Fire Alarm Control Panel Model FC2005 Installation, Operation and Maintenance Manual A6V10333722_m_en_-2021-12-28 Smart Infrastructure
TABLE OF CONTENTS INTRODUCTION ........................................................................................................................................................1 CONTROL PANEL LIMITATIONS ........................................................................................................................1 PREFACE ..............................................................................................................................................................
City Tie Circuits ................................................................................................................................................ 16 DACT Circuits ................................................................................................................................................... 17 CONTROL PANEL OPERATION ........................................................................................................................... 18 OPERATION INSTRUCTIONS .......
DACT Wiring..................................................................................................................................................... 49 PROGRAMMING THE CONTROL PANEL ............................................................................................................ 50 KEYPAD PROGRAMMING ................................................................................................................................ 50 PC PROGRAMMING ........................................
INTRODUCTION CONTROL PANEL LIMITATIONS This control panel may not show an alarm condition without compatible initiating devices (smoke detectors, etc.) and notification devices (horn, strobes, etc.) connected to it. Electrical ratings of the initiation and notification appliances must be compatible with the electrical ratings of the control panel and must be properly interconnected.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below.
PREFACE Along with the use of this instruction manual, the appropriate following standards and the manufacturer's instructions for initiating and notification devices should be used to install and maintain a functioning fire alarm signaling system. National Electrical Code, NFPA 70; National Fire Alarm Code, NFPA 72; Clean Agent Fire Extinguishing Systems, NFPA 2001. For other standards that may apply contact the authority having jurisdiction.
d) The FCC Registration Number [US:02XAL00BFCM901] Items (b) and (d) are indicated on the label. The ringer equivalence number (REN) is used to determine how many devices can be connected to your telephone line. In most areas, the sum of the RENs of all devices on any one line should not exceed five (5.0). If too many devices are attached, they may not ring properly.
DESCRIPTIONS FC2005 SYSTEM DESCRIPTION The FC2005 is a compact but powerful standalone fire alarm control panel. It features advanced addressable fire detection, keypad and offline programming, notification circuits, a 160 by 64 dots LCD display and event history retention capability.
Power Supply A 26 V (nominal) power supply provides all operating power to the control panel for both standby and alarm conditions. Batteries no smaller than 12 AH and no greater than 19 AH for US, and no smaller than 12 AH for Canada must be used to meet code requirements.
Battery Sets The FC2005 control panel can only use rechargeable sealed lead-acid batteries for back-up power. The battery charging capacity is 12 Ah for Canada and 12 - 18 Ah for US. Remote Printer Module (FCA2018-U1) The Model FCA2018-U1 is a Universal Fire Protocol module that interfaces to a parallel printer. It must be located where there is access to the fire system’s serial interface circuit network. Up to 2 FCA2018-U1 may be addressed by the communication circuit.
The information of the rest annunciators is displayed in the below table: Product Zones System status LEDs FT2008-U1/R1 16 7 FT2009-U1/R1 32 7 FT2018-U1/R1 16 6 Buttons Audibles On/Silenced Acknowledge Signal Reset Lamp Test Audibles On/Silenced Acknowledge Signal Reset Lamp Test N/A FT2019-U1/R1 32 6 N/A Up to 8 annunciators may be addressed by the communication circuit. Each annunciator requires connection to the Serial Interface circuit on the mainboard.
SLC ADDRESSABLE DEVICES Smoke Detector The control panel processor sends the sensitivity settings to the detectors and polls the detectors for their status. The detector determines normal, trouble and alarm conditions and communicates the conditions to the control panel. Variable Thresholds - The detectors can be set to operate in various pre-programmed profiles, depending on the environment where the detectors are used.
the system configuration tool. When users need to disable the audible base, they will need to select the “disable audible base” option. When the audible base ABHW-4B and ABHW-4S is used with H series detectors, it can be programmed to 1 output channel, and only 2 tone patterns (steady, temporal 3) can be selected using the system configuration tool. When users need to disable the audible base, they will need to select the “disable outputs” option.
EVENT HISTORY The control panel includes a non-volatile memory recording 1000 system events. Identified alarm, trouble, supervisory, status and other significant events will be recorded along with the date and time of occurrence. The history event log can be viewed at the main system display by operating menu controls from the panel. The history event log can also be transferred from the panel to a computer using the FXS901-U2 system configuration tool.
