Description: Setting to select and de-select the acceptance test for SLP(SE).
Value: 0: [00 hex] deselect acceptance test SLP(SE)
172: [AC hex] select acceptance test SLP(SE)
Dependency: Refer to: p9358, p9370, p9558, p9570, p9601
Note: Acceptance test mode can only be selected if the motion monitoring functions, which are integrated in the drives,
are enabled (p9601.2/p9801.2).
Description: Sets the reference value to define the brake ramp.
The rate of rise of the brake ramp depends upon p9581 (reference value) and p9583 (monitoring time).
Dependency: Refer to: p9582, p9583
Description: Sets the delay time for monitoring the brake ramp.
Monitoring of the brake ramp starts once the delay time has elapsed.
Dependency: Refer to: p9581, p9583
Description: Sets the monitoring time to define the brake ramp.
The rate of rise of the brake ramp depends upon p9581 (reference value) and p9583 (monitoring time).
Dependency: Refer to: p9581, p9582
p9575 SI Motion acceptance test mode (processor 1) / SI Mtn acc_mod P1
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00AC hex 0000 hex
p9581 SI Motion brake ramp reference value (processor 1) / SI Mtn ramp ref P1
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
600.0000 [rpm] 240000.0000 [rpm] 1500.0000 [rpm]
p9582 SI Motion brake ramp delay time (processor 1) / SI Mtn ramp t P1
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
10.00 [ms] 99000.00 [ms] 250.00 [ms]
p9583 SI Motion brake ramp monitoring time (processor 1) / SI Mtn rp t_mon P1
PM240
PM250
PM260
CU240E-2_DP_F
CU240E-2_F
CU240E-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.50 [s] 3600.00 [s] 10.00 [s]