6.15 Event texts
For each system object it shall be possible to configure texts with object specific
information and instructions that must be displayed in case of an alarm. Different
texts for to off-normal and back to normal transitions shall be supported.
Specified products: Siemens / Desigo CC or similar
6.16 Filter alarms
The building automation and control system must offer alarm filtering. Filtering
must be possible by alarm lists or priorities. Alarms are displayed in popup
windows.
Step-by-step instructions on handling each alarm help the building automation and
control system operator to find a solution.
Specified products: Siemens / Desigo CC or similar
6.17 Event management
Event routing and sorting
Event messages can be displayed on each workstation in a table application and
must include the following information: name, value, event time and date, state,
priority, acknowledge information, and alarm counter. The system must also be
able to send out an audio message appropriate for the event category.
Specified product: Siemens / Desigo CC or similar
Event message
Event messages can be displayed on each workstation in a table application and
must include the following information on each event: name, value, event time and
date, state, priority, acknowledge information, and alarm counter. Each event must
also be able to send out an audio message appropriate for the event category.
Specified product: Siemens / Desigo CC or similar
Event acknowledgement
The user can acknowledge each event directly from the list, suppress the acoustic
notification and print or delete it. The interface must also have an option to deleted
active, acknowledged events until it is reset to the normal state.
The user must be able to navigate to information associated with a data point, start
an associated graphic or trended graphic diagram, or run a report for a data point
selected directly from the event list.
Specified product: Siemens / Desigo CC or similar
6.17.1 Event routing and sorting
Event messages can be displayed on each workstation in a table application and
must include the following information: Name, value, event time and date, state,
priority, acknowledge information, and alarm counter. The system must also be
able to send out an acoustic message appropriate to the event category
Specified product: Siemens / Desigo CC or similar
6.17.2 Event message
Event messages can be displayed on each workstation in a table application and
must include the following information on each event: Name, value, event time and
date, state, priority, acknowledge information, and alarm counter. Each event must
also be able to send out an acoustic message appropriate to the event category
Specified product: Siemens / Desigo CC or similar