4.7 Hierarchical reporting and Filtering
The system must allow the creation of a hierarchical structure for report generation.
Every element belonging in the selected node must be included in the relevant
report.
The system must allow every meter to be assigned into a category (e.g. electricity)
and the report generation must allow filtering based on these categories.
Specified product: Siemens / Desigo CC or similar
4.8 Power Quality meters
The system must allow the integration of power quality meters with the IEC61850
protocol.
In case a device generates a fault based on the waveform capture, the system
must be able to download the file from the device for further analysis and storage.