Environmental
Temperature: 32°F (0°C) to 100°F (38°C)
Humidity:
Up to 93% RH, non-condensing
Air Pressure:
No effect
Alarm Temperature:
135°F (57°C)
Electrical
Voltage: 16 − 27 VDC
Ripple:
3V, peak-to-peak
Supervisory Current:
110μA max
Alarm Current:
33 − 50mA
Dimensions
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.
Model
Part
Number
Description
FP-11 500-095112 Addressable FirePrint
TM
Detector
DB-11 500-094151
Detector Mounting Base
For Series 11
I
ntelligent Detectors
ADBX-11 500-096181
Audible Base
DB-11E 500-094151E
Detector Base (Small)
DB-ADPT 500-094187
Base Adapter to Model DB-3S Base
DB-X11RS
500-096125
Relay Base for Model 11-series
Intelligent Detectors
DMK-11 500-695338
Model 11-series Maintenance Kit
(replacement labyrinth and bug screen)
FDBZ492
S
54319-B22-A1
Air-Duct Housing
A two-wire addressable or conventional
duct detector (without relays) designed for
direct use on heating, ventilating and air
-
conditioning (HVAC) air-duct systems.
When equipped, the air-
duct detector
housing wi
ll signal the presence of smoke
being carried through the duct system.
FDBZ492-
HR
S
54319-B23-A1
Air-Duct Housing
A two-wire addressable duct detector
(with relays) designed for direct use to
HVAC air-duct systems.
This part has a programmable relay base,
and when equipped, the addressable air-
duct detector housing will signal the
presence of smoke being carried through
the duct system.
LK-11 500-695350
Base Locking Kit for Series 11 Detectors
RLI-1 500-390673
Remote Alarm Indicator
4” Octagon Box Mount, Red
RLI-2 500-390674
Remote Alarm
I
ndicator
Single-Gang Mount, Red
In Canada, please order:
Model
Part
Number
Description
FP-11C 500-095112C
135°F Fixed Temperature, Plug-In
Detector Addressable FirePrint
TM
Detector [
ULC Listed]
DB-11C 500-095687
Detector Mounting Base
(for Model 11-series Intelligent Detectors)
[
ULC Listed]
DB-X11RSC
500-093125C
Relay Base for Model 11-series
Intelligent Detectors [ ULC Listed]
ADBX-11C 500-096181C
Audible Base for Model 11-series
Intelligent Detectors [ ULC Listed]