MK8000 OPC Server Interface Specification for FC700A Building Technologies Fire Safety & Security Products
Building Technologies Fire Safety & Security Products Data and design subject to change without notice. / Supply subject to availability. © Copyright by Siemens Switzerland Ltd We reserve all rights in this document and in the subject thereof.
Building Technologies Fire Safety & Security Products FC700A The FC700A fire detection system represents the current generation of the SIEMENS fire detection technology. FC700A Objects represent parts of the central control unit(s) as well as external distributed devices devoted to fire detection.
Building Technologies Fire Safety & Security Products FC700A - ( FINOAPMN ) The Application object represents the events related to the entire FC700A detection system and the terminal that controls it. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1351 Anomaly Ack The Control Unit is partialy Reachable. The event has been acknowledged.
Building Technologies Fire Safety & Security Products Fire Area - ( FINOARRO ) Fire Area represents the highest logical level in the FC700A logical structure Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The event should now be acknowledged by the operator. 502 Alarm Unreset The system is in General Alarm state. The event should now be reset by the operator.
Building Technologies Fire Safety & Security Products 812 Prealarm & Fault Unreset This event is the combination of the Prealarm and Fault state. The event should now be reset by the operator. 1000 Quiet The system is in Unmanned (Night) mode. No abnormal conditions present. 1300 Disarmed The system is in Manned (Day) mode. 1351 Anomaly Ack The system is partially Off. The event has been acknowledged. 1352 Anomaly Unack The system is partially Off.
Building Technologies Fire Safety & Security Products RtController Alarm - ( FICORCAL ) The RtController Alarm (RT = Remote Transmission) object represents the state of the `Alarm Remote Transmission Delay` within the Area.
Building Technologies Fire Safety & Security Products rtDevice - ( FINORDGE ) The Rt Device (RT = Remote Transmission) object represents the state of the `Remote Transmission Device` associated to the Area. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1329 Blocked Ack The event has been acknowledged. 1330 Blocked Unack The remote transmition device is block.
Building Technologies Fire Safety & Security Products Fire Section - ( FINOSEGE ) The Fire Section represents the logical level below the Area in the FC700A structure and reports the conditions of the affiliated detection zones. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack Some zone are in allarm. The event should now be acknowledged by the operator. 502 Alarm Unreset Some zone are in allarm.
Building Technologies Fire Safety & Security Products Extinguishing Section - ( FIEXSEGE ) Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The event should now be acknowledged by the operator. 502 Alarm Unreset The event should now be reset by the operator. 510 Alarm & Fault Unack This event is the combination of the Alarm and Fault state.
Building Technologies Fire Safety & Security Products 812 Prealarm & Fault Unreset This event is the combination of the Prealarm and Fault state. The event should now be reset by the operator. 946 Active Unack The event should now be acknowledged by the operator. 948 Active Unreset The event should now be reset by the operator. 1000 Quiet No abnormal conditions present. 1100 Test 1300 Disarmed 1319 Manual Ack The event has been acknowledged.
Building Technologies Fire Safety & Security Products 1999 Fault Ack The event has been acknowledged.
Building Technologies Fire Safety & Security Products Build. Serv. Section - ( BSCOSEGE ) The Building Services Section is a type of section made up of zones (and in turn elements) that monitor or control devices for general services in the supervised building. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1300 Disarmed The entire section is switched off.
Building Technologies Fire Safety & Security Products Single Zone - ( FIDEZOSI ) The Single-Logic Fire Zone object represents a zone made up of a single detection element. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The zone is in Alarm. The event should now be acknowledged by the operator. 502 Alarm Unreset The event should now be reset by the operator.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The zone is in not ready or it is switched in fast/low reaction mode. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Multi Zone - ( FIDEZOMU ) In a Multi-Logic Fire Zone the alarm decision is based on the response of multiple detection elements affiliated with the zone. The conditions can be parameterised within the FC700A. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The zone is in Alarm. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The zone is in not ready or it is switched in fast/low reaction mode. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Extinguishing Zone Multi - ( FIEXZOMU ) In a Multi-Logic Extinguishing Zone, the alarm decision is based on the response of multiple detection elements affiliated with the zone. The basis upon which these decisions are made can be customised through the FC700A. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The zone is in alarm.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The zone is switched in fast reaction mode or the zone is not ready.The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Manual Zone - ( FIDEZOMA ) The Fire Zone Manual object represents a zone made up of manual call-points (emergency alarm buttons). Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The zone is in alarm. The event should now be acknowledged by the operator. 502 Alarm Unreset The event should now be reset by the operator.
