User Manual
System description
System continuity
1
A6V11878994_en_a_42 11 | 33
● Compatibility with the latest version of supported operating systems
● Support of the latest versions of the integrated subsystems
Specified product: Siemens / Desigo System or similar
1.4 System continuity
Products used must be have a label for a global standard that ensures inaction
with products from various manufacturers. Products with these labels can also be
combined if manufactured at intervals of more than 10 years.
Specified product: Siemens / Desigo System or similar
1.5 Hardware requirements
Embedded Hardware
Special purpose embedded hardware is required for small and / or mid-sized sites.
The hardware and software environment must fulfil the following definition:
● Type: Embedded
● Processor: Intel Celeron N2930, Intel Atom E3827, Intel Celeron 4CJ1900
● Memory: 8GB
● Hard disk: 100GB SSD
● Network Card: Gigabit speed
● Graphics Card: Onboard graphics adapter with integrated processor
● Minimum Software environment:
● Win10 IOT Enterprise 2016 LTSB
● Microsoft SQL Server 2014 – Express Edition
● Network Requirements:
● Local network
● Single subnet
● 100 Mbps up/down
● Support Wake on LAN
● Defined range
● 1 server
● Max number of objects = 10,000
Specified product: SIMATIC Nanobox IPC227E or similar
Standard Hardware for small or medium plants
(ca. 500-2000 data points)
One client/server system for mid-sized sites with a high data transfer rate is
required. The hardware environment must fulfill the following definitions:
● Processor: Core i7 or equivalent >= 3.2 GHz
● Cores: 4 per running system
● Memory: 16GB
● Hard Disc: 1 * 1024GB SSD
● Network card: Gigabit speed
● Graphics card: Mid-range graphics card
Network requirements:
● Local network
● 1000 Mbps up/down
● Latency less than 10 ms
● For the integration of XNET Fire Safety Systems, the server hardware needs to
have a PCI slot for the NCC-2F card
● Defined range