Desigo™ CC Version 4 Specification Texts A6V11878994_en_a_40 Smart Infrastructure
Table of Contents Copyright Notice ........................................................................................... 5 2 | 29 1 1.1 1.2 1.3 1.4 1.5 1.6 System description ............................................................................... 6 Management level requirements ..................................................................6 Operating system for building automation and control system ......................8 Product lifecycle ..............................................
6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 6.10 6.19 6.20 6.21 6.10.1 Media independent formats .........................................................21 Alarm message escalation list ....................................................................21 Acknowledgment .......................................................................................21 Alarm management strategy ......................................................................21 Alarm display ..........................................
10.4 10.5 10.6 10.7 10.8 Integrate via IEC 61850 ............................................................................. 27 Integrate via Modbus ................................................................................. 27 KNX .......................................................................................................... 27 M-Bus........................................................................................................ 28 Standard BACnet / AMEV .........................
Copyright Notice Copyright Notice Notice Document information is subject to change without notice by Siemens Switzerland Ltd. Companies, names, and various data used in examples are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Siemens Switzerland Ltd.
1 System description Management level requirements 1 System description 1.1 Management level requirements General All information comes together at the management level. The management level is the graphical, interactive interface for the operator to the automation station and the integrated plants and plant parts. System operation must be based on a simplified approach. The operator can display, query, process, save, or print any plant information via the peripheral units at the management level.
System description Management level requirements 1 Specified product: Siemens / Desigo CC or similar Scripting The system must provide a Script Editor to create scripts based on a known scripting language. The script engine must allow the manual execution of scripts manually by the operator, or automatic execution triggered by the system based configurable conditions.
1 System description Operating system for building automation and control system 1.2 Operating system for building automation and control system All data servers, operator stations, etc., for the BAC system must be compatible with the most current, generally available Windows 64-bit operating system. As a result, the current version of Windows (at least 6 months after release by Microsoft) as well as a minimum of the last Version is supported. Modifications to the customer network must be possible.
System description Product lifecycle 1 ● Visualize elevators and escalators state on a floor plan, as well as dynamically generate graphic templates ● Monitor elevator status ● Monitor escalator status Specified product: Siemens / Desigo CC or similar Integration of Building Information Modelling (BIM) data The system must natively support Building Information Modelling (BIM) technology to perform the following actions: ● Display visual and data information from Building Automation components such as ro
1 System description Hardware requirements 1.5 Hardware requirements Embedded Hardware Special purpose embedded hardware is required for small and / or mid-sized sites.
System description Software Requirements 1 ● ● ● ● ● ● ● ● ● ● Cores: 4 per running system Memory: 32GB Hard Disc: 1 * 1024GB SSD Network card: Gigabit speed Graphics card: Mid-range graphics card Network requirements Backbone Gigabit 1000 Mbps up/down Latency less than 10 ms For the integration of XNET Fire Safety Systems, the server hardware needs to have a PCI slot for the NCC-2F card ● IPV6 supported (NOTE: IPV6 for BACnet networks not supported) ● Standard secure mechanisms for DMZ, such as port for
1 System description Software Requirements High Availability software: Microsoft HyperV Server 2012, 2016, and 2019 (Replica configuration is only supported with dongle-based licenses) Specified product: Siemens / Desigo CC or similar 12 | 29 A6V11878994_en_a_40
User profiles 2 Individual views 2 User profiles 2.1 Individual views Individual, specific or user defined views must be adjustable for the plant overview. The views must cover various electrical and mechanical installations or follow geographic or organizational criteria and permit a customized, hierarchy view, that depicts the management station, control systems, plant geographic layout as well as relationship of the mechanical facilities.
3 Graphics Operating interface to CAD system 3 Graphics 3.1 Operating interface to CAD system The user interface must allow users access to various system diagrams and floor plans using graphical depictions, menu selections, and data point assignments. The graphics software must also permit the import of CAD symbols (DWG, DXF format) or scanned images for use in the system. Specified product: Siemens / Desigo CC or similar 3.
Graphics Graphic symbols and standards 3 3.7 Graphic symbols and standards Plant graphics must meet the ergonomic needs of the operator. The displayed graphic symbols must correspond to the generally valid standard for HVAC symbols (DIN EN 62424 (VDE0810-24)) and ASHRAE guidelines. The symbols must be supported as 2 and 3 dimensional graphics.
4 Energy management Integration of power meters 4 Energy management 4.1 Integration of power meters The system must support the integration of power meters and provide standard electrical symbols as well as dedicated graphics and templates for meters or electrical components commonly used in data centers, such as PDUs and UPSs. The integration must allow different poll rates for different properties and to allow the archiving and trending of selected values.
