User Manual

Siemens Data Sheet 6154
Smart Infrastructure - Building Products usa.siemens.com/fire
Desigo® Fire Safety
Detectors and Peripherals
Multi-Criteria Fire Detector [with ASAtechnology™]
Model FDOOT441
Product Overview
Model FDOOT441 is an advanced, flexible multi-criteria fire detector incorporating a
redundant optical / thermal sensor. Additionally, Model FDOOT441 utilizes
ASAtechnology a distinctive forward / backward, light-scattering technology that
provides high-tech, unparalleled fire detection to the widest range of fire types
allowing the detector to distinguish non-threatening deceptive phenomena.
Each FDOOT441 unit is UL 268 7th edition listed incorporating advanced built-in
ISOtechnology- True Class-X SLC operation (use is optional) greatly improving
system reliability and circuit integrity while providing advanced addressable fault
finding.
The unit may be programmed as a high-sensitivity detector, with a 0.2 %/ft Pre-Alarm
threshold and 1.0 %/ft Alarm threshold thus meeting NFPA 76 requirements
(Standard for the Fire Protection of Telecommunications Facilities) as a Very Early
Warning Fire Detector (VEWFD).
Every FDOOT441 unit is a multi-purpose, addressable detector providing a
complete contemporary solution meeting fire detection needs for commercial
facilities. Each individual FDOOT441 sensor can be field programmed for
simultaneous and / or independent functionality, depending upon the precise
customer and application requirements.
For example, the detector can simultaneously utilize the optical and heat sensors
for enhanced multi-criteria fire detection, as well as provide independent outputs
for heat detection. Any combination of the sensors is possible.
The detector is very versatile, and meets the following fire-industry standards:
Multi-criteria fire detector ( UL 268 7
th
edition)
Heat detector ( UL 521) with five (5) possible field-selectable
temperatures; combined with four (4) rate-of-rise options
Direct, in-duct (plenum) detector ( UL 268A)
Supervisory monitoring for temperature ranges
NFPA 76 (Telco Standard) as VEWFD
Low-temperature warning signal at 40°F
(4.4°C) for sprinkler systems, per NFPA 25
/ NFPA 72
For instance, the signals from the detectors
sensors are monitored and processed via
the ASApatented algorithm technology,
which combines the signals into a neural
network to create an intelligent, multi-
criteria addressable detector.
Model FDOOT441
Multi-Criteria Fire Detector
[with ASAtechnology]
Architect & Engineer Specifications
UL 268 7
th
edition Listed, ULC Listed; FM
(#3230, #3210), CSFM (#7272-0067:0258)
Approved
Built-in ISOtechnology
Advanced multi-criteria fire detector
that has dual-optical thermal sensors
Differentiates between deceptive
phenomena and an actual fire
(nuisance-alarm avoidance)
Provides enhanced detection
via forward-and-backward
light-scattering technology
Complies with NFPA 76 (Telco standard)
as `VEWFD’ high-sensitivity detector
UL Listed and FM Approved as a multi-
criteria and `VEWFD’ fire detector
UL 268A Listed for direct air-duct
use (4,000 FPM)
Supervisory temperature-
monitoring feature
Remote sensitivity-measurement capability
Automatic environmental compensation
Up to 22 application profiles
Tri-color detector-status light-
emitting diode (LED)
Polarity insensitive via SureWire™
Low-temperature warning for sprinkler
systems, per NFPA 25
Meets UL, NFPA 72 requirements for
sensitivity self-monitoring
Compatible with:
- Model DB-11series mounting bases
- Model 8720 / DPU (device
programmer / loop tester)
Restriction of Hazardous
Substances (RoHS compliant)
Responds to both flaming and
smoldering-fire signatures