Desigo® Fire Safety
Detectors and Peripherals
Multi-Criteria Fire Detector
Model FDOT421
Model FDOT421-
Multi-Criteria Fire Detector
Architect & Engineer Specifications
UL 268 7th Edition Listed
Built-in ISOtechnology
252 Isolation devices per SLC
Each detector is self-testing:
- complete
diagnostics performed
every 10 seconds
- self-monitored for sensitivity within
UL Listed limits
Listed, approved as a heat detector:
- Rate-of-Rise Detection: 15
°
F / min.
(8.3
°
C / min.)
- Fixed: 135
°
F (57
°
C)
Superior electromagnetic interference
(EMI) and radio-frequency interference
(RFI) immunity
Field programmable as rate-of-rise or
fixed temperature, per `Alarm Source 2’ |
Standard parameter
Tri-color detector-status light-emitting
diode (LED) with 360° view
Compatible with Model DPU (device
programmer / loop tester)
Polarity insensitive via SureWire™
technology (in non-isolator mode)
Functions with Model DB-11series
mounting bases
Restriction of Hazardous Substances
(RoHS compliant)
Automatic environment compensation
UL L
isted | FM, CSFM Approved
- UL 268: `Open Area Smoke Detection
- UL 268A (
Duct) - `Direct
-in-Duct use
- UL 521: `Open Area Heat Detection
- ULC-S529: `Sys
tem Smoke Detector
- ULC-S5
30: `Heat Actuated Fire Detection
- FM 3230: `Open
Area Smoke Detection
- FM 3210: `O
pen Area Heat Detection
- CSFM |
File: 7272-0067:0258
Product Overview
The Photoelectric | Thermal (Heat) Detector (Model FDOT421) is an intelligent,
addressable multi-criteria detector that incorporates optical and thermal sensors, and
uses signals in a neural network to create an intelligent multi-criteria detector. The
encompassing result is a detector that provides enhanced detection to a wide range of
products of combustion.
Model FDOT21 is UL 268 7th Ed. listed and incorporates advanced built-in
ISOtechnology - True Class-X SLC operation (use is optional) greatly improves
reliability, circuit integrity and provides advanced addressable fault finding.
The multi-criteria detector additionally has state-of-the-art microprocessor
circuitry (with error check), as well as detector self-diagnostics and supervision
programs that is used on Desigo Fire Safety Modular | FireFinder XLS/V and on
Model FC/FV20-series Desigo Fire Safety fire-alarm control panels (FACPs).
Additionally, Model FDOT421 is a plug-in and addressable two-wire multi-criteria
detector (with both photoelectric and thermal sensors) whose value is increased
with built-in ISOtechnology feature, that is compatible with all current Siemens
intelligent, addressable systems.
Operation
Model FDOT421 utilizes an infrared light emitting diode (IRLED), and infrared
light-sensing photodiode. Under normal conditions, light transmitted by the LED
is directed away from the photodiode and scattered through the smoke chamber
in a controlled pattern.
The smoke chamber is designed to manage light dissipation and extraneous
reflections from dust particles or other non-smoke, airborne contaminants in such
a way as to maintain stable, consistent detector operation. When smoke enters
the detector chamber, light emitted from the IRLED is scattered by the smoke
particles, and is received by the photodiode.
Model FDOT421 also utilizes a modern, accurate and shock-resistant thermistor to
sense temperature changes.
The signal processing with detection algorithms
allows the detector to first gather smoke and thermal
data, and then analyze this information in the
detector’s `neural network.By comparing data
received with the common characteristics of fires or
fire signatures, Model FDOT421 can compare these
signals to those of deceptive phenomena that cause
other detectors to trigger a false alarm.
Each Model FDOT421 detector provides three (3) pre-programmed parameter sets
that can be selected by the FACP.