Data Sheet for Product

s Canada Limited Cerberus® PRO
Technical Data (continued)
Detector Sensitivity Range:
UL: 0.77% to 3.82% / ft.
NFPA 76 (Telco) VEWFD:
0.2% / ft. Pre-alarm,
1.0% / ft. Alarm
Application Profiles: 22 (field configurable)
Programmable Supervisory Temperature Warning
available with compatible FACPs:
-
4°F (
-
20°C) to 120°F (49°C)
Relative Humidity:
0-95%; non-condensing
Air Velocity
(Open Area): 0 4,000 feet-per-minute (fpm)
Direct-in-Duct: 0 4,000 (fpm)
Air Pressure: No effect
Maximum
Spacing: 30-foot centers (900 sq. ft.),
per NFPA 72 and ULC-S524 Listed
Input Voltage Range: 13VDC 32VDC
Alarm Current: 650μA
Quiescent (Standby) Current: 280 360μA
Detector Weight: 0.281 lbs. (0.128 kg.)
Approvals / Standards:
FM 3210, 3230
CSFM 7272-0067:0260
UL 268 NFPA 25
UL 268A NFPA 72
UL 521 NFPA 76
ULC-S524 Listed
Mounting Diagrams
Dimensions
Model OOH941
Model OOH941
with Model DB-11 base
Model OOH941
with Model DB-11E base
Detector Compatibility Table
Model
Data
Sheet
Number
Description
6300 FireFinder® XLS (system overview)
FC922 9815C 252-point system (networkable)
FC924 9815C 504-point system (networkable)
FV922 9821
252-point intelligent voice
communication system
FV924 9821
504-point intelligent voice
communication system