Building Technologies Fire Safety & Security Products Extinguishing Sprinkler - ( FIEXZOSP ) The Extinguishing Sprinkler Zone object represents a zone that processes binary information. Associated extinguisher activators are set in alarm state with a YES/NO binary alarm signal. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The zone is in alarm. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The zone is not ready or it`s switched in fast reaction mode. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Build. Serv. Binary Zone - ( BSDEZOBI ) The Building Services Binary Zone uses a binary trigger rather than danger threshold level triggers. A YES signal (element active) from an affiliated detector is enough to cause the alarm state. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The zone is in alarm.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The zone is not ready or it`s switched in fast reaction mode. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Build. Serv. Zone Auto - ( BSCOZOAU ) The Building Services Control Zone object represents a zone that can activate output control reactions based on a pre-programmed evaluation logic of the states of affiliated digital detection elements.
Building Technologies Fire Safety & Security Products Build. Serv. Zone Progr. - ( BSCOZOPG ) The Building Services Control Zone object represents a zone that generates (activates) a signal when it detects a state of danger. It evaluates whether a situation should be considered dangerous based on parameters that were configured into the zone.
Building Technologies Fire Safety & Security Products Fire Detector Addr - ( FIDEDEAD ) The `Fire Detector Addressable` element represents a fire detector for automatic alarm detection and individual identification Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The detector is active. The event should now be acknowledged by the operator. 947 Active Ack The event has been acknowledged.
Building Technologies Fire Safety & Security Products 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The detector is in fault. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Manual CallPoint - ( FIDECPGE ) The Fire Detector Call-point element represents an alarm pushbutton for manual alarm activation. Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The detector is active. The event should now be acknowledged by the operator. 947 Active Ack The event has been acknowledged.
Building Technologies Fire Safety & Security Products 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Fire Detector Generic - ( FIDEDEGE ) The Fire Detector Generic element represents a fire detector for automatic alarm detection Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The detector is active. The event should now be acknowledged by the operator. 947 Active Ack The event has been acknowledged.
Building Technologies Fire Safety & Security Products 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Fire Detector Collective - ( FIDEDECO ) The Fire Detector collective element represents a detector of the series DS11-C for collective lines.
Building Technologies Fire Safety & Security Products Fire Detector Binary - ( FIDEDEBI ) The Fire Detector Binary element represents a fire detector that uses a simple on/off alarm logic. Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The detector is active. The event should now be acknowledged by the operator. 947 Active Ack The event has been acknowledged.
Building Technologies Fire Safety & Security Products 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Exting. Digital Input - ( FIEXDIGE ) Digital input objects represent generic digital input (e.g. contacts) elements, activated by sensors that signal alarm states to the FC700A. Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The detector is active. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Build. Serv. Digital Input - ( BSDEDIGE ) Digital input elements represent generic digital inputs (e.g. contacts), activated by sensors for signalling alarm states to FC700A Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The detector is active. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Digital Output - ( BSDEDOGE ) Digital output objects represent output elements without feedback, activated to control simple external devices such as lamps etc. These elements do not have a feedback input, but can detect an internal fault. Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The detector is active.
Building Technologies Fire Safety & Security Products Supervised Output - ( BSDEDOSV ) Digital output represents output elements with feedback. They are activated to control complex external devices such as horns, door locks, etc. These elements have a feedback input, which is used to detect an unsuccessful activation. Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The detector is active.
Building Technologies Fire Safety & Security Products Internal Horn - ( FICOHOIT ) The Internal Horn element represents an internal audio output that receives its control activation commands directly from the higher-ranking area. Typically, the internal horn is activated simultaneously with the buzzer on the CT11. Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The horn is sounding.
