User Manual

Security
Acknowledgment
6
24 | 33 A6V11878994_en_a_42
6.10.5 Message optimization
In the situation of event related alarm bursts, the system shall avoid generating
notification bursts to allow users to keep the overview in exceptional situations.
Specified product: Siemens / Desigo CC or similar
6.10.6 Graphical easy buttons to trigger notifications
The system shall allow to send out notifications manually, using graphical buttons
for triggering. These graphical buttons shall be part of normal graphic pages (for
example, campus, building and ground floor graphics).
Specified product: Siemens / Desigo CC or similar
6.11 Acknowledgment
Operator units for acknowledgement
All alarms (alarms and faults, errors) must be acknowledgeable after issue of
individual rights from all connected workstations. For tracking reason, a time stamp
and assignment (based on user account) is required.
This includes:
Local acknowledgement (control cabinet, automation station)
Management level
Remote operating equipment
Specified products: Siemens / Desigo CC or similar
6.12 Alarm management strategy
The software must permit configuration of alarm management strategy for each
data point. The editor provides a way to edit data points directly, online via the
building management system.
The software for the user interface is also able to make batch changes to data
point definitions and attributes to one or more data points selected by the user.
Specified product: Siemens / Desigo CC or similar
6.13 Colored display of Alarms and Events
Incoming alarms must be colored for quick and easy interpretation. Both order and
state, as well as alarm priority must be recognizable. The alarm window must be
displayed as per operator needs. Alarm window displays must be added to the bid.
Specified products: Siemens / Desigo CC or similar
6.14 Alarm message content
The message texts must contain all information necessary to allocate and resolve
the error. This includes at least the following attributes:
Clear text.
Control cabinet name
Plant name
Priority
Timestamp
Time.
Status (acknowledged, unacknowledged).
Instructions on how to resolve the problem must be available in the background.