Introduction 1 Introduction .............................................................................................5 2 2.1.1 2.1.2 2.1.3 2.1.4 2.1.4.1 2.1.4.2 2.1.4.3 2.1.4.4 2.1.4.5 2.1.4.6 2.1.4.7 2.1.5 2.1.5.1 2.1.5.2 2.1.5.3 2.1.5.4 2.1.5.5 2.1.5.6 2.1.5.7 2.1.5.8 2.1.5.9 2.1.5.10 2.1.5.11 2.1.5.12 Main new features in MP3.20-0x release ..............................................6 MK8000 integrated in MM8000.................................................................6 Installation .....
Introduction 8.1 8.2 8.2.1 8.2.2 8.3 Siemens FS.............................................................................................44 Microsoft..................................................................................................44 Windows 2000.........................................................................................44 Windows XP ............................................................................................44 Adobe Acrobat ..................................
Introduction 1 Introduction The new MM8000 software release MP3.20-02 is now available. These release notes document the characteristics of the new software, including bug corrections and known issues. We recommend that users carefully read this document before installing and using the software. About this document This document includes and replaces the release notes published for MP3.20 and MP3.20-01. MP3.20-02 release MM8000 MP3.20-02 is a bug-correction service release for latest complete setup (MP3.
Main new features in MP3.20-0x release 2 Main new features in MP3.20-0x release This section presents the main enhancements provided in the new MM8000 software, starting from MP3.20, compared with previous MP3.15-xx. 2.1.1 MK8000 integrated in MM8000 Starting from MP3.20, MM8000 and MK8000 are integrated in the same general software environment.
Main new features in MP3.20-0x release 2.1.3 Composer Multiple clients and remote client Two Composer client stations can be used simultaneously for configuration purposes on the same project, using the Composer client software and connecting (even from a remotely networked PC) to the Composer server. As for a single client, Composer requires a license + key or a Service key installed on the server machine.
Main new features in MP3.20-0x release 2.1.4 Connectivity Network News in MP3.20-xx Further info. in this document Further info.
Main new features in MP3.20-0x release Control units – CS11 AlgoRex® EP5 and EP7 – FC700A – CS1115 Phase 4 – FC330A Phase 4 – SIGMASYS (field test only) – D100 (field test only) – STT2410 / STT11 – STT20 News in MP3.20-xx Further info. in this document EP7F Z2.1 (V7.8x) 2.1.5.12 Further info. in DMS8000 documentation CISxx8.85 2.1.4.4 Network, Fire & Intrusion Connectivity Guide: 007083_j_en SIGMASYS V40-2 D100 V3.5 2.1.4.
Main new features in MP3.20-0x release 2.1.4.1 SiPass The following table shows the compatibility between MM8000 and SiPass versions: Compatibility MM8000 matrix: SiPass 2.2 SiPass 2.3 SiPass 2.3 Build 18 Build 21 SiPass 2.35 2 Build 31( ) MP3.15 Yes No No No MP3.15-01 No Yes No No No No Contact support (*) No MP3.20 No No Yes No MP3.20-01/-02 No No No Yes MP3.15-02 The following table shows the characteristics of the integrated solutions: # Description MM 3.15 + SiPass 2.
Main new features in MP3.20-0x release 2.1.4.2 Video SISTORE CX/SX Digital Video Recorders are now supported: please refer to the compatibility matrix provided below and to the known issues described on page 40. Video device model Video device version MM8000 Version / type SISTORE AX V2.40 MP3.15, 3.15-01, 3.15-02, 3.20, 3.20-01, 3.20-02 V2.50 MP3.15, 3.15-01, 3.15-02, 3.20, 3.20-01, 3.20-02 V2.60 (recommended) MP3.15, 3.15-01, 3.15-02, 3.20, 3.20-01, 3.20-02 SISTORE MX (including NVR) V2.55, V2.
Main new features in MP3.20-0x release 2.1.4.4 FC330 (CS1115) FC330A / CS1115 version The version CISxx8.85 has been tested with MM8000 (xx depends on the national text version). Please contact support for compatibility with latest Service Release 4 (CISxx8.86). Configuring the communication port in FC330A In FC330A, in order to enable the communication protocol on the serial port, you need to configure the unit at control panel level. Follow this procedure: 1.
