User Manual

Building Technologies A6V10277374_n_en_--
Fire Safety 2018-09-26
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Supply
Operating voltage DC 12…33 V
Operating current (quiescent) Max. 250 µA
Sound activated DBS721/DBS729: 3.5 mA
DBS728: 3.6 mA (115 mW)
Optical indicator activated DBS728: 3.0/7.8 mA (65/130 mW) (dark/light)
DBS729: 1.5/4.0/6.5 mA (dark/medium/light)
Optical indicator and sound activated DBS728: 5.6/10.6 mA (160/225 mW) (dark/light)
DBS729: 5.0/7.5/10.5 mA (dark/medium/light)
Functional data
Sounds
DBS721/DBS729: 11
DBS728: 13
2 alarm levels
2 sound levels
(1 alarm sound level, 1 test sound level)
Sound level (alarm sound level) DBS721/DBS729: 82…89 dBA
DBS728: 77…93 dBA
Luminous intensity
DBS728 in accordance with EN 54-23:
light/high C-3-5
dark/low O-1.5-2.4
(ceiling mounted, cylindrical cover cap as in Class C)
DBS729: 0.9…3.2 cd
Luminous intensity levels DBS728: 2 levels (not available with all control panels)
DBS729: 3 levels, 2 flashing modes
(not available with all control panels)
Communication protocol C-NET
System compatibility C-NET FS720, FC360
Color ~RAL9010 pure white / translucent
Line connections
Conductor cross-section on detector base 0.2…1.5 mm
2