GENERAL DESIGN FEATURES Environmental The FC2005 panels and subassemblies are suitable for use in a dry, indoor or protected location. Power Limiting The AC power connection, battery wiring and four system status relays are not power limited. All other circuits leaving the control panel meet the requirements for power limited circuits when installed in accordance with the National Electrical Code and local requirements. Ground Fault Detection The control panel provides system ground fault detection.
Device type supervision: If the device type identifier reported by an addressable detector or module does not agree with the configuration, the system reports a trouble condition. Device address supervision: The system checks that all configured devices on the addressable device circuit respond to an address poll. The system reports a trouble condition if the following conditions are detected: ◼ ◼ ◼ ◼ ◼ Configured device is missing. Unconfigured device is installed.
GENERAL SPECIFICATIONS Operating specifications for the FC2005 are as follows: Environmental Operating temperature - 32 – 120 F (0 – 49 C) Relative humidity - Up to 93% @ 90 F (32 C) To be installed in an indoor dry protected environment only Primary Power Supply (FP2011-U1) Input: 120 VAC, 60 Hz or 240 VAC, 50 Hz @ 2.0 A max. Supervised Output: 26 VDC @ 6.5 A max. Max current: 6.5 A (2 hours max.) Filtered and Regulated Secondary Power Supply 24 V lead-acid battery set Max. charged voltage: 27.
Status Relays Non-power limited One programmable relay Three non-programmable relays: Trouble, Supervisory, Alarm Contact rating: 2 A, 30 VDC maximum Form C contact Notification Appliance Circuits Power limited Supervised Current Draw Maximum Line Resistance 2.5 A 3.2 Ω 2.0 A 4.0 Ω 1.5 A 5.3 Ω 1.0 A 8.0 Ω 0.5 A 16.0 Ω Alarm voltage: 16 to 32 VDC Maximum ripple: 0.1 VAC Used for special application only Two Class B or one Class A Total Max. Current: 2.
Max. 50 addressable devices City Tie Circuits Supply Input: Voltage: 26 VDC 18 – 28 VDC for battery Current: Max. 0.4 A Supervised Output: City Tie-Output 1 Normal output voltage: 19-28 VDC (open circuit condition) Supervisory current: 1 mA Maximum trip current: 400 mA Maximum coil plus wire resistance: 22.
DACT Circuits Power limited Supervised for short or open circuit conditions Compliance to FCC part 68 Support RJ31X connection Compatible Digital Alarm Communication Receiver (DACR) list Manufacturer Model Number Communication Technology Telguard DMP NAPCO Starlink NAPCO Starlink NAPCO Starlink NAPCO Starlink NAPCO Starlink NAPCO Starlink B465 DSC DSC TG-7FS ICOMSLF SLE-LTEVI-FIRE SLE-LTEVI-CFB SLE-LTEVI-CFBPS SLE-LTEAI-CFBPS SLE-LTEAI-CFB SLE-LTEAI-FIRE Bosch TL300CF LE4010CF GSM IP IP/GSM IP/GSM IP/G
CONTROL PANEL OPERATION OPERATION INSTRUCTIONS Standby Condition In normal standby operation, the green AC POWER ON LED should be illuminated and no other indicator operating. The display will show the system label and the current time. Alarm Conditions ALARM When the system detects an alarm condition, the alarm LED activates (ON – flashing) and the local panel buzzer activates in a specific pattern to indicate an alarm condition.
Unmanned status. After logged in as L2/L3 user, user can select Unmanned item in operate menu to enter Unmanned status and bypass all on-going PAS alarms. PRE-SIGNAL ALARMS (not supported under ULC standard) Activation of an initiating device in an input group programmed for PRE-SIGNAL activates the Alarm LED, LCD display, and the local panel buzzer. System and user-programmed outputs activate immediately except NAC.
If the panel is configured for Supervisory/Trouble Resound Reminder, and the supervisory condition is not corrected, the local panel buzzer will re-activate when the reminder timer has relapsed to remind users of the supervisory condition. If the FC2005 is configured as “Supervisory self-restoring”, the system shall return to the “System Normal” status when the supervisory condition is restored unless there are additional events on the system.