Main new features in MP3.20-0x release 2.1.4.5 NK8000 and BACnet/IP A new NK822x firmware has also been released. The new firmware includes defect corrections and optimisations. Upgrading the NK8222, NK8223 and NK8225 units is recommended. Warning: the NK822x units handle the protocol interpretation for the subsystems supporting interactions.
Main new features in MP3.20-0x release 2.1.4.7 3rd party subsystem connectivity via NK8000 Although not integrated in the basic package, the support for a number of control units is possible using specific Add-on packages. The list of (MP3.
Main new features in MP3.20-0x release Geographical tree Linking a node into the geographical tree also links the corresponding subtree. This allows to easily merge the geographical and logical structure and provides the full status information and control commands in the geographical views. 2.1.5.2 History archive History archive management Automatic archiving can be provided when database is full or on a (scheduled) time basis.
Main new features in MP3.20-0x release As for any other association criteria, manual assignments can be used to modify the association of individual objects. See MM8000 ICC manual no. ‘006799_h_en’. 2.1.5.5 Improved performances in SISTORE CX video applications In MP3.20, due to an external component, MM8000 software was remarkably slow in opening a new live video image. A delay of about 15 seconds might occur upon each new image selection. The MP3.
Main new features in MP3.20-0x release 2.1.5.7 Safer NK822x download In the NK8000 network solutions, the NK8225 unit was introduced with DMS8000 MP3.20 in order to support new BACnet protocol connections. See Network, Fire & Intrusion Connectivity Guide no. ‘007083_j_en’. In the new configuration environment, the NK822x units require be identified with a specific type, which is set in the Ethernet Node page (see picture below).
Main new features in MP3.20-0x release 2.1.5.9 MS-SQL server databases replacing older MS-Access files In the MM8000 files and services, new MS-SQL-server databases have replaced MS-Access files. Although no user interface functions have been affected, you need to be aware of this change and more precisely: For general information, be informed that the SQL databases used by MM8000 are the following: MM8000Srv1, MM8000Srv2, MM8000Support, HSRegistrations. Default names might be customised: see 2.1.5.
Main new features in MP3.20-0x release 2.1.5.10 Redundant server solution with Marathon In DMS8000 systems, the Marathon EverRun FT software can be used in order to satisfy fault-tolerant requirements. Marathon EverRun FT is a software application that can provide a Virtual server based on two identical PC machines connected over a local network. MM8000 and MK8000 can be installed on the virtual machine, which appears in all respects as a fully standard Windows system.
Main new features in MP3.20-0x release 2.1.5.11 Integrated Engineering Tools A number of small programs, which used to be separately available in the ‘Utilities/Tools’ folder, have been integrated into a common environment for an easier and safer access. As shown in the picture below, the new program: \Utilities\ToolsUtilities\EngineeringTools.
Main new features in MP3.20-0x release 2.1.5.12 CC11 AlgoRex EP7F Z2.1 – Extinguishing messages The new version Z2.1 of CC11 AlgoRex (Firmware 7.8x) is fully supported in all configurations and protocols but BACnet/IP. New data and command messages, previously not handled by MP3.20 and earlier releases, concern the extinguishing functions. Limitations The new messages are NOT yet supported in the full BACnet configuration, including NK8225 for DESIGO and DMS8000 / NS8011.
Bug correction 3 Bug correction 3.1 Corrections in MP3.20 ID Description Notes 7295 7867 Download failure in case of corrupted bitmap during the activation phase. Also repaired in MM8000 MP3.15 Hotfix #14 7086 7116 Occasional disconnections of WinCC OPC Also repaired in MM8000 Server. Errors in managing the link supervision. MP3.12 Hotfix #02 7253 History database restore troubles (HS.exe module). Also repaired in MM8000 MP 3.12.
Bug correction ID 6598 Description An occasional (and erroneous) “Server not available” message used could appear on the MM8000 client screen. 6836 In the Scheduler configuration tool, selection field associated to "Every week on" was not correctly managed. 7390 In the CC11 EP7 import procedure, Sinteso detector texts were not properly set (missing sequential number). 7294 The "Points not inserted in maps" export does not work correctly with special characters.
Bug correction 3.2 Corrections in MP3.20-01 ID Description Notes 6929 Installation Procedure MM8000 did not provide any exception message in case the SQL database instance for history service cannot be created. The consequence was that MM8000 server could not start (red status of the History Server). This case is now clearly reported to the user.