Energy management Hierarchical reporting and Filtering 4 4.7 Hierarchical reporting and Filtering The system must allow the creation of a hierarchical structure for report generation. Every element belonging in the selected node must be included in the relevant report. The system must allow every meter to be assigned into a category (e.g. electricity) and the report generation must allow filtering based on these categories. Specified product: Siemens / Desigo CC or similar 4.
5 Scheduler programs Management via central scheduler programs 5 Scheduler programs 5.1 Management via central scheduler programs Operate all scheduler programs online from the management level to achieve consistent, transparent operation of all integrated systems and subsystems. Specified products: Siemens / Desigo CC or similar 5.2 Scheduler programs The system must offer the ability to operate schedulers on automation stations as well as support management station-based time scheduling.
Scheduler programs Create scheduler online 5 5.7 Create scheduler online Scheduler programs must be able to be remotely created online to provide service personnel a high level of flexibility. Specified products: Siemens / Desigo CC or similar 5.8 Create offline trend online Trend log objects, both offline or online, must be able to be remotely created in order to provide service personnel a high level of flexibility.
6 Security Access protection 6 Security 6.1 Access protection Different persons maintain and operate the plant. For this reason, passwords must be assigned to authorized persons to guarantee transparency for tracking or authorization purposes. A minimum of four different rights must be assignable. ● Administrator. ● Program and graphics creation. ● Operation to change or adjust setpoints. ● Guest. Specified products: Siemens / Desigo CC or similar 6.
Security System safety 6 6.7 System safety High availability is expected from the building automation and control system. This results in greater data availability, greatly reducing any down times. Specified product: Siemens / Desigo System or similar 6.8 Alarm generation 6.9 Message handling The building management system must support alarms generated at the automation level (substations). Specified product: Siemens / Desigo CC or similar 6.10 Alarm routing 6.10.
6 Security Alarm display 6.14 Alarm display 6.14.1 Color display Incoming alarms must be colored for quick and easy interpretation. Both order and state as well as alarm priority must be recognizable. The alarm window must be displayed as per operator needs. Alarm window displays must be added to the bid. Specified products: Siemens / Desigo CC or similar 6.15 Alarm message content The message texts must contain all information necessary to allocate and resolve the error.
Security Event treatment 6 Specified product: Siemens / Desigo CC or similar 6.18.3 Event acknowledgement The user can acknowledge each event directly from the list, suppress the acoustic notification, print or delete it. The interface must also have an option to deleted active, acknowledged events until it is reset to the normal state.
7 Reports Report generation 7 Reports 7.1 Report generation Must generation spontaneous or predefined reports to provide important plant data at any time. The reports must be printable and exportable as a PDF file. The data must be able to be edited in other programs (Microsoft Excel or Microsoft Access) for further analysis. Specified product: Siemens / Desigo CC or similar 7.2 Standard report templates Template to generate detailed reports at little effort.
Remote operation User requirements on operation 8 8 Remote operation 8.1 User requirements on operation The web-based user interface offers the same functionality as those on other workstations including operation and configuration. All user functions be available on clients via browser, installed client console, or Windows desktop App. Specified product: Siemens / Desigo CC or similar User must be able to remotely operate and engineer plants regardless of location.
9 Trend data Simultaneous, multiple trends 9 Trend data 9.1 Simultaneous, multiple trends Multiple trend views must be possible simultaneously to provide a comprehensive plant overview. Standard plants from medium to higher complexity (as in this project) require a simultaneous display of up to 10 trend curves on the current page view to assess the plants. Multiple trend curves must thus be recorded at the same time. Specified products: Siemens / Desigo CC or similar 9.
Communication Interfaces 10 10 Communication 10.1 Interfaces The building automation and control system must be extendible to ensure longterm operation and provide all standard interfaces commonly available on today's market. Specified product: Siemens / Desigo System or similar 10.
10 Communication M-Bus 10.7 M-Bus The management station must support native communication to meter bus devices, via M-Bus/IP protocol though M-Bus Gateway, or M-Bus Master to Ethernet converter or converters. Specified product: Siemens / Desigo CC or similar 10.8 Standard BACnet / AMEV 10.8.1 DIN EN ISO 16484-5 / AMEV AMEV (Management station) AMEV Profile MBE-A and MBE-B The management station must meet AMEV profiles MBE-A and MBE-B as per AMEV guideline "BACnet 2011" V1.1.