User Manual
Communication
M
-
Bus
10
A6V11878994_en_a_42 31 | 33
10.7 M-Bus
The management station must support native communication to meter bus
devices, via M-Bus/IP protocol though M-Bus Gateway, or M-Bus Master to
Ethernet converter or converters.
Specified product: Siemens / Desigo CC or similar
10.8 Standard BACnet / AMEV
10.8.1 DIN EN ISO 16484-5 / AMEV
AMEV (Management station) AMEV Profile MBE-A and MBE-B
The management station must meet AMEV profiles MBE-A and MBE-B as per
AMEV guideline "BACnet 2011" V1.1.
Specified products: Siemens / Desigo CC or similar
10.8.2 B-AWS (management station)
The required management stations match the BACnet profile B-AWS (advanced
management station) as per BTL Listing and ANSI / ASHRE 135 guidelines. They
must also support BACnet data points and BACnet personal safety security zone
functionality. The BACnet protocol revision must be at least 1.15.
Specified product: Siemens / Desigo CC or similar
10.9 ONVIF video standard
The management system must be capable of video operations fully integrated into
the same user interface with the following capabilities:
● Live video, Recording and Video Search and Replay
● Live video, Recording and Video Search and Replay
● Video display of multiple cameras
Status and Commands
TZ and predefined PTZ Positions
● Remote Control of Video Monitors
● Video Events and Video Event Treatment including video tagging with alarm
information
● Diagnostic information of Video Devices
● Video as Operating Procedure step
Specified product: Siemens / Desigo CC or similar
10.10 Building automation and control system – Industrial
Devices
Integration of Simatic systems
A native integration of Simatic (S7 300/400/1200/1500) and S7 PLUS must be
supported.
Specified product: Siemens / Desigo CC or similar