DMS8000 MP4.
Data and design subject to change without notice. / Supply subject to availability. © 2011 Copyright by Siemens Building Technologies AG We reserve all rights in this document and in the subject thereof.
About this document...............................................................................................2 Building Technologies Fire Safety & Security Products 1 Introduction .............................................................................................4 1.1 What has been changed in MP4.40 configuration tools ...........................4 2 2.1 2.2 2.3 2.4 2.5 Configuring SiPass Access Control System .......................................5 SiPass integration .................
Introduction About this document Purpose of this document This manual is a guide to the configuration procedures for the integration of SiPass Access Control system in the DMS8000 systems: MM8000 management station and MK8000 OPC server. It is specifically for those individuals responsible for the commissioning of the management station, such as technical project managers, engineers, and commissioning personnel.
Introduction Advanced search criterias: Select Brochure No. and enter the document number to search for (e.g. A6V10062415). Alternatively, select Title and enter the product name (e.g. MM8000). 2. Click Search to start. 3. In the resulting area on the right, select the document type (e.g. Contacts, Data Sheet, etc). For more information such as Siemens news and announcements, visit the STEP Web portal at: https://workspace.sbt.siemens.com/content/00001123/default.
Introduction 1 Introduction This is a guide to the software configuration procedures for the integration of SiPass Access Control systems in the MM8000 Management Station and MK8000 OPC server. For a complete guide to the configuration process, this manual should be used with the DMS8000 Network, Fire and Intrusion Guide, and with the Installation, Configuration and Commissioning manual (ICC) of the specific product. SiPass SiPass is an access control system that monitors and controls access to a site.
Configuring SiPass Access Control System 2 Configuring SiPass Access Control System 2.1 SiPass integration The DMS8000 systems MM8000 and MK8000 can support the integration of SiPass access control system in order to provide for a comprehensive security solution.
Configuring SiPass Access Control System Fig. 1 Adding the SiPass Driver (A) Note: The Composer plug-in #252401 is required. 2.3 Configuration checklist of SiPass Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration procedure that follows. ITEMS NEEDED FOR CONFIGURATION 2.
Configuring SiPass Access Control System Fig. 2 Adding the SiPass subsystem Linking the SiPass subsystem to the SiPass Driver You have now to link the subsystem to the Driver. 1. Select the SiPass subsystem node. 2. Drag and drop it on the SiPass Driver (Fig. 3). A new link node appears. Fig. 3 Linking the SiPass subsystem Setting the SiPass server address In this step, you have to specify the network name or address of the SiPass server. 1. Select the SiPass Subsystem node. 2. Select the Node tab.
Configuring SiPass Access Control System Fig. 4 A Setting the SiPass Server IP address Enter the PC name or IP address of the SiPass server. Note that the value 127.0.0.1 is always valid if the SiPass and MM8000/MK8000 servers are installed on the same PC. Setting up the SiPass configuration structure The SiPass configuration can be imported into Composer in order to allow a fast and seamless alignment process between the two systems. There are two ways to import the configuration: A.
Configuring SiPass Access Control System Fig. 6 Error in connecting to SiPass server 2. Click the Align button. The SiPass configuration data is transferred over the network to Composer. In a few seconds, the configuration status message will show “system is aligned” and the SiPass structure will become available in the Composer tree (Fig. 7). Fig. 7 Transferring SiPass configuration 3. While the connection with SiPass stays active, any modification in the SiPass configuration is detected by Composer.
Configuring SiPass Access Control System Fig. 8 Exporting SiPass configuration Then, the resulting XML file can be imported into Composer with the following procedure: 1. Select the SiPass Subsystem node. 2. Select ToolsImport or right-click the SiPass node and select Import (Fig. 9). Fig. 9 Start SiPass off-line import After a confirmation request, the software presents a browsing window to search for the file to import (a file with extension XML is expected). 3.
Configuring SiPass Access Control System Fig. 10 Selecting the SiPass XML file In a few moments, the SiPass structure is imported, and the node is represented in the Composer tree. Selecting the Import tab results in a page report being displayed. This page contains the detailed logs of the latest import procedure, including all the added (or removed) objects. Customising the SiPass configuration point (MM8000 only) Once the SiPass structure is imported, it is ready to be downloaded.
Configuring SiPass Access Control System Fig. 12 Customising individual SiPass points event setting In the Transaction Extensor tab of each individual point and transaction, customise the log options (e.g.: enabling/disabling properties as in Fig. 13). Fig. 13 12 Building Technologies Fire Safety & Security Products Customising individual SiPass log options 048_DMS_DMS8000_Connectivity_Access_Control_MP4.40_A6V10062451_a_en 06.
Configuring SiPass Access Control System In the Style tab of MM8000 system - Logical configuration - User Data Event and Points - Style, customise the options of a class of points (e.g.: modifying the event settings for the properties of Door points as in Fig. 14). Fig. 14 Building Technologies Fire Safety & Security Products Customising event settings of SiPass Doors 13 048_DMS_DMS8000_Connectivity_Access_Control_MP4.40_A6V10062451_a_en 06.
Configuring SiPass Access Control System 2.5 Further SiPass configuration notes 2.5.1 Tips and hints SiPass configuration (MM8000 only). In order to work with MM8000, the SiPass configuration must include the following: Users authorised on both MM8000 and SiPass have to be configured in both environments with balanced permissions (MM8000 security profiles and SiPass Operator Group functions). In SiPass, the common Operator(s) must be enabled to Automatic Logon as Windows users.
Configuring SiPass Access Control System If the SiPass server does not run on the same PC as MM8000, then specific installation steps are required on the networked PC where SiPass is installed: 1) In the Windows user list, the SiPass PC should include the MM8000 Internal User, by default DMS8000_Proc. Use the same username and password as on the MM8000 PC. Refer to MM8000 ICC Manual (doc.no.A6V10062413_a_en).
Configuring SiPass Access Control System 6. 7. 8. 9. Click the This Account button and then select Browse In the Select User window, select the Advanced button Select Find Now and then DMS8000_PROC Restart the PC From MM8000, select Change Server in the Composer Properties Management window, and select the SiPass server to connect. 2.5.2 SiPass alarm classes In the integrated system, the use of SiPass Alarm Classes requires a special attention.
Configuring SiPass Access Control System The table below presents the possible scenarios and the results for the system operator. Refer to this table for any further needs of Alarm Classes when discussing the issue with SiPass specialists. No Alarm Classes defined Effect in MM8000/MK8000 Effect in SiPass Event generation and transactions (within the documented limitations) as configured in Composer by default. No alarm pop-ups. Registrations in audit trail.
Configuring SiPass Access Control System 2.5.3 SiPass Field Simulator A simulation function is available for simulating the SiPass events in MM8000. However, this is not part of the Field Simulator described in the Appendix A of MM8000 Installation, Configuration, and Commissioning manual (ICC). Activating the SiPass simulator The SiPass field simulator can be activated by selecting the Children tab of the SiPass driver’s parent node and clicking the Simulation checkbox.
Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel +41 41 724 24 24 Fax +41 41 724 35 22 www.sbt.siemens.com Document no. A6V10062451_a_en Edition 06.