ADDITIONAL OPERATING PROCEDURES In addition to the basic fire alarm instructions above, several features are included to facilitate maintenance and increase the versatility of the system. The following are procedures used to initiate these functions. Lamp Test When selected, Lamp Test activates LCD, the buzzer and turns on all the LEDs on the user interface, then back to its previous state. To initiate a Lamp Test, proceed as follows: Press "MENU". On the MENU display, select "Oper".
FC2005 OPERATING INSTRUCTIONS Alarm Operation In case of alarm, the Alarm LED flashes, LCD displays alarm conditions and the panel buzzer sounds in a distinct alarm pattern. Local audible and visual signals and remote alarm signals operate. When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are accounted for and notify the Fire Department to advice of the alarm and/or verify that an automatic signal has been received at the Fire Department.
Frame these instructions and mount them near the control panel for operator reference. FSD901 OPERATING INSTRUCTIONS Alarm Operation In case of alarm, the Alarm LED flashes, LCD displays alarm condition and the buzzer sounds. Local audible and visual signals and remote alarm signals operate. When an alarm occurs, proceed according to the established emergency plan.
CONTROL PANEL INSTALLATION PARTS SUPPLIED – FC2005 FC2005 Enclosure Assembly FH901-U2 (Black) / FH902-U2 (Red) FC2005 Main Board Assembly FCM901-U2 / FCM901-L2 Power Supply Assembly FP2011-U1 FC2005 City Tie Module Assembly (optional) FCI2020-U1 FC2005 Configuration Kit (optional) FXS901-U2 FC2005 Spare HW Kit FX901-S1 1.
3. FC2005 Configuration Kit Package Description FC2005 Configuration programming disk FC2005 Commissioning cable (FCA3600-A1) Qty 1 1 4.
CAUTIONS 1. Remove the printed circuit boards for any procedure that may cause dust, metal shavings, grease (or such matter that may affect the operation of the boards) to get in contact with the units. 2. Disconnect all sources of power prior to installing or removing modules, connecting or disconnecting wiring.
There are two key-shaped cutouts on the top of the backbox. Make sure the end with the two key-shaped cutouts is on top when installing the backbox. The front door can be removed from the enclosure for more convenient installation. 2. Hinge axis can be removed 1. Remove the hinge axis lock pin Drill the two holes located in the previous step and screw in the top bolts, leaving a small gap between the wall and each top bolt.
FC2005 Enclosure Mounting Pictures 28
1 7/16” FC2005 Installation Size 1 1/32” 16” 1 7/16” 2 5/16” 1 31/32” 2 5/16” 13 25/64” 1 31/32” 2 5/16” 1 3/16” 6-2 3/8” 1 23/64” 1 61/64” Remove Knock-Outs Prepare the enclosure for electrical wiring by breaking out the appropriate conduit entry points. Segregation is required between power limited and non-power limited conductors. In order to maintain the minimum separation, follow the wire routing illustrated on page 31.
Power Supply FP2011-U1 Mounting Secure the power supply to the back of enclosure using the four provided #8-32 x 3/8 screws. AC Input terminals must be located at the right side of the enclosure.
Ground Wire Installation Install one end of the grounding cable on the enclosure back box. Enclosure back box Install the other end of the grounding cable on the enclosure outer door.
Battery Installation Use the battery calculation chart to determine the battery size. Place the batteries in the space provided in the bottom of the backbox. Secure the battery bracket (if required) to the back of enclosure using the eight provided #8-32 x 3/8 screws. Recommended battery size: Length: 5.94 inch, Width: 3.86 inch, Height: 3.7 inch. A separate enclosure must be used if a battery set larger than 12 AH in the FC2005 is required.
Optional City Tie Mounting Secure the city tie to the main board using the two provided #4-32 x 3/8 screws. Spacer T1 Detail A T2 2 #4 screws T3 City tie module Connect the city tie cable between city module and main board.
Main Board Assembly Installation Secure the main board assembly to the enclosure using the four provided #8-32 x 3/8 screws 4 #8 screws Earth Cable Installation Connect the earth cable to the backbox and connector at the upper left corner of the main board.
