User Manual

Siemens
Smart Infrastructure - Building Products
5
usa.siemens.com/fire
Technical Data
OPERATING
TEMPERATURE:
+
32°
+
120°F
(0°
+
49°C)
HEAT DETECTOR
RANGE:
+
135°
+
175°F
(
+
57°
+
79°C)
PROGRAMMABLE
SUPERVISORY
TEMPERATURE
WARNING:
-
4°
+
120°F
(
-
20°
+
49°C)
(available with compatible FACPs)
DETECTOR
SENSITIVITY
RANGE:
UL Listed: 0.88 to 3.35 % / ft.
NFPA 76 (Telco)
VEWFD: 0.2 % / ft. Pre-alarm
1.0 % / ft. Alarm
AIR VELOCITY:
0 − 4,000 feet-per-minute (fpm)
0 − 4,000 fpm
Open Area:
Direct-in-duct:
AIR PRESSURE:
No effect
APPLICATION
PROFILES:
22
(field-configurable)
RELATIVE
HUMIDITY:
0 95%
(non-condensing)
Thermal Ratings
FIELD-SELECTABLE TEMPERATURE PROFILES
FIXED
TEMPERATURE:
135°F (57.2°C)
145°F (62.8°C)
155°F (68.3°C)
165°F (73.9°C)
175°F (79.4°C)
FIXED
TEMPERATURE +
RATE-OF-RISE:
(R-O-R)
135°F (57.2°C) +
R-o-R, 15°F (
-
9.4°C)
175°F (79.4°C) +
R-o-R, 15°F (
-
9.4°C)
135°F (57.2°C) +
R-o-R, 20°F (
-
6.6°C)
175°F (79.4°C) +
R-o-R, 20°F (
-
6.6°C)
FIELD-SELECTABLE
ALARM-THRESHOLD PROFILES
THRESHOLD:
2.5% / feet
3.0% / feet
THRESHOLD,
VERIFIED:
2.5% / feet
3.0% / feet
FACTORY MUTUAL (FM)
3210, 3230
CALIFORNIA STATE
FIRE MARSHAL (CSFM)
7272-0067:0260
UNDERWITERS
LABORATORES (UL | ULC)
UL268
UL268A
UL521
ULC-S524
NATIONAL FIRE
PROTECTION AGENCY
NFPA 25
NFPA 72
NFPA 76
Electrical Ratings
INPUT VOLTAGE RANGE:
13 32 VDC
ALARM CURRENT:
650 μA, max.
STANDBY CURRENT:
(quiescent)
Mounting Diagrams | Dimensions
Model FDOOT441
Model FDOOT441
[with Model DB-11 detector base]
Model FDOOT441
[with Model DB-11E detector base]
MODEL
OR TYPE
PART
NUMBER
PRODUCT
FDOOT441
S54320-F7-A1
Multi-Criteria Fire
Detector with
ASAtechnology
DB-11
500-094151
Detector
Mounting Base
DB-11E
500-094151E
Detector Base, small
DB2-HR
S54370-F12-A1
Detector Mounting
Base with Relay
RL-HC
500-033230
Remote Alarm
Indicator: 4”
(10.2 cm) octagon-
box mount, red
RL-HW
500-033310
Remote Alarm
Indicator: single-
gang box mount, red
LK-11
500-695350
Base Locking Kit
See: www.STI-USA.com for further
details on ordering Model STI-9604
In Canada order:
MODEL
OR TYPE
PART
NUMBER
PRODUCT
DB-11C
500-095687
Detector
Mounting Base,
ULC Listed
Product Compatibilities
MODEL OR
TYPE
DATA
SHEET
PANEL
XLS
6300
FireFinder (fir e)
XLSV
6340
FireFinder
(fire w/ voice)
FC2005
6813
Desigo Fire Safety
50-point addressable
FC2025
6815
Desigo Fire Safety 252-
point addressable (fir e)
FC2050
Desigo Fire Safety 504-
point addressable (fir e)
FV2025
6821
Desigo Fire Safety 252-
point addressable
(fire w/ Intelligent Voice
Communication [IVC])
FV2050
Desigo Fire Safety 504-
point addressable
(fire w/ Intelligent Voice
Communication [IVC])
Approvals | Standards
Details for Ordering