Data Sheet for Product

Siemens Data Sheet 9900
Smart Infrastructure Building Products usa.siemens.com/fire
Product Overview
The
Photoelectric | Thermal (Heat) Detector (Model OH921) is an intelligent,
addressable multi
-criteria detector that incorporates optical and thermal sensors,
and uses signals in a neural network to create an
intelligent multi-criteria detector.
The encompassing result is a detector that provides enhanced detection to a wide
range of products of combustion.
Model OH921 is UL 268 7th Ed. listed and incorporates
advanced built-in
ISO
technology- True Class-X SLC operation (use is optional) greatly improves
reliability, circuit integrity and provides advanced addressable fault finding.
The multi
-criteria detector also has state-of-the-art microprocessor circuitry (with
error check), as well as detector self
-diagnostics and supervision programs that is
used on Cerberus PRO Modular
| FireFinder XLS/V and on Model FC/FV9-series
Cerberus PRO
fire-alarm control panels (FACPs).
Additionally, Model OH921 is a plug
-in and addressable two-wire multi-criteria
detector (with both photoelectric and thermal sensors)
whose value is
increased with built
-in ISOtechnology feature, that is compatible with all
current
Siemens intelligent, addressable systems.
Operation
Model OH921 utilizes an infrared light emitting diode (IRLED),and infrared light
-
sensing photodiode. Under normal conditions, light transmitted by the LED is
directed away from the
photodiode and scattered through the smoke chamber in a
controlled pattern.
The smoke chamber is designed to manage light dissipation and extraneous
reflections from dust particles or other non
-smoke, airborne contaminants in such a
way as to maintain stab
le, consistent detector operation. When smoke enters the
detector chamber, light emitted from the IRLED is scattered by the smoke particles,
and is received by the photodiode.
Model OH921 also utilizes a modern, accurate and shock
-resistant thermistor to
sense temperature changes.
The signal processing with detection algorithms
allows the detector to first gather smoke and thermal
data, and then analyze this information in the
detector’s `neural network.’
By comparing data
received with the common chara
cteristics of fires or
fire signatures, Model OH921 can compare these
signals to those of deceptive phenomena that cause
other detectors to trigger a false alarm.
Each Model OH921 detector provides three (3) pre
-programmed parameter sets
that can be sele
cted by the FACP.
Cerberus® PRO
Detectors and Peripherals
Multi-Criteria Fire Detector
Model OH921
Model OH921
Multi-Criteria Fire Detector
Architect & Engineer Specifications
UL 268 7th Edition Listed
Built-in ISOtechnology™
252 Isolation devices per SLC
Each detector is self-testing:
- complete diagnostics performed every 10
seconds
- self-monitored for sensitivity within UL
Listed limits
Listed, approved as a heat detector:
- Rate-of-Rise Detection: 15
°
F / min. (8.3
°
C
/ min.)
- Fixed: 135
°
F (57
°
C)
Superior electromagnetic interference (EMI)
and radio-frequency interference (RFI)
immunity
Field programmable as rate-of-rise or fixed
temperature, per `Alarm Source 2’ | Standard
parameter
Tri-color detector-status light-emitting diode
(LED) with 360° view
Compatible with Model 8720 | DPU (device
programmer / loop tester)
Polarity insensitive via SureWire™
technology (in non-isolator mode)
Functions with Model DB-11series mounting
bases
Restriction of Hazardous Substances (RoHS
compliant)
Automatic environment compensation
UL Listed | FM, CSFM Approved
- UL 268: `Open Area Smoke Detection
- UL 268A (Duct) - `Direct-in-Duct’ use
- UL 521: `Open Area Heat Detection
- ULC-S529: `System Smoke Detector
- ULC-S530: ‘Heat Actuated Fire Detection
- FM 3230: `Open Area Smoke Detection’
- FM 3210: `Open Area Heat Detection
- CSFM | File: 7272-0067:0258
Model OH921
Multi-Criteria Fire Detector

Summary of content (5 pages)