SYSTEM WIRING Before connecting the field wiring, check the wiring for opens, shorts, grounds and stray voltages. WARNING Damage may result if a high voltage insulation tester is used on wiring while connected to the control panel. Terminate the field wiring to the main board in accordance with the diagrams in System Wiring Section. All wiring must be in accordance with local codes and the National Electrical Code. AC Connection Wire the AC supply to power supply on the back of enclosure.
Control Panel Wiring Overview In compliance with NEC Article 760 and UL 864, all power limited fire protective signaling conductors must be separated a minimum of 1/4 inch from all of the following wiring located within a control panel: Electric light Power Class 1 or non-power limited fire protective signaling conductors To meet these requirements, the following guidelines must be observed when installing modules and wiring to this control panel.
Wiring Separation All high voltage and non-power limited wiring must be kept separate from power limited wiring. A separation of at least 1/4 inch must be maintained with high voltage and non-power limited wiring running in separate conduit openings from power limited wiring.
Power Supply and Battery Wiring Route all high voltage and non-power limited wiring together and away from power limited wiring. Use the battery calculation chart to determine battery size. AC connection is done on power supply.
Keep All Non-Power Limited WiringCity Separate from Power Limited Wiring P2 device Auxiliary power Series Interface tie and NAC DACT Status Relays Power limited T_NO T_CO T_NC A_NC A_CO A_NO U_CO U_NO U_NC S_NO S_NC S_CO DACT PORT1 DACT PORT2 N_AN N_AP N_BN N_BP LL_SN LL_SP CT_N CT_P EARTH lease line PR_B GND1 PR_A EARTH Circuit GND1 SE_A SE_B X1_N X1_P output X2_N X2_P EARTH S_AN S_AP EARTH S_BN S_BP circuit Non power limited Wiring terminals located on top of main board Status
The auxiliary power of control panel supervises only the short circuit and ground circuit. The open circuit is not included. To supervise the open circuit, a PAD-5 device power must be used. When using an annunciator with the 50pt. panel, use the non-resettable power supplied from the Fire Alarm Control Panel (FACP). When the annunciator is located too far from the FACP use a Battery backed up UL approved Power Supply to ensure continuous and proper operation.
NAC Wiring Two individual NACs are provided and the polarity shown is when the NAC is activated. Power Limited Supervised Current Draw Maximum Line Resistance 2.5 A 3.2 Ω 2.0 A 4.0 Ω 1.5 A 5.3 Ω 1.0 A 8.0 Ω 0.5 A 16.0 Ω Alarm voltage: 16 to 32 VDC Maximum ripple: 0.1 VAC Used for special application only Two Class B or one Class A Total maximum current: 2.
NAC ….. N_AN N_AP N_BN N_BP Serial Interface Circuit (UFP) The serial interface circuit can address up to 8 devices, which includes annunciators and printers. Up to 2 printers can be addressed. Devices on the circuit may be connected up to 4000 feet from the control panel. Serial Interface Circuit (UFP) (PR_A, PR_B) RS-485 level Wire type - Twisted pair for data EARTH – Shielding earth connection Wire resistance - 50 Ohm/line (Max. 4000’) Supervised, Power limited.
43
Serial Remote Device Wiring Overview When connecting devices on the Serial Interface Circuit (UFP), the data wires must be daisy chained and with no T-taps to preserve the integrity of the data. The following diagrams show the proper wiring.
SLC Addressable Device Circuit These devices are polled by the control panel every few seconds and input or output functions communicated to determine device status or function. The control panel monitors all device addresses for alarm and trouble conditions. Addressable Device Circuit Class B (DCLB) or Class A (DCLA) or Class X (DCLC) Operation Max. 50 devices can be connected to the circuit. Wire Resistance – Max.
SLC Addressable Device Wiring Diagrams Refer to the instruction sheets packed with each device. Detectors and modules may be wired together according to several NFPA defined wiring classes. The wiring class that is appropriate for your installation should be determined from the relevant building codes and the local Authority Having Jurisdiction. Class B wiring permits the branching of circuit connections.
SLC ADDRESSABLE DEVICE CIRCUIT WIRING / OPERATION COMPARABLE TO NFPA CLASS A (or ULC DCLA) Class A (DCLA) provides redundant communication paths. SUPERVISED POWER LIMITED PORT-A - S_AN + S_AP ISOLATOR MODULE SEE NOTE SEE NOTE PORT-B - S_BN SEE NOTE SEE NOTE + S_BP ISOLATOR MODULE ISOLATOR MODULE SEE NOTE SEE NOTE SEE NOTE Notes: • Siemens SLC Devices: Detectors, Monitor Modules, or Control Modules up to a maximum of 50 devices. A maximum of 20 devices recommended between Isolator Modules.
