3 876 s RXL Room controller RXL39.1 Communicating room controller for fan-coil applications FC-13 The RXL39.1/FC-13 room controller is used for temperature control in individual rooms.
Use The RXL39.1 room controller is optimized for control of fan-coil systems in individual rooms. The function of each controller is determined by the application software. The controllers are delivered with a fixed set of applications. The relevant application is selected and activated during commissioning using one of the following tools: • "HandyTool" (the QAX34.
Technical design The RXL39.1 controller consists of a housing base, a housing cover and the printed circuit board with connection terminals. The controller also has a tool socket, a service LED and a programming button.
Terminal cover Terminal covers (RXZ30.1) are available as an option, to protect the connection terminals from physical contact and dirt. The service LED remains visible when the terminal covers are in place, and the programming button can be operated with a pointed implement. The cable is connected to the room controller by breaking out the perforated cable entry guide.
Communication The RXL39.
Disposal The device is classified as waste electronic equipment in terms of the European Directive 2012/19/EU (WEEE) and should not be disposed of as unsorted municipal waste. The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. Engineering Bus Topology Cable length Cable type Number of RXL Controllers per Network Bus supply Bus terminator Tree, line, or star NO closed loops Max.
Mounting The room controllers can be mounted in any orientation, and fixed as follows: 80060 80061 Rail mounting The housing base is designed for snapmounting on DIN rails, type EN5002235x7.5 (can be released with a screwdriver) Surface mounting There are four drill holes for screwmounting (see “Dimensions” for drilling template). The housing base is fitted with raised supports. When mounting note the following: • The controller should not be freely accessible after mounting.
Technical data Power supply Operating data Inputs (SELV) Signal inputs D1 … D4 (for volt-free contacts) Measured value input B1 Outputs (SELV) DC 0 … 10 V YC1, YC2, YC3 Supply output G (SELV) Relay outputs Q34 (fan release) Q14 (heater release) Ports/interfaces Interface to room unit Bus Operating voltage Frequency Power consumption with connected field devices Internal fuse External supply line protection Control algorithm AC 230 V +/-10 % 50/60 Hz Max.
Cable connections Connection terminals for signals and power supply Bus connection terminals (plug-in screw terminals) Single cable lengths Signal inputs D1 … D4 Measured value input B1, B2 0 … 10 V outputs YC1, YC2 (valve actuators) 0 … 10 V outputs YC3 (fan) Relay outputs Q14, Q34 Interface to room unit Cable type Bus Tool connecting cable Solid or stranded conductors 0.25 … 2.5 mm2 or 2 x 1.5 mm2 Solid or stranded conductors 2 x max. 1.0 mm2 e.g. YCYM 2x2x0.
GND D2 D3 GND D4 3 19 19 21 21 Q34 Q33 Q14 23 24 25 26 27 G0 4 G 1 Q13 L L N N AC 230 V G0 2 Ni1000 0 ... 10 V YC1 24 ... 230 V 5(4) A 10 A T 3876A08 D1 CE + B2 17 18 CE – B1 10 11 12 13 14 15 16 0 ... 10 V YC3 9 CE + 8 CE – 7 0 ... 10 V YC2 6 CP + 5 AC 24 V 4 CP – 3 N.C. 2 N.C. 1 M Connection terminals Bus QAX...
Connection diagrams Connection of field devices, room unit, bus and power supply G0 G G0 G N1 B1, B2 D1 … D4 Y1 Y2 Q1 Q2 Q3 B3 RXL39.1 LG-Ni 1000 temperature sensor Volt-free contacts (window contact, occupancy sensor, etc.) 0 … 10 V valve actuator heating 0 … 10 V valve actuator cooling (heating / cooling in case of changeover) Controlled fan Power controller (PWM or modulating) e.g. SEM61.4 + SEA45.1, data sheets N5102, N4937 Electric heating QAX… room unit Twisted pair STOP For Q2 (1.8 kW max.
Dimensions Dimensions in mm 3876M01 90 110 35,3 Without terminal covers 3,9 1 62 50 With terminal covers 62 120 35,3 6 3,9 1 161 3876M02 152 80056 100 Drilling diagram 135 Published by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24 www.siemens.