Siemens RXL24.1 Room controller CM2N3878en_07
Building Technologies 2015-12-23
The programming LED shows the operational status of the room controller as
follows:
Green flashing
OK, device is in operation
Red ON
Addressing mode (ACS / ETS)
Fault
Orange / green flashing
Parameter download
OFF
No supply voltage
Fault
Service LED disabled by software
Other patterns
Start-up (approx. 5.sec)
Fault
The programming pin is used to identify the controller in the commissioning phase.
Pressing this pin causes the red programming LED to light up and remain on until
identification of the controller is complete.
Once the programming pin has been pressed, the tool overwrites the hardware
address in the room controller.
Terminal covers (RXZ20.1) are available as an option, to protect the connection
terminals from physical contact and dirt. The service LED remains visible when the
terminal covers are in place, and the programming pin can be operated with a
pointed implement. The cable is connected to the room controller by breaking out
the perforated cable entry guide.
3873J02
Removing the terminal cover
Identification number
(unique serial number)
ID in bar-code form, code 128
Protection standard
Temperature range
(0 … 50 °C)
Serial No.
Test date, series
(Z, A, B, C…)
Observe notes
in this document
Activated application
Location
010025CA9900
060215B 513
3878Z04
Options for use of the labeling fields “Appl.” and “Loc.”:
Handwritten identification of the location and the activated application group.
Service LED
Programming pin
Terminal cover
Label
Note