SLC ADDRESSABLE DEVICE CIRCUIT WIRING / OPERATION COMPARABLE TO NFPA CLASS X (or PABE DCLC) CLASS X (DCLC) provides redundant communication paths. SUPERVISED POWER LIMITED PORT-A - S_AN + S_AP SEE NOTE SEE NOTE SEE NOTE PORT-B - S_BN SEE NOTE SEE NOTE + S_BP ISOLATOR MODULE SEE NOTE SEE NOTE SEE NOTE SEE NOTE Notes: • Siemens SLC Devices: Monitor Modules, or Control Modules up to a maximum of 50 devices.
Optional City Tie/Leased Line FC2005 provides one city tie or one leased line to connect with local energy and polarity reversal. City tie and Leased line Supervised, Power Limited City tie CT_P + CT_N - Master Box LL_SP LL_SN Leased line CT_P + leased line CT_N - detection circuit LL_SP + leased line LL_SN - detection circuit alarm/trouble supervisory DACT Wiring FC2005 will provide two connections to Public Switched Telephone Network (PSTN).
PROGRAMMING THE CONTROL PANEL KEYPAD PROGRAMMING Customized programming of the control panel may be accomplished through the keypad included in the control panel. PC PROGRAMMING Programming the panel may also be done by a temporary connection to the programming port with a computer. This is the recommended method to program the panel. The Siemens FXS901-U2 software is available to allow programming the control panel by connection to a Personal Computer (PC) with an USB port.
MAINTENANCE GENERAL The FC2005 provides maintenance functions to allow for the setting and controlling of various features in the system. The maintenance functions are protected by a four digit password. To access the maintenance features press the “MENU” button and select Login item in the View menu, enter the four digit code when prompted and then press “OK”. FC2005 Maintenance is separated into two levels. The user can enter a different password to enter different levels.
QUICK TEST The Quick Test mode makes it fast and easy to test a system by eliminating the need to disconnect panel from remote connections to the Fire Department or other monitoring stations. In this way, operator can test all devices locally without annunciating any condition to remote connections. To configure the Quick Test parameters, enter L2 user level and navigate to the Quick Test item in the Operate menu.
This page is left intentionally blank.
APPENDIX-A: REFERENCE DATA This appendix provides reference for the following topics: Wire selection guides Battery size calculations WIRE SELECTION GUIDES Resistance of Solid Copper Wire AWG Ohm per Thousand Feet* 18 8.08 16 5.08 14 3.19 12 2.01 *NEC Chapter 9, Table 8. Addressable Device Circuit Wire Selection Guide Each addressable device circuit must meet the following requirements: Total loop resistance – 50 Ohm maximum with 50 devices Total loop capacitance - 0.5 uF max line to line per km and 1.
BATTERY SIZE CALCULATIONS System Current Draw Break down System Current Draw Components Main board NAC SLC Auxiliary power City tie module Standby (A) 0.1590 0 C2 C4 0.0017 55 Alarm (A) 0.1864 C1 C3 C5 0.
SLC Current Draw Break down SLC Current Draw Components HFP-11 HFPO-11 HFPT-11 OOHC941 OOH941 OH921 OP921 HI921 FDCIO42 HMS HTRI-S HTRI-D HTRI-R HZM HCP ILED FDOOTC441 FDOOT441 FDOT421 FDO421 FDT421 ABHW-4B ABHW-4S XTRI-R XTRI-D XTRI-M XTRI-S ILED-XC ILED-XW TSM-1X PAD-5-MB PAD-5-CLSA PAD-5-CDC Pull station Standby (A) 0.00140 0.00140 0.00140 0.00075 0.00068 0.00030 0.00030 0.00028 0.00120 0.00140 0.00140 0.00140 0.00140 0.00140 0.00140 0.00140 0.00075 0.00068 0.00030 0.00030 0.00028 0.00030 0.00030 0.
