Data Sheet for Product

Siemens
Smart Infrastructure - Building Products
3
usa.siemens.com/fire
Application Data
Installation of Model HI921 intelligent, addressable thermal detector requires a two-wire SLC circuit. In many retrofit
cases, existing wiring may be used. `T-tapping’ is permitted only for Style 4 (Class B) wiring. Model HI921 is polarity
insensitive when not used in Class-X mode, which can reduce installation and debugging times. The unit’s value is
multiplied with built-in ISOtechnology the True Class-X - NFPA 72 compliant SLC isolation feature supporting up to 252
isolation ready devices per loop. When used in mixed mode a maximum of 30 non-isolated devices between isolation
devices (wired in polarity-insensitive mode). Each detector fits into one (1) wall-or-ceiling footprint, and only occupies
one (1) address on the signal-line circuit (SLC).
Model HI921 can be applied within the maximum 50-feet (15.24 m.) center spacing (2,500 sq. ft. [232.3 sq. m.]) per
Underwriters’ Laboratories. This application guide is based on ideal conditions, specifically, smooth-ceiling surfaces,
minimal air movement, and no physical obstructions between potential fire sources and the actual detector. Do not
mount detectors in close proximity to heating | ventilation | air-conditioning (HVAC) outlets. Exposed joists or beamed
ceilings may also affect safe spacing limitations for detectors.
Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire-protection system
engineering and common sense dictate how and when fire detectors are installed and used. Contact your local
Siemens Fire Safety distributor or sales office whenever you need assistance applying Model HI921 in unusual
applications.
Be sure to follow NFPA guidelines and UL Listed / ULC Listed installation instructions included with every Siemens Fire
Safety detector and local codes for all fire-protection equipment.
Specifications
Model HI921 is a plug-in, (2) two-wire thermal (heat) detector, compatible with Cerberus PRO Modular | FireFinder
XLS/V and Model FC9-series FACPs. Each Model HI921 detector has microcomputer-chip technology and highly stable,
solid-state electronic circuitry. Model HI921 detectors utilize a modern, accurate and shock-resistant thermistor to
sense temperature changes. This electronic-sensing method virtually eliminates thermal lag associated with mechanical
temperature-sensing devices and provides almost instantaneous temperature status to the FACP.
Model HI921 provides seven (7) field-selectable, pre-programmed temperature settings:
Fixed Temperature set points (5)
Rate of Rise set points (2)
• Fixed 135°F (57°C)
• Fixed 145°F (63°C)
• Fixed 155°F (68°C)
Fixed 165°F (74°C)
• Fixed 175°F (79°C)
Rate-of-Rise: 15°F / min. (8.3°C) at fixed 135°F (57°C)
Rate-of-Rise: 15°F / min. (8.3°C) at fixed 175°F (79°C)
Additionally, the Model HI921 detector has the following optional feature:
Model HI921 provides indication of potential water freezing for sprinkler systems, via configuration for reporting a
low-temperature warning of 40°F (4.4°C).
This feature is compatible with Cerberus PRO Modular systems, as well as with FireFinder XLS/V and Cerberus PRO
FC/FV922 or FC/FV924 FACPs.
Mounting Diagrams | Dimensions
Model HI921