Bug correction ID Description Notes 8003 Project update errors with direct CK11 link Configurations including a direct CK11 connection via NS8010 driver might fail to be properly updated to MP3.20. This has been resolved. 8045 SIGMASYS import procedure The ‘Output’ type of objects did not get properly imported. The defect has been corrected. 7893 Download reliability In MP3.20, download may fail after a few attempts (‘empty_db’ was necessary to download again). This defect has been removed.
Bug correction ID Description 7877 7878 IP camera configuration Problem used to occur when downloading IPCamera over FTP. This has been corrected. 7932 Problem in getting CS1115 communicating The MM8000 MP3.20 configuration tool was improved (Node Tab and COM0 port) to prevent communication difficulties with CS1115 from occurring. 8054 Page Manager Server This server task used to have problems related to very specific cases.
Bug correction 3.3 Corrections in MP3.20-02 Notes ID Description 7375 The creation of Manual pages did not work correctly. When a manual page was saved in mapmaker, it slightly moved up implying that some points included in the manual page extended outside the page area and were not shown runtime. 7804 The duration of the link procedure of points under NK822x interactions was long (40 seconds nearly). This problem was also present in MM8000 MP3.20. This is now fixed. 7940 In 3.
Bug correction Notes ID Description 8151 Problems with MM8000 supervision. In some cases, MM8000 erroneously reported internal problems: the System Status lights at the top right on the screen show in yellow and the PC buzzer seems to indicate a processor’s overloaded. A switchover / restart seemed to solve the problem, but it may then occur again. 8153 Missing license check of the configured graphical Maps.
Bug correction ID 8169 8170 8171 Description NK8210 3.15 – Memory corruption error generated by CEI Protocol. This error was detected when the protocol determined to dispatch again the message addressed to a branch because the “acknowledge” was not received in the expected time. In particular, during the transmission of a CEI identification message which is only 9 bytes, date/time update caused a memory corruption of 4 bytes. Notes NK8210 3.15 crash.
Installation and configuration procedures 4 Installation and configuration procedures 4.1 Software installation Unlike previous MP3.20-01 (that was distributed with a complete setup procedure), MP3.20-02 is an add-on package to be installed after the base installation of MP3.20-01. For detailed information about the basic MM8000 setup refer to the MM8000 ICC manual (006799_i_en), section 3. Also, note that new setup options are available for supporting Marathon-based redundant systems. See 2.1.5.
Installation and configuration procedures 8. Install now the MP3.20-02 software: Stop MM8000 client applications Copy the MP3.20-02 folder onto the same disk where MM8000 in installed Run the command “Install_MM8000_MP3.20-02.exe” 9. Install the hardware key and enter the license code using the PAK Manager tool. Note that SiPass also requires a license option (Management Station Integration). Notes: Software License: all previous Composer and MM8000 licenses must be updated to MP3.20.
Installation and configuration procedures – If the SiPass server does not run on the same PC as MM8000, then additional installation steps are required on the networked PC where SiPass is installed: 1) In the Windows user list, the SiPass PC should include the MM8000 Internal User, by default ‘DMS8000-Proc’. Use the same username and password as on the MM8000 PC. Refer to MM8000 ICC Manual (006799) and specifically to section 3.4.11.4. See the ‘Security’ settings in the new tool described at 2.1.5.
Migrating from older releases 5 Migrating from older releases 5.1 Software License All previous Composer and MM8000 licenses must be updated to MP3.20. 5.2 Localisation Referring to the localised versions, be informed that the language file (ZIP) for MP3.20-02 is the same as the previous MP3.20-01. 5.3 Migrating from MP2.xx The configuration database migration from MP2 releases – namely MP2.10, MP2.20, MP2.21, and MP2.30 - is possible using MM8000 MP2.31 and MP3.
Migrating from older releases 10. The update procedure will take some minutes, depending on the size of the project. Please wait for the procedure to complete. 11. [Database 3.15-xx and earlier only, not required for 3.20] In the MM8000 structure tree, select: Supervision System Settings MM8000 System Logical Configuration User Data Graphic Maps On the Node tab, press the button labelled “Map Update” and wait for the graphic map update procedure to complete. 12. [Database 3.
Known issues in MP3.20-02 6 Known issues in MP3.20-02 This is a list of known limitations, problems, bugs and recommended practises regarding MP3.20-02 at the time this software was released. 6.1 Installation SQL security MSDE has a security weakness (the empty ‘sa’ password) that can be fixed by setting your SQL password with a special command available in: \Utilities\Bat\SetSQLServerPassword.
Known issues in MP3.20-02 Pak Manager and 3rd-party PAK codes New in MP3.20-01 6.2 Pak Manager shows the 3rd Party PAK codes only if the related Add-on is installed. Instead, if the additional software is not present, the related PAK does not appear in the list. Note alto that, if you install the Add-on package after the PAK configuration, you need to re-insert the PAK's in the PAK Manager to get the correct license. Additionally, this implies to restart the MM8000 servers.
Known issues in MP3.20-02 CC11 AlgoRex EP7 The following structures are imported in the logical and not in the physical tree: 1551 - Digital output; 1552 - Digital output supervised; 1560 - Internal horn; 1561, 1564, 1565 - External horn; 1562 attribute = RTFIRE – “Alarm” remote transmission channel; 1562 attribute = RTFAULT – “Fault” remote transmission channel; 1562 attribute = RTOTHER – “Other” remote transmission channel. CC11 EP7F Z2.1 The new version Z2.
Known issues in MP3.20-02 New in MP3.20 Screen savers Please abide by the following guidelines if you wish to use a Screen saver while running MM8000: – Use only standard Windows Screen savers; – Do not configure password protection for Screen savers. Standard Windows Screen savers allow for the Event icon area and the Summary bar to be present while the Screen saver occupies the Work area. Failure to comply with the guidelines listed above may result in problems with the MM8000 system.
Known issues in MP3.20-02 Remote SiPass server (Windows XP only) If the SiPass server is installed on a remote PC, the “Log On” properties must be changed on the remote PC so that the SiPass server can communicate with MM8000. Perform the following steps: 1 Log on to the PC with the SiPass server. 2 Right-click on ‘My Computer’ and select ‘System Tools → Local User and Groups → Users’.
Known issues in MP3.20-02 SISTORE AX Note that SISTORE AX can support only one client at the time. When one MM8000 station is connected to the video unit to show video images, no other station can connect at the same time. SISTORE MX In general, we recommend that you use SISTORE MX V2.58 or upgrade to this version. Depending on the version installed, the following difficulties may be encountered: 1 The SISTORE MX 2.55 must be used with the remote player of SISTORE MX 2.57 or later.
Documentation 7 Documentation New “STEP” document database The new STEP Documentation Repository System has recently replaced the previous EDMS system. The STEP Web interface can be found at the following intranet address: https://intranet.sbt.siemens.com/dbcom/en/db_porta/client.asp The following describes one way to search and find a DMS8000 document: 1.Click on the "STEP WEB Client" image: New in MP3.20-02 7.1 2.Choose "04 Fire -3F" from the "Product Segment" box and select “Activate filter”. 3.
Documentation 7.2 Technical documentation MM8000 Operation Manual (document no. 006798 rev.“h”) This manual is an operation guide, meant for end users. MM8000 Installation, Configuration and Commissioning (ICC) (document no. 006799 rev.“i”) The ICC guide provides step-by-step procedures for installation and configuration of the MM8000. During configuration, this manual should be used in tandem with the DMS8000 Connectivity Configuration guides.
Documentation 7.2.1 MP3.20 documentation errata MP3.20 Release Notes (009421_a_en) – It erroneously reported that SiPass FLN3a bus objects could not be supported, whereas they can be safely used in configurations including SiPass. – It also indicated that MM8000 CD included the latest SiPass software, while this is actually not the case. New in MP3.20-01 MM8000 ICC (006799_i_en) – At pag.
Customer support links & resources 8 Customer support links & resources 8.1 Siemens FS Updated in MP3.20-01 8.2 Our Customer Support Center intranet site at: http://intranet10.sbt.siemens.com/divisions/fs/customer+support+center/ provides useful information and links. In the Online Support section of this intranet page, software downloads and known product issues can be found in the PSP (password-protected Product Support Platform). Please note the support mailbox: fs.support.sbt@siemens.com.
Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel +41 41 724 24 24 Fax +41 41 724 35 22 www.sbt.siemens.com Document no. A6V10067812_a_en Edition 04.