Battery Size Total Standby Current (from above) Total Alarm Current (from above) Hours of Standby Required per NFPA 72 Standard (4, 24 or 90) A X Hours = 5 Minutes of Alarm AH for Alarm Operation per UL 4 Minutes of Alarm plus 12 hours reduced time annunciation per UL (CO monitoring UL 69.2.5 Exception #2) 30 Minutes of Alarm Operation per ULC A X Hours = A.H. for A.H. for Standby Alarm + AH for Standby Calculated A.H. = De-rating Factor (20% derating per UL864) X 1.2 A.H.
APPENDIX-B: COMPATIBLE DEVICES FC2005 Desigo UL FC2005 Desigo ULC FC901 Cerberus UL FC901 Cerberus ULC DEVICES FOR ADDRESSABLE DEVICE CIRCUITS x means supported.
59 FC901 Cerberus ULC FC901 Cerberus UL FC2005 Desigo ULC FC2005 Desigo UL 8710 8713 8712 Manual pull station 8700-S Single action manual pull station 8700-D Dual action manual pull station 8700-M Single action metal manual pull station Line modules 8702 Single input interface module 8703 Dual input interface module 8704 Single input interface module with relay 8701 Mini single input interface module 8706 Intelligent control point 8705 Conventional zone module 8726C Intelligent remote indicator ceiling
x x x x x x x x x x FC901 Cerberus ULC FC901 Cerberus UL FC2005 Desigo ULC FC2005 Desigo UL STRI-M SZM SLIM SFPO-11 SFPT-11 SFP-11 ILED-SC ILED-SW Other PAD5 x x x x x x x x x x Notes: 1) Siemens SLC devices, detectors and modules, up to a maximum of 50 addresses may be used. 2) For specific wiring and installation information, read the instructions provided with each device.
UFP devices Siemens Cat. No.
APPENDIX-C: TROUBLESHOOTING DEFINITIONS FOR EVENT HISTORY ENTRIES A.
B.
APPENDIX-D: ALARM VERIFICATION A Smoke detector goes into alarm. (LED on device turns to red) AB Retard-Reset Period, FACP senses detector in alarm and retards alarm signal. AC Retard-Reset-Restart Period – FACP reports alarm verification event and the supervisory LED is lit on. In this period. no alarm event is reported on FACP. The duration of this period is adjustable, ranging from 1 s to 60 s. The default value is 60 s.
Below devices are compatible with the Alarm verification function: Supported Devices OP921 OH921 OOH941 OOHC941 HFP-11 HFPO-11 SFP-11 (Only available in Canada) SFPO-11 (Only available in Canada) HZM SZM (Only available in Canada) PAD-5-CDC module Supported Version (Or Above) 17 17 27 27 Depends on the device Retard-ResetRestart Time Range Configurable: 1~60 s Confirm Time Range Configurable: 1~60 s Depends on the device Depends on the device 65 Configurable: 60~125 s Alarm Verification Execution P
APPENDIX-E: APPLICATION SPECIFIC DETECTION Application Specific Detection (ASD) allows the system designer to program a detector’s sensitivity, pre-alarm threshold, and other alarm-related parameters using English descriptions of the detector's environment (application). This eliminates the need for detailed knowledge of smoke detector terminology and operation.
APPENDIX-F: TESTING/MAINTENANCE If the system is connected to the fire department, etc., or actuates an internal system, disarm the appropriate outputs before servicing to prevent actuation. Notify the fire department and personnel at your facility that a System test is being performed so that any alarm sounding can be ignored during the test. Notify the fire department before resetting the system.
APPENDIX-G: LCD, CONTROLS AND INDICATORS The FC2005 has a buzzer, 7 LEDs, 4 navigational push buttons, 4 push buttons, alphanumeric keypad, 3 menu control buttons (menu, cancel and ok) and a communication port connector.
Communication Port Connector The communication port is connected to the USB port of the computer that has the FXS901-U2 programming tool. This is used to upload and/or download panel configuration if this method of programming is used. The computer must be disconnected from the panel if not in use.
OFF Flashing Audible On (US) 7 Alarm Signal Activation (Canada) Steady ON Red OFF There is no Ground Fault event in system. There are ground fault events in system, but some of them have not been acknowledged. The LED 7 can only be steady on when any of the following conditions are met: 1. There are activated NACs and some of them are not silenced. 2. There are silenceable devices activated and some of them are not silenced. The LED 7 will be OFF when above conditions are not met.
