User Manual

System description
Management level requirements
1
8 | 33 A6V11878994_en_a_42
Conditions can be time-based, event-based, on change of values or on a
combination of some or all. When conditions are met, the system shall execute a
pre-configured list of commands
Specified product: Siemens / Desigo CC or similar
Scripting
The system must provide a Script Editor to create scripts based on a known
scripting language. The script engine must allow the manual execution of scripts
manually by the operator, or automatic execution triggered by the system based
configurable conditions. Among others the scripts must support:
Commanding of objects
Reading attributes of object
Subscription to value changes
Read/Write text files
Loading of external DLL’s
Mathematical / logical operations
Specified product: Siemens / Desigo CC or similar
Drafted for use by fire detection and security systems (UL certified)
The management station must have passed Underwriters Laboratories (UL)
performance and environmental tests.
The management station must offer all relevant functions to connect comfort and
fire detection systems:
Display and handle events
Graphically monitor and control the fire detection system
Highlight the highest priority events.
Direct navigation to the element triggering an event.
Quickly go to user-defined instructions and graphically display event locations.
Save and query activity data from the fire detection system.
Distribute fire monitoring and control capabilities.
Provide operating instruction checklists for operators during stressful situations
for handling fire events.
Send automatic remote messages of impacted device per e-mail.
Display and plan automatic history reports.
Specified product: Siemens / Desigo CC or similar
System-wide self-monitoring
The system must be capable of monitoring running applications, printers, and all
connected subsystems. The system must report an event in case of an exceptional
state.
Specified product: Siemens / Desigo CC or similar
System analysis
Detailed analysis on system and user activities must be available in chronological
order.
Specified product: Siemens / Desigo CC or similar
Scada Platform
The management station must be based on a SCADA platform that is compatible
with the BACnet B-AWS profile. It must permit integration of any building
installation including HVAC and lighting.