User Manual

Communication
Interfaces
10
30 | 33 A6V11878994_en_a_42
10 Communication
10.1 Interfaces
The building automation and control system must be extendible to ensure long-
term operation and provide all standard interfaces commonly available on today's
market.
Specified product: Siemens / Desigo System or similar
10.2 Fire detection system, BACnet-based
BACnet-based fire detection systems supporting BACnet BIBB AE-LS-B as well as
objects LifeSafetyPoint and LifeSafetyZone as per the PICS (Protocol
Implementation Conformance Statement) document must be able to be integrated
for best deployment of a building automation and control system. The following
functions must be supported:
Alarms and events from the fire detection system must be identified clearly and
unambiguously.
Signaling device states must be displayed as per the BACnet standard.
Instruction texts must be able to be added to detectors and zones.
Situational and floor plans as well as dynamic symbols must be used for
visualization.
A technical hierarchy, e.g. building, building part, zone, detector, must be
provided to the operator for ease of operation.
Specified product: Siemens / Desigo System or similar
10.3 Integrate third-party devices via OPC
The OPC Foundation must test and certify the system, which must be able to
integrate and edit OPC data, and yet supply real time OPC data as an OPC server.
System processing must include alarming, trend, scheduler, reporting, and be able
to communicate with other devices.
The system must support the OPC specification:
OPC data access (DA)
Specified product: Siemens / Desigo CC or similar
10.4 Integrate via IEC 61850
A native integration with an electrical power network via IEC 61850 protocol must
be supported.
Specified product: Siemens / Desigo CC or similar
10.5 Integrate via Modbus
The management station must support communication to Modbus TCP/IP devices
and sub systems directly from the management station.
Specified product: Siemens / Desigo CC or similar
10.6 KNX
The management station must support native communication to KNX devices, via
KNX/IP protocol through KNX IP Routers, or KNX IP interfaces and gateways.
Specified product: Siemens / Desigo CC or similar