FXS901-U2 programming tool. 16 Menu Press Menu button for PMI operation. 18 Four-way button Press A four-way button for menu navigation.
LCD Display A 160 by 64 dot LCD display is used to display information such as event types, event amount, event location, user level, releasing timer, etc. A back light is included in the display to assure visibility in dim light. To save power, the back light is only activated during a reported event or on operation of a display control button. The LCD display has altogether 7 lines, and each line displays 26 characters. It displays two events at a time.
LCD display in US The text displays in the below graphic and table is just an example. The actual display corresponds to the actual situation. Line Current text Description 1 Alarm 01/03 L1 Current event type Current event/total events Access level 2 V Possible display: V: The event is acknowledged !: The event is unacknowledged Event location Event type Possible display: I/O (in or out flag) Possible display: V: The event is acknowledged !: The event is unacknowledged User defined (Max.
APPENDIX-H: OUTPUT FEATURES Output Activation- and Deactivation- Delays Each output device has a selection for Activation delay and Deactivation delay when it is installed in the configuration. The Activation delay refers to the delay in which the output will activate after the reception of its activation command. If the Activation delay is set to 0 (default setting), the output immediately activates.
APPENDIX-I: PAS / PRE-SIGNAL PAS (Positive Alarm Sequence) and Pre-Signal features allow the user to delay the activation of the audibles, strobes and other output devices when an initial alarm is detected. Output can be interlocked by zones. When an initial alarm is detected, all outputs except remote devices (off-premises devices like general relays and city tie) associated with PAS Zone (Zone configured with PAS feature) will be activated immediately.
Pre-Signal When an alarm causing device in a Pre-Signal input group is initiated, the alarm condition is reported at the panel. Its associated NACs are not activated until the programmed investigation delay has relapsed or 2nd Alarm is initiated anytime during the Pre-Signal delay time (see figure below).
APPENDIX-J: DACT INFORMATION OVERVIEW The DACT (Digital Alarm Communicator Transmitter) is an optional module for the FC2005 control panel that allows transmission of event information to a remote receiver at a monitoring station using a dial-up modem connection. These events are transmitted in one of the following formats: ◼ ◼ ◼ SIADCS 8 SIADCS 20 ADEMCO Contact ID A few aspects of the operation of the DACT are clarified below.
To configure an event to be reported to Account 1 and Account 2, set it to Must report on both. If the event needs to be reported to either Account 1 or Account 2, set it to Can report on both. If it has to be reported to Account 1, but only needs to be reported on Account 2 if Account 1 is temporarily out-of-order, set the event to Must Report on Account 1 and Can Report on Account 2. Following are examples for illustration purposes.
Scenario 2 – Must/Can Alarm Event is set to Must Report on Account 1 and Can Report on Account 2. Panel fails on Account 1 the first time. Step 1: Panel goes into alarm. Step 2: Panel tries to send event to Account 1, but is unsuccessful. N Account 1 Account 2 Step 3: Panel keeps trying to send event to Account 1 until the programmed Number Of Attempts has been reached. Step 4: Panel switches to Account 2 and attempts to transmit, but is unsuccessful too.
Scenario 3 – Must/Can Alarm Event is set to Must Report on Account 1 and Can Report on Account 2. Panel succeeds on Account 1 the first time. Step 1: Panel goes into alarm. Y Account 1 Step 2: Panel tries to send event to Account 1 successful. Account 2 Step 3: Panel does NOT attempt to send event to Account 2, since Account 2 is set for Can Report and the event was transmitted to Account 1 successfully. Done.
Scenario 4 – Can/Can Alarm Event is set to Can Report on Account 1 and Account 2. Panel succeeds on Account 2 before Account 1. Step 1: Panel goes into alarm. Step 2: Panel tries to send event to Account 1, but is unsuccessful. N Account 1 Account 2 Step 3: Panel keeps trying to send event to Account 1 until the programmed Number Of Attempts has been reached. Step 4: Panel switches to Account 2 and successfully transmits the event. Account 1 Y Account 2 Done.