Building Technologies Fire Safety & Security Products External Horn - ( FICOHOET ) The External Horn object represents the output to external devices that receives its control activation commands directly from the higher-ranking area.
Building Technologies Fire Safety & Security Products RtChannel alarm - ( FICORHAL ) The RtChannel alarm object represents a remote transmission output for alarms. Remote transmission channels receive their control commands directly from the higher-ranking area.
Building Technologies Fire Safety & Security Products RtChannel Fault - ( FICORHFL ) The RtChannel fault object represents a remote transmission output for faults. Remote transmission channels receive their control commands directly from the higher-ranking area.
Building Technologies Fire Safety & Security Products RtChannel Other - ( FICORHOT ) The RtChannel Other object represents a remote transmission output for other events. Remote transmission channels receive their control commands directly from the higher-ranking area.
Building Technologies Fire Safety & Security Products Addressable Detection Line - ( HWNODCAD ) The Addressable Detection Line object reports alarms and faults that, for some technical reasons, cannot be addressed on the detection zones Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The collective Alarm was detected. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 2000 Fault Unack The detection line is in fault. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Colletive Detection Line - ( HWNODCCO ) The Collective Detection Line object reports faults on a collective line. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The collective Alarm was detected. The event should now be acknowledged by the operator. 502 Alarm Unreset The event should now be reset by the operator.
Building Technologies Fire Safety & Security Products Controller Binary I/O - ( HWNOICBI ) Representation of a digital I/O module. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The fault condition was detected. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Power Supply - ( HWNOPSGE ) The Power Supply object reports the conditions determined by power supply monitoring logic Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The power supply is in fault. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Vds I/O Controller - ( HWVDICRO ) The VDS I/O controller object covers the fault states of the interface and Fire Brigade panel approved by VDS norms Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1999 Fault Ack The event has been acknowledged.
Building Technologies Fire Safety & Security Products Vds Remote Trasmission - ( HWVDRCGE ) The VDS Remote Transmission object covers the states of the remote transmission device approved by VDS norms. Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The Remote trasmission is active. The event should now be acknowledged by the operator. 947 Active Ack The event has been acknowledged.
Building Technologies Fire Safety & Security Products Vds External Controller - ( HWVDECGE ) The VDS Remote Transmission object covers the states of the extinguishing interface approved by VDS norms. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The Extinguishing was manually actived. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 2000 Fault Unack The fault condition was detected. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Vds Key Cabinet - ( HWVDICKC ) The VDS Remote Transmission object reports the conditions of a Fire Brigade key box (a protected cabinet reserved for the Fire Brigade, which is a hardware interface required for VDS approval). Multistate Commands 1-Ack 900 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Tamper Unack The key Cabinet was tampered.
Building Technologies Fire Safety & Security Products 2000 Fault Unack The Key Cabinet is in fault. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Extinguishing Controller - ( HWEXICRO ) The Extinguishing Controller object represents an extinguishing control module Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The fault condition was detected.
Building Technologies Fire Safety & Security Products Lon Interface - ( HWLNICRO ) Representation of a LON network module Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The fault condition was detected. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Control Panel - ( HWNOCCRO ) The Control Panel object reports alarms and faults that, for some technical reasons, cannot be addressed on the detection zones nor on detection lines. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The Control Pannel is in Emergency Alarm.The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 2000 Fault Unack The Control Pannel is in fault. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Printer - ( HWNOPRGE ) The Printer object reports non-normal conditions with the serial printer connected to the FC700A Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1305 Disarmed Ack The printer is off. The event has been acknowledged. 1306 Disarmed Unack The printer is off.
Building Technologies Fire Safety & Security Products Unidentified event - ( SYNOUDGE ) The `unindentified event` indicates the conditions, which could not be associated with any known object in the current structure.
Building Technologies Fire Safety & Security Products Australian single detector zone - ( FIDEZOSI ) The Single-Logic Fire Zone object represents a zone made up of a single detection element. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The event should now be acknowledged by the operator. 502 Alarm Unreset The event should now be reset by the operator.
Building Technologies Fire Safety & Security Products 812 Prealarm & Fault Unreset This event is the combