MM8000 MP4.
Data and design subject to change without notice. / Supply subject to availability. © 2009 Copyright by Siemens Switzerland Ltd We reserve all rights in this document and in the subject thereof.
Table of contents Building Technologies Fire Safety & Security Products 1 1.1 1.2 Introduction .............................................................................................2 MP4.15-01 at a glance..............................................................................2 MP4.15 at a glance ...................................................................................2 2 2.1 2.1.1 2.2 2.3 2.4 2.5 2.5.1 2.5.2 What’s new in MP4.15 releases ..........................................
Introduction 1 Introduction DMS8000 software MP4.15-01 is now available for MM8000, MK8000, MT8001, and NK8000 products. These release notes provide the characteristics of the new software, including bug corrections and known issues. We recommend reading this document carefully before installing and using the software. This document includes and replaces the release notes published for MP4.15. 1.1 MP4.15-01 at a glance DMS8000 software MP4.
Introduction MK8000 OPC server includes FS20 support. Æ See MK8000 MP4.15 Release Notes MT8001 Terminal MP4.15 aligned with Composer and NK8000 MP4.15. Æ See MT8000 MP4.15 Release Notes NK8000 MP4.15 provides an improved firmware version (DF8003 support). Æ See NK8000 MP4.15 Release Notes Building Technologies Fire Safety & Security Products 3 073_DMS_MM8000_Release_Notes_MP4.15-01_A6V10062509_a_en.doc 03.
What’s new in MP4.15 releases 2 What’s new in MP4.15 releases This section presents the enhancements provided in the new MM8000 software, starting from MP4.15, compared with previous MP4.10-xx. 2.1 New MP4.15 features New connectivity z FS20 fire systems MP1.3 over BACnet/IP FS20 MP1.3 can connect to max.2 client systems (e.g. DMS8000). DMS8000 MP4.15 supports NS8011 BACnet driver capable of connecting up to 50 devices on valid BACnet IP network architectures. Therefore, a total of max.
What’s new in MP4.15 releases z History backup operations are now registered as history log. z Scheduled and manual tasks are now more flexible as they can include com- z z z z z mands that apply to a subset (and no longer to the entire set) of the linked points. Enhanced task supervision: an event is generated in case of task failure (Scheduled Tasks, Manual Tasks, and Time Programs). Quad view available to show images from up to 4 cameras.
What’s new in MP4.15 releases Number of drivers (for FEP configurations) Number of connections to DVR’s z NICE license check: – 3rd-party license – Number of drivers (for FEP configurations) – Number of connections to DVR’s – – Installation CD z MT8001 MP4.15 setup option added to install configuration tools and drivers z NK8000 MP4.15 setup option added to install configuration tools and drivers 2.1.1 Localisation As illustrated in the Localisation Guide (document no. A6V10062459), the MM8000 MP4.
What’s new in MP4.15 releases ID Found in… Module Notes 9457 4.15 DESIGO PX alarm reset The DESIGO PX alarm reset did not work properly. Also corrected in: MM8000 MP4.15 Hotfix #12 9458 4.15 Filtered event acknowledgement When a filtered event is acknowledged, the generation time in the event bar used to be erroneously replaced by the acknowledgement time. Also corrected in: MM8000 MP4.15 Hotfix #21 9461 4.
What’s new in MP4.15 releases 2.3 ID Found in… Module Notes 9571 4.15 Plant Browser with dual screen in closed mode When running a dual screen interface under Windows Vista in closed and locked mode, the Plant Browser application failed to start on the second monitor. Also corrected in: MM8000 MP4.15 Hotfix #23 9573 4.15 Tamper events of Sintony E-Bus devices Tamper handing for Sintony E-Bus devices has been modified to prevent false alarms from occurring. Also corrected in: MM8000 MP4.
What’s new in MP4.15 releases Building Technologies Fire Safety & Security Products ID Found in… Module 8593 4.10-00 Composer, Subsystems that do not provide any OPC interface used to OPC interface erroneously show the MK8000 tab in Composer. Notes 8603 4.10-00 License Key Problems occurred in changing customer key and PAKS while Service Key is also installed. 8621 4.
What’s new in MP4.15 releases ID Found in… Module 8760 4.10-00 Plant Browser The Save Layout function did not include the settings in the detailed view required for video playback viewer. Notes 8767 4.10-00 SiPass Access Denied messages (Card not yet active, Time schedule violation, Expired card, Void card, Wrong PIN, Access with Daily code) were not supported. 8788 4.10-00 Composer A defect was corrected that caused Composer restore to fail with specific file names. 8798 4.
What’s new in MP4.15 releases ID Found in… Module Notes 9101 4.10-01 Graphical maps Composer graphic tool might not show the configured AutoCAD layer. 9144 4.10-01 NK822x This defect was also repaired in MM8000 MP 4.10 Hotfix#12. The performances of NK8000 Network Driver NS8010 has been improved to better support large configurations. This defect was also repaired in MM8000 MP 4.10-02 Hotfix#14. 9149 4.
What’s new in MP4.15 releases 2.4 Summary of connectivity options Network Notes Further info.
What’s new in MP4.15 releases 2.5 Summary of Add-on modules Add-on New in MP4.15-01 Building Technologies Fire Safety & Security Products Version Notes – Autronica BSxx Fire Control Units V3.20 Distributed as separated module – CDDL-CDSF Units V4.10 Distributed as separated module – CP100 Gas Detection Unit V3.20 Distributed as separated module – DLCS Door Control System V4.15 Installed with base setup – Geutebrueck Video Units V4.
What’s new in MP4.15 releases Control units FS20 CS11 AlgoRex® EP5 and EP7 FC700A CS1115 Phase 4 FC330A Phase 4 SIGMASYS D100 STT11 Notes about latest version supported MP1.3 Connectivity and configuration notes LAN EP7Z V2.2 Direct link, Cerloop, and NK8000 Direct link CISxx8.86 SIGMASYS V3.
What’s new in MP4.15 releases 2.5.1 SiPass The following table shows the compatibility between MM8000 and SiPass versions: Compatibility matrix: SiPass 2.2 MM8000 SiPass 2.3 Build 18 SiPass 2.3 Build 21 SiPass 2.35 Build 38 SiPass 2.35 Build 41/52 SiPass 2.40 Build 37 SiPass 2.40 Build 41 MP3.15 Yes No No No No No No MP3.15-01 No Yes No No No No No No No Contact support (*) No No No No MP3.15-02 MP3.20 No No Yes No No No No MP3.
What’s new in MP4.15 releases 2.5.2 Video All models of the SISTORE Digital Video Recorders are supported in various software versions: please refer to the compatibility matrix provided below and to the corresponding known issues described on page 27. Device model Device version/type MM8000 Version SISTORE AX V2.4.0, V2.50 MP3.15, 3.15-xx, 3.20, 3.20-01/-02/-03/-04, 4.10, 4.10-01/-02, 4.15 V2.6.0, V2.6.1 MP3.15, 3.15-xx, 3.20, 3.20-01/-02/-03/-04, 4.10, 4.10-01/-02, 4.15 V2.6.2 MP4.15-01 V2.
Installation and configuration procedures 3 Installation and configuration procedures 3.1 Software installation MM8000 MP4.15-01 is distributed as an add-on package for MP4.15 installations. For detailed information about the MP4.15 installation procedure, refer to the MM8000 ICC manual (document no. A6V10062413_a_en). 3.1.1 New systems: installing MP4.15 and then 4.15-01 The MP4.15 installation procedure includes the following steps: 1. Check system requirements.
Installation and configuration procedures 6. Reboot the PC. 7. Install the MP4.15-01: – Make sure that no MM8000 client applications are active (including Composer and Simulation tools). – Copy the MP4.15-01 setup files on a local drive, e.g. in the folder: C:\MM8000_MP4.15-01_Setup\... – Launch the command: Fix_MM8000 MP4.15.01.exe and follow the instructions on the screen. 8. Install the hardware key and enter the license code using the PAK Manager tool.
Updating from older releases 4 Updating from older releases 4.1 Software License All previous MP4.1x Composer and MM8000 licenses are still valid for MP4.15. Earlier licenses needs to be updated. 4.2 Localisation Use the language file (ZIP) of the MP4.15 localisation toolkit. Æ See MM8000 Localisation Engineering Guide, doc.no. A6V10062459. 4.3 Updating from MP2.xx The configuration database update from MP2 releases - namely MP2.10, MP2.20, MP2.21, and MP2.30 - is possible using MM8000 MP2.
Updating from older releases again (note that the deletion will force you to reconfigure the access control points in maps, reactions, sequences, etc.). – [Database 3.15-02 and later] the alignment of the access control configuration is required. After restoring a previous SiPass configuration, it is necessary to add a new user to the list of authorised operators for SiPass.
Known issues in MP4.15-01 5 Known issues in MP4.15-01 This is a list of known limitations, problems, bugs and recommended practises at the time this software was released. Compared with previous Release Notes, new and updated points are marked by a side label for easier identification. 5.1 Installation MS Windows 64-bit edition Windows 2003 64-bit edition is not supported. MS Windows Vista The use of Windows Vista requires specific attention.
Known issues in MP4.15-01 Clear History DB Rare cases of difficulties in the history functions have been reported after installation. In such cases, the FS-DMS support may recommend the use of the program: \Utilities\ToolsUtilities\EngineeringTools.exe This can clear (and optionally also resize) the database and solve the problem. Windows NT 4.
Known issues in MP4.15-01 – Adding CAD fonts: additional CAD fonts can be manually added in the folder \Resources\CADfonts (e.g. C:\MM8000\ Resources\CADfonts). If not already existing, the ‘CADfonts’ subfolder must be created. DMS7000 metafile for CZ10 and CZ12 CZ10 and CZ12 customer texts (DMS7000 databases) can be imported only once. No subsequent import of CZ10 and CZ12 is possible.
Known issues in MP4.15-01 FS20: migrating from MP4.10-02 Configurations restored from MP4.10-02 –and including some specific types of FC20 zones– need a special reworking when FS20 databases are re-imported into Composer. In that case, the FC20 Zones are deleted and then recreated as new objects. Therefore, the related links and map symbols need to be configured again.
Known issues in MP4.15-01 5.3 Functionality FEP stations require server when starting up Distributed configurations including FEP stations: When you start up a FEP station, you must ensure that the MM8000 server is already up and running. Low virtual memory events Depending on the specific configuration and on the PC hardware characteristics, MM8000 software may use up the memory resources in Windows and cause the “Low virtual memory” error message to display.
Known issues in MP4.15-01 SiPass New in MP4.15-01 – Reader name, FLN name and structure This information cannot be acquired from SiPass; this prevents MM8000 from representing the entire physical structure of the devices.
Known issues in MP4.15-01 SISTORE AX Note that SISTORE AX can support only one client at the time. When one MM8000 station is connected to the video unit to show video images, no other station can connect at the same time. Hardware acceleration of the video adapter may influence the correct display of the SISTORE AX live video when used in MM8000. In case of problems, please reduce the acceleration, typically to a medium setting, following this procedure: – Right click on Desktop.
Known issues in MP4.15-01 As a work-around, we suggest to set the "Ethernet" node of the NK8225 "out-ofscan". Note that, if a real communication problem occurs, it will be displayed as NK8225 unit not reachable. SI410 Sintony After commissioning on first connection, MM8000 may show a fault and a nondefault event related to Sintony. You can clear these events by sending a Silence command. 28 Building Technologies Fire Safety & Security Products 073_DMS_MM8000_Release_Notes_MP4.15-01_A6V10062509_a_en.
Documentation 6 Documentation All documents were updated to include the new features added in MP4.15. Note the document numbers related to the new STEP numbering. STEP documentation repository On the Siemens intranet, the product documentation can be found in the STEP Documentation Repository. The STEP Web Client interface is available at the following address: https://intranet.sbt.siemens.com/dbcom/en/db_porta/client.asp The following describes one way to search and find a document: 1.
Documentation Sales Guide (document no. A6V10062427_a_en) This guide presents the most important sales arguments. Also, a FAQ section provides the answer to some typical questions. Sales Presentation (document no. A6V10062423_a_en) This is a PowerPoint presentation provided by the marketing department. It can be modified, or used as is to show potential customers what the MM8000 can do. DMS8000 Application & Planning (document no.
Documentation MM8000 Localisation Guidelines (document no. A6V10062459_a_en) This guide provides assistance with the localisation of the MM8000 MP3.20 software, including information about using the Catalyst tool. Quick reference guides These short guides (4 to 8 pages A5 format) can be used as reference papers for the most typical software functions. The list of available quick guides includes: – Operation (document no. A6V10067779_a_en) – Installation, Configuration Commissioning (doc.no.
Customer support links & resources 7 Customer support links & resources 7.1 Siemens BT FS Updated in MP4.15 7.2 Our Customer Support Center intranet site at: https://intranet10.sbt.siemens.com/about_bt/Business_Units/fs/Customer+Support+ Center/?languagecode=en provides useful information and links. In the Online Support section of this intranet page, software downloads and known product issues can be found in the PSP (password-protected Product Support Platform). Æ The support mailbox is: fs.
Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel +41 41 724 24 24 Fax +41 41 724 35 22 www.sbt.siemens.com Document no. Edition A6V10062509_a_en 03.