Installation Instructions

12
Figure 8
Positioning the Alarm LED
NOTES:
1. When installing FD-UL detectors in a FireFinder-XLS panel, use the
following panel versions
PMI ver 10.02 or later
Zeus ver 10.02 or later
DLC ver 06.01 or later
2. ABHW-4SZ alarm current can ONLY be powered from auxiliary power;
device loop power is used for the control circuits in ABHW-4SZ.
3. When the audible base ABHW-4SZ works with FD-UL series detectors, up
to six tone patterns and two volume levels can be selected by user with
system configuration tool.
4. When the audible base ABHW-4SZ works with H-series detector, a fixed
85dB tone is provided and only two tones can be selected (Steady and
Temporal 3). Steady: without a jumper at terminals 3 and 4; Temporal 3:
terminals 3 and 4 are shorted with jumper.
5. For additional information on the modules used in an individual system,
refer to the Installation Instructions for that particular module or contact your
authorized Siemens Industry, Inc. representative.
BASE
MOUNTING
HOLES
ALARM LED LOCATION
WITH DETECTOR
INSTALLED IN BASE