e1103 Section 6 6. 6
6.3 Interface to non-Cerberus Acquisition Equipment
Description
Integration of non-Cerberus equipment may be realised in the following ways:
individual I/Os via CZ10 etc.
normal inputs or control outputs of a satellite control-unit (Sector E) may be used to
interface with individual sensors or actors of a foreign system.
large numbers of I/O via MM7033
the emulation functions contained in this autonomous MUX/DMUX control unit (built in
a standard 19 rack) allows complete integration of incoming signals into the Cerberus
concept.
Functions
CZ10 Potential-free input connections and output relay contacts.
MM7033 see MF/MM7000 Summary
System Limits
CZ10 max. number of elements 96
MM7033 full PLC-functionality (see Summary MF/MM7000)
sum of all inputs/outputs 576 (max. 12 MUX/DMUX units)
system capacity: 20,000 load factors (see PLC-Function Handbook)
Display/Operation no display
operation automatic
HW-Requirements
CZ10 relay board
MM7033 A complete MM7033 is contained a 19 enclosure and comprises the following units:
MPU-board E2H081
comm.unit E1H130
modem K1D081
1..12 MUX-boards E2A041
1..12 DMUX-boards E2A032
Options:
relay board B1G040 (48 relays max. 30VDC/100mA)
line supervision B1G030 (12 lines > 24 MUX-inputs)
SW-Configuration
CZ10 CZ10-connection standard programming procedure in CZ10
DMS7000 Tree Editor SWE100-03
MM7033
Table Editor SWE700FT
Logic Editor (not yet available)
References Equipment Description e988 System Handbook MF/MM7000
PLC-Function Handbook e999 System Handbook MF/MM7000
Notes none
Applications see below
Customer Advantages
MM7033 process image based devices ensure correct intervention under all conditions
PLC-applications may be realised within the DMS-family
no special adaptations to PLCs from other suppliers
all engineering controlled by a single supplier
no problems with responsiblity (when trouble-shooting etc.)
extremely flexible programming tailored to DMS-requirements
Integrated MF/MM-software is included in purchase price of MC70xx.