User Manual

Network Security Controls
Protected System Configuration Concept
2
A6V11646120_enUS_b_40
37 | 85
Field
System
Hosts
Component /
Process
Port
Port
Configuration
Comment
Protocol
APOGEE
P2
Main
Server,
FEP
APOGEE P2
driver
WCCOAApogee
Drv.exe
2)
TCP: 3001
UDP: 3001
APOGEE
Network
SnapIn
Required for
APOGEE
Ethernet
Microserver
(AEM)
APOGEE
P2
Main
Server,
FEP
APOGEE P2
driver
WCCOAApogee
Drv.exe
2)
TCP: 5033
UDP: 5033
APOGEE
Network
SnapIn
Required for
APOGEE
Ethernet networks
APOGEE
P2
Main
Server,
FEP
APOGEE P2
driver
WCCOAApogee
Drv.exe
2)
TCP: 5441
UDP: 5441
No
Required for
APOGEE
Ethernet networks
(diagnostic
channel)
BACnet
Main
Server,
FEP
BACnet Driver
WCCOAGmsBA
Cnet.exe
2)
UDP:
47808
3)
BACnet
SnapIn
Communication
with BACnet field
systems
(APOGEE
BACnet, Desigo
PX, Desigo TRA,
FS20)
BACnet/I
P
Modbus
Main
Server,
FEP
Modbus Driver
WCCOAmod.exe
1)
TCP: 502
Modbus
SnapIn
Communication
with Modbus TCP
devices
Modbus/
TCP
OPC
Main
Server
OPC Driver
WCCOAopc.exe
1
)
TCP: 135
UDP: 135
No
OPC/TC
P
OPC
Main
Server
OPC Driver
WCCOAopc.exe
1
)
TCP:
variable
5)
Windows
Registry
OPC/TC
P
Simatic S7
Main
Server,
FEP
Simatic S7 Driver
WCCOAs7.exe
1)
TCP: 102
No
Communication
with S7 PLC (also
for Siclimat-S7
devices)
Simatic
S7
Protocol
SNMP
Main
Server,
FEP
SNMP Driver
WCCOAsnmp.ex
e
1)
UPD: 161
4)
SNMP
Network
Configuration
SnapIn
SNMP/IP
SPC
Main
Server,
FEP
SPC Driver
WCCOASPC.exe
2)
TCP:
50000
UDP:
50000
SPC Driver
SnapIn
EDP Receiver Id
Port
XNET
Main
Server,
FEP
XNET Driver
NCCGMS.exe
2)
TCP: 1977
XNET Driver
SnapIn