Caution: If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note: The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal (of the technology controller).
- if the actual value increases with increasing motor speed, then the inversion should be switched out.
- if the actual value decreases with increasing motor speed, then the inversion should be set.
If value = 0:
The drive reduces the output speed when the actual value rises (e.g. for heating fans, intake pump, compressor).
If value = 1:
The drive increases the output speed when the actual value increases (e.g. for cooling fans, discharge pumps).
Description: Displays the smoothed speed setpoint of the technology controller prior to switching to operation with fault response
(see p2345).
Dependency: Refer to: p2345
Note: Smoothing time = 10 s
Description: Sets the response of the technology controller to the occurrence of fault F07426 (technology controller actual value
limited).
The fault response is executed if status bit 8 or 9 in the technology controller status word r2349 is set. If both status
bits are zero, a switch back to technology controller operation will follow.
Value: 0: Function inhibited
1: On fault: Changeover to r2344 (or p2302)
2: On fault: Changeover to p2215
Dependency: The parameterized fault response is only effective if the technology controller mode is set to p2251 = 0 (technology
controller as main setpoint).
Refer to: p2267, p2268, r2344
Refer to: F07426
Notice: Dependent upon the application, the changing over of the setpoint when fault F07426 occurs can lead to the fault
condition disappearing and the re-activation of the technology controller. This can repeat itself and cause limit oscil-
lations. In this case, a different fault response or a different fixed setpoint 15 for the fault response p2345 = 2 should
be selected.
Note: The parameterized fault response can only be achieved if the default fault response of the technology controller
fault F07426 is set to "NONE" (see p2100, p2101). If a fault response other than "NONE" is entered in p2101 for
F07426, p2345 must be set to zero.
If the fault occurs during ramping up to the starting setpoint p2302, this starting setpoint is retained as the final value
(there is no changeover to the fault response setpoint).
r2344 CO: Technology controller last speed setpoint (smoothed) / Tec_ctrl n_setp_sm
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- [%] - [%] - [%]
p2345 Technology controller fault response / Tech_ctrl flt resp
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0 2 0