DMS7000 Danger Management System Terminal systems Document no. e933b Edition 05.
System consoles System console MA7033 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System console MA7003 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Danger Management System DMS 7000 System overview . . . 3 Terminal systems e933b Contents 05.93 Combinations of Central processors and System consoles . . . . . . . . . . . . . . . . . . 4 Compact terminal MT7023 . . . . . . . . . . . . . . . . . . .
System console MA7033 Danger management system DMS 7000 display and operating unit for text and graphics. Guided operation and standardized display. Significant information on alarm location and operating status. Events are displayed geographically in the sequence: general location, building, floor, room.
System console MA7003 Danger management system DMS 7000 display and operating unit for the display of information in plain language. Guided operation and standardized display. Accurate information on alarm location and operating status. Events are displayed geographically in the sequence: general location, building, floor, room.
Danger Management System DMS 7000 System overview Control units for different risk sectors System console MA7033 Central processor MC7033 MC7003 C1 CZ10 C2 Fire Extinguishing Gas Building services C3 System console MA7003 C4 C5 Intrusion Network CZ12 C6 System printer MP... C7 (CC4) CZ4 Intrusion MM7033 Building services & control MUX/DMUX C8 MUX/ DMUXModule Display Control Synoptic Lifts Ventilators Dampers etc.
Terminal systems Combinations of Central processors and System consoles System console MA7033 Central Processor Text & Graphics 4000 names, 4 end interfaces to system console printer End interfaces Front interface Network MC7003 1 MC... ËËÁÁ ËËÁÁ ÁÁ MP... MA70.. /MP.... 2 or 3 Light pen 4 controls remote transmission MF7013 12 programmable Outputs DMUX MN7001 Mouse System console MA7003 Text MC...
Compact terminal MT7023 Compact system terminal with integrated central processor. Danger management system DMS 7000 display and operating unit for the display of information in plain language. Guided operation and standardized display. Accurate information on alarm location and operating status. Events are displayed geographically in the sequence: room, floor, building, and general location.
Compact terminal system MT7023 Standard configuration MP7011 occupied by MP7011 End Interfaces Network Printer MP.... CERBAN/CERLOOP Controls, remote transmission ËË ËË ËË ÁÁ ÁÁ ÁÁ Light pen or Mouse 6 Data and design subject to change without notice / Supply subject to availability Copyright by CERBERUS Ltd., CH-8708 Männedorf 1992 05.
Optional terminal system combinations MT7023 controls remote transmission MT7023 Text & Graphics MP... ÁÁ ÁÁ ËË ËËÁÁ End Interfaces or System console MA7033 Text & Graphics MC... ÁÁÁ ÁÁÁ ËËË ËËËÁÁÁ MP... or Light pen Mouse System console MA7003 Text MC... Printer MP... MC... e933b 05.93 Data and design subject to change without notice / Supply subject to availability Copyright by CERBERUS Ltd.
Functions Monitoring Control Observation Operation Logging Filing Remote transmission Configuration Fire Extinguishing Intrusion Gas Building services Basic Risk sectors: Monitoring Detection-/control elements Detection-/control zones Peripheral equipment: – remote transmission, logging printer etc. Power supply Battery Presence of equipment Communication network – data base: process-/building/equipment image – max.
Operation Basic operation: Buzzer off, Reset via function keys with guided operation Extended operation: From acknowledge, reset etc. ..... to detection/control elements ”on/off; active/inactive” Scroll, turn pages, cursor movement, selection of elements and functions etc.
Description of equipment General technical data microprocessor technology serial interfaces for the communication network CERBAN/CERLOOP provision for monitoring their own emergency power supply ”Local Evaluation Level” equipment The following satellite control units form sub-systems within the Danger Management System DMS 7000 CZ10 Danger detection system control unit handling the risk sectors: fire, extinguishing, gas and building services CZ1–02 Multisector extinguishing control unit can only be con
”Central Evaluation Level” equipment General technical data Processor – data bus, clockrate – main memory – operating system – file system 16/32bit, 8MH3 pulse frequency max. 16M bytes CERTOS real time, multi-tasking MS-DOS 19” module concept MC70.. Central Processor Central processor for central monitoring and control of the danger management system.
MC7033 Network CERBAN or CERLOOP max. 8 serial interfaces CERTER for peripheral equipment – system console MA7003 text – system console MA7033 text und graphics – system console MA7013 text und graphics (CS100 compatible) – printer Disk drive for data security ON/OFF interface controlled in modular concept – max. 4 floppy disk drives (each with 720kB) – max. 2 hard disks 40MB Storage capacity approx.
MF7033 MUX/DMUX, PLC unit (autonomous device) Front interface to the network (CERBAN or CERLOOP) max. 528 potential-free outputs and /or inputs (opto coupler) – output characteristic –Ua = 5 ... 29V DC; Ia = 40 mA – input characteristic –Ue = 17 ... 29V DC; Ie = 1 mA option: relays full PLC functions application max.1000 elements (allocation of output, input & logic) MA70.. System/Operation console system console for information display and guided operation of the danger management system.
MT70.. Terminal System consisting of central processor and system operating console MT7003 central processor MC7003 and operating console MA7003 or MA7033 MT7033 central processor MC7033 and operating console MA7003 or MA7033 MT7023 Compact terminal system central processor MC7023 and operating console MA7023 integrated in one housing max. 2 end interfaces integratable printer MP7011 for emergency operation storage capacity 52,000 nodes (names) integratable DMUX module MF7013 with max. 6 outputs MK70..