Sensitivity Settings
Application Parameter Sets
Model FDO421 provides four (2) pre-programmed sensitivity parameter sets that can be selected by the Siemens fire-alarm
control panel in order to match the expected application or environmental conditions:
Standard
Air-duct
Standard:
This application parameter set, which is ideal for normal office | hotel-lobby-type
applications, is the default setting.
Air-Duct:
This application parameter set is used when the detector is used a UL268A (DI)
compliant, direct in-air duct application without a duct housing.
Model FDO421 does not require a field sensitivity test. Model FDO421 is UL Listed as a self-testing
device and complies with NFPA 72 as a self-monitoring detector and control-panel arrangement. This
parameter set is also used when Model FDO421 is used in air-duct housings (Models FDBZ492 and
FDBZ492-HR).
A quick visual inspection is sufficient to indicate the condition of Model FDO421 at any time. If more
detailed information is required, a printed report can be provided from the compatible FACP, indicating
the status and settings assigned to each individual detector. When Model FDO421 moves to `Alarm
mode, the detector will flash R
ED and continue flashing until the system is reset at the FACP. At that
same time, any user-defined, system-alarm functions programmed into the system are activated.
Model FDO421 contains a tri-color LED indicator, capable of flashing any one (1) of three (3) distinct
colors: G
REEN | YELLOW | RED. During each flash interval, the microprocessor-based detector monitors
the following scenarios:
Smoke sensitivity is within the range indicated on the nameplate label
Smoke in its sensing chamber
Internal sensors and electronics are functional
Based on the results of the monitoring, the LED indicator flashes the following:
FLASH COLOR CONDITION
FLASH INTERVAL
[in seconds]
GREEN
:
Normal supervisory operation.
Smoke sensitivity is within rated limits.
10
YELLOW: Detector is in trouble and needs replacement. 4
RED: `Alarm condition 1
NO FLASH: Detector is not powered.
denotes LED can be turned OFF
Please follow the corresponding description of the panel used.
1. Labyrinth
2.
Optical
transmitter
3.
Optical
receiver
Photoelectric
smoke
1
2
Model FDO421-