 Sensitivity Settings 
Application Parameter Sets 
Model FDO421 provides four (2) pre-programmed sensitivity parameter sets that can be selected by the Siemens fire-alarm 
control panel in order to match the expected application or environmental conditions: 
•   Standard 
•   Air-duct 
Standard:
 This application parameter set, which is ideal for normal office | hotel-lobby-type 
applications, is the default setting. 
Air-Duct:
 This application parameter set is used when the detector is used a UL268A (DI) 
compliant, direct in-air duct application without a duct housing.
Model FDO421 does not require a field sensitivity test. Model FDO421 is UL Listed as a self-testing 
device and complies with NFPA 72 as a self-monitoring detector and control-panel arrangement. This 
parameter set is also used when Model FDO421 is used in air-duct housings (Models FDBZ492 and 
FDBZ492-HR). 
A quick visual inspection is sufficient to indicate the condition of Model FDO421 at any time. If more 
detailed information is required, a printed report can be provided from the compatible FACP, indicating 
the status and settings assigned to each individual detector. When Model FDO421 moves to `Alarm’ 
mode, the detector will flash R
ED and continue flashing until the system is reset at the FACP. At that 
same time, any user-defined, system-alarm functions programmed into the system are activated. 
Model FDO421 contains a tri-color LED indicator, capable of flashing any one (1) of three (3) distinct 
colors: G
REEN | YELLOW | RED. During each flash interval, the microprocessor-based detector monitors 
the following scenarios: 
•   Smoke sensitivity is within the range indicated on the nameplate label 
•   Smoke in its sensing chamber 
•   Internal sensors and electronics are functional 
Based on the results of the monitoring, the LED indicator flashes the following: 
FLASH COLOR  CONDITION 
FLASH INTERVAL  
[in seconds] 
GREEN
: 
Normal supervisory operation.  
Smoke sensitivity is within rated limits. 
10 
YELLOW:  Detector is in trouble and needs replacement.  4 
RED:  `Alarm’ condition  1 
NO FLASH:  Detector is not powered. 
– 
  denotes LED can be turned OFF  
Please follow the corresponding description of the panel used. 
1.  Labyrinth 
2.
  Optical 
transmitter 
3.
 Optical 
receiver 
1.  Dust cover 
2.
  Photoelectric 
smoke 
detector 
1
2
Model FDO421- 