DACT COMPATIBLE ALARM COMMUNICATORS The FC2005-U2 /-R2 DACT is also compatible with Alarm communicators that utilized different communication technologies (IP and GSM technologies) to connect to compatible Receivers using compatible protocol listed within this documentation.
WIRING DIAGRAM FOR DSC’S TL300CF AND LE4010CF CONNECTION, INCLUDING TROUBLE REPORTING ROUTE 83
LE4010-CF Configuration (Reference from DSC Installation Manual) 84
TL300-CF Configuration (Reference from DSC Installation Manual) 85
LE4010-CF & TL300-CF Power Supply Wiring Configuration (Reference from DSC Installation Manual) The ACT shall be connected to Input 1 of the transmitter and transmission delay is to be configured via CONNECT 24. The LBT and TEST shall be connected to FACP’s trouble inputs. The outputs are active low (switched to ground) and shall be connected via listed supervision relay (suggested model: DSC, RM-2 or RM1C).
APPENDIX-K: DRIFT COMPENSATION The H-Series optical detector cannot implement drift compensation on its own. Drift compensation is the panel’s responsibility. While the system is running, the detector sends its chamber real-time values to the panel periodically and does not do compensation by itself. For the first hour after a panel startup, the panel will check the detector chamber values every 10 minutes. After that, the panel will check the chamber reading every 24 hours.
APPENDIX-L: RELEASING OPERATION Configure: • Set up a countdown time for the releasing operation to start when the releasing control condition is satisfied. • Set up the activation time for the NAC/Output channel: ReleaseSync: operate simultaneously with the releasing channel. Immediately: operate once the releasing control condition is satisfied. • When the releasing control condition is satisfied, the countdown time starts.
Releasing indication configuration in Canada For Canadian applications, LEDs on FT2018 or FT2019 annunciator shall be configured to indicate pre-discharge, discharge, abort in alarm condition and “invalid abort” trouble in normal standby condition. Following is an example of configuration: Preconditions: • Releasing control configuration • LED control configuration Area configuration Under the property for Area, there is a setting named “Function”.
Release Trouble Indication 1 2 Release circuit trouble Yellow steady Releasing circuit trouble Off Releasing circuit is normal Invalid abort trouble Yellow steady Abort switch activation normal standby condition No invalid abort switch activation Off 90
APPENDIX-M: GLOSSARY AC Power Fail. Refers to a condition in which AC power loss is detected by the system. Alarm Signal. A signal indicating an emergency requiring immediate action, such as an alarm for fire from a manual station, a waterflow alarm, or an automatic smoke detector. Signal Silence Inhibit. An option that prevents an operator from silencing the notification appliances for a preset period of time. Alarm System.
fan restart usage has higher priority than the OFF time delay and will therefore immediately deactivate the hold-thru reset outputs. DeactPersistDevs (Deactivate Persistent Devices). Used to deactivate the outputs when the outputs are deactivated by control logic and the “Hold-Thru Reset” is configured as “True”. Initiating Device. A manually or automatically operated device such as a manual pull station, smoke detector, heat detector, waterflow switch or tamper switch. Initiating Device Circuit (IDC).
Trouble Signal. An audible signal indicating trouble of any nature, such as a circuit break or ground, occurring in the device or wiring associated with a fire alarm signal. Waterflow Switch. An assembly approved for service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler head will result in activation of this switch and subsequent indication of an alarm condition. Zone. A designated area of a building.
APPENDIX-N: PAD-4 WIRING INSTRUCTION Placeholder for PAD-4 to FC360 wiring instruction so the PAD-4 is able to report troubles back to the FC360.
APPENDIX-O: ISOLATOR SUPPORT Isolator support feature allows a device with an isolator to report alarms as well when a short circuit or open circuit happens on the device. The wiring of the device with an isolator and the setting of its corresponding “Isolator Support” checkbox on FXS901 tool should be consistent, otherwise, the system reports trouble. For example, when a device with an isolator is wired as an isolator module, then the “Isolator Support” checkbox should be ticked as True.
Issued by: © Beijing Siemens Cerberus Electronics Ltd., 2016 Beijing Siemens Cerberus Electronics Ltd. No.1, Fengzhi East Road, Xibeiwang Haidian District, 100094 BEIJING, China Tel. +86 10 64768806 Document no. A6V10333722_m_en_-- Technical specifications and availability subject to change without notice.