Installation Instructions

Recommended wiring for FHA2054
6
12 | 16
Building Technologies
A6V10590197_en
--
_a
Siemens Industry, Inc.
-
02
-
26
6 Recommended wiring for FHA2054
The low-level audio input can
1
be used for non-emergency applications such as
background music or convenience paging. A wiring example is shown below.
Figure 7: FHA2054 wiring application with single booster amplifier panel
* FACP = Fire alarm control panel
NOTICE
1
Nonapplicable for Canadian installations
Usage not conform with the National Building Code of Canada
Note that for Canadian installations, playing Background music in a fire alarm
or voice communication system is prohibited, per Section 3.2.4.18 of the
National Building Code of Canada.
The inputs of the FHA2054 audio transformer kit cannot be cascaded together as
this will degrade the low-level audio input by introducing excessive load on the
circuit. If a low-level audio signal needs to be transmitted, one output of the booster
amplifier mainboard can be used to send the audio signal to other booster amplifier
mainboards through the high-level input as shown in the figure below.
FACP* voice
Low-level
audio input
UL listed
EBA2001
High-level
audio output
(25 V / 70 V)
Booster amplifier mainboard
EBA2004
FHA2054