Data Sheet for Product
Siemens
Smart Infrastructure - Building Products –4– usa.siemens.com/fire
Field-Device Programmer / Test Unit
Model OH921 is compatible with the Siemens field-device programmer / test unit (Model 8720 | DPU), which is a compact,
portable and menu-driven accessory for electronically programming and testing these addressable detectors promptly and
reliably. For instance, the field technician selects the accessory’s program mode, and enters the desired address.
Model DPU eliminates the need for cumbersome, unreliable mechanical programming methods (e.g. – dials and rotary
switches), and reduces installation and service costs by electronically programming and testing the detector prior to
installation. When set in `test’ mode, Model DPU will perform a series of diagnostic tests without altering the address or
other stored data, allowing technicians to determine if the detector is operating properly.
Each field-device programmer / test unit operates on
AC power or rechargeable batteries, providing flexibility and
convenience in the programming / testing of fire-safety equipment from practically any location.
Additionally, with the use
of a Model DPU unit, there is no longer a cause for concern with any vibration, corrosion and other deteriorating conditions
that can accompany the vitality of a mechanical-addressing mechanism.
The encompassing result is an intelligent detector that provides enhanced detection capability to a wide range of products
of combustion – while offering unsurpassed rejection to nuisance-alarm sources, including: dust | steam | aerosols and
other deceptive phenomena that could cause false alarms.
Technical Data
O
PERATING
TEMPERATURE:
+
32
°
–
+
100
°
F
(0° –
+
38°C)
R
ELATIVE
H
UMIDITY:
0 – 95%
(non-condensing)
AIR PRESSURE:
No effect
INPUT VOLTAGE
RANGE:
16VDC – 30VDC
`ALARM’
CURRENT, MAX.:
410μA
`STANDBY
’
CURRENT, MAX.:
250μA
MAXIMUM
SPACING:
30–ft. (9.144 m.) centers
(900 sq. ft. | 83.6 sq. m.),
per NFPA 72 and ULC-S524
THERMAL
RATING:
• Fixed 135°F (57°C)
• Rate-of-Rise:
15°F / min. (8.3°C)
at fixed 135°F (57°C)
DETECTOR
WEIGHT:
0.317 Lbs. (0.144 kg.)
MECHANICAL
PROTECTION
GUARD:
UL Listed / ULC Listed
with STI Guard Model STI-
9604
SENSITIVITY
RANGE:
• UL268 3.52-4.17% / ft obs.
• ULC 3.52-4.27% / ft obs.
• UL268A 2.32-2.84% / ft
obs
. (direct in-duct)
MODEL
OR TYPE
DATA
SHEET
PANEL
XLS
6300
FireFinder®
(fire-only overview)
XLSV
6340
FireFinder (fire w/ voice)
CERBERUS
PRO
M
ODULAR
8300
Cerberus PRO Modular
(system overview)
FC901
9813
Cerberus PRO
50-point addressable
FC922
9815
Cerberus PRO 252-pt.
addressable (fire)
FC924
Cerberus PRO 504-pt.
addressable (fire)
FV922
9821
Cerberus PRO
252-point addressable
(fire w/ Intelligent Voice
Communication [IVC]
)
FV924
504-pt. addressable
(fire w/ Intelligent Voice
Communication [IVC]
)
MODEL
OR TYPE
PART
NUMBER
PRODUCT
OH921 S54320-F6-A2
Addressable
Multi-Criteria
Fire Detector
Compatible Devices:
MODEL
OR TYPE
PART
NUMBER
PRODUCT
ABHW-4B S54320-F13-A1
Sounder base with
Loop-Power
Option
ABHW-4S S54320-F14-A1
Sounder base for
Sleeping Areas
ADB-BOX 500-698360
Surface Mount Adapter
Box for Audible Base
DB2-HR S54370-F12-A1
Relay base compatible
with Siemens standard
and advanced detectors
DB-11 500-094151
Detector Mounting Base
(for Series 11)
DB-11E
500-094151E
Detector Base (small)
RL-HW 500-033310
Remote Alarm Indicator:
Single-gang-box
mount, red
RL-HC 500-033230
Remote Alarm Indicator:
4” (10.2 cm.) octagon-
box mount, red
LK-11 500-695350
Base Locking Kit
(for Series 11)
See: www.STI-USA.com for further details
on ordering Model STI-9604
In Canada order:
MODEL
OR TYPE
PART
NUMBER
PRODUCT
DB-11C 500-095687
Detector
Mounting Base,
ULC Listed
S
Details for Ordering
Panel Compatibilities