User Manual

List of parameters
Parameters
1-353
© Siemens AG 2009 - 2013 All Rights Reserved
SINAMICS G120 CU240B/E-2 Control Units List Manual (LH11), 01/2013
Index: [0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLS4
Dependency: Refer to: p9363, p9531
Refer to: C01714
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SLS: Safely-Limited Speed
Description: Sets the tolerance for the crosswise data comparison of the actual position between processors 1 and 2.
Dependency: Refer to: p9542
Refer to: C01711
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: For a linear axis, the tolerance is internally limited to 10 mm.
For a "linear axis with rotating motor" and standard setting of p9320, p9321 and p9322, the standard setting of
p9342 corresponds to a position tolerance of 36 ° on the motor side.
Description: Sets the filter time for the SSM feedback signal to detect standstill.
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The filter time is effective only if the function is enabled (p9301.16 = p9501.16 = 1).
The parameter is included in the crosswise data comparison of the two monitoring channels.
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the velocity limit for the SSM feedback signal to detect standstill (n < nx).
When this limit value is undershot, the signal "SSM feedback signal active" is set.
Dependency: Refer to: p9546
Caution: The following applies for p9306 = 3:
The "SAM" function is switched out if the selected threshold value is undershot.
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
p9342 SI Motion act. val. comparison tolerance (crossw.) (processor 2) / SI Mtn actV tol P2
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0010 [°] 360.0000 [°] 12.0000 [°]
p9345 SI Motion SSM filter time (processor 2) / SI Mtn SSM filt P2
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2823
Min Max Factory setting
0.00 [µs] 100000.00 [µs] 0.00 [µs]
p9346 SI Motion SSM velocity limit (processor 2) / SI Mtn SSM v_limP2
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2823
Min Max Factory setting
0.00 [rpm] 100000.00 [rpm] 20.00 [rpm]