User`s manual

Troubleshooting, Continued
The device may have an invalid or duplicate device ID, IP address,
Subnet mask, or iproute.
Configuration Parameter
Errors:
Verify the configuration parameters by connecting a PC serial port to the
Configuration Port, logging in, and typing config display.
> login password
Siemens
Advance DataNET Hub
local> config display
Config:
type DATANET HUB
address ip 172.16.99.7
subnetmask 255.255.0.0
address ethernet 00.c0.c9.01.20.a7
device ID 172.16.99.7
1 time server ip 0.0.0.0
2
3
Make sure each Hub half has a
unique IP address and that both Hub
halves have the
same device ID. Usually the device ID is set to the IP
address of the ‘A’ Hub.
Advance Network devices periodically broadcast their status for
diagnostic and network routing purposes.
The Subnet mask must be identical on all Advance network devices
(Maxum analyzer, NAU, ANCB, DNH), and connected to a single
network, for the broadcast message to be received properly. If a remote
device does not show up in the device routing table, verify that the
remote device matches the local device Subnet mask.
66 Data Communications Setup