.
Dependency: Default setting PM260: 103 %.
Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description: Sets the filter time constant of the DC link voltage used to calculate the modulation depth.
Description: DC link voltage used to determine the maximum possible output voltage.
Description: Displays the effective modulator mode.
Value: 1: Flat top modulation (FLB)
2: Space vector modulation (SVM)
9: Optimized pulse pattern
Description: Sets the configuration for the modulator.
p1803[0...n] Maximum modulation depth / Modulat depth max
PM250
PM260
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
20.0 [%] 150.0 [%] 106.0 [%]
p1806[0...n] Filter time constant Vdc correction / T_filt Vdc_corr
Access level: 4 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 0.0 [ms]
r1808 DC link voltage actual value for U_max calculation / Vdc act val U_max
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_2 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
- [V] - [V] - [V]
r1809 CO: Modulator mode actual / Modulator mode act
Access level: 4 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 9 -
p1810 Modulator configuration / Modulator config
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Avg value filter for U_lim (only for
Vdc_comp. in modulator)
Yes No -
01 DC link voltage compensation in the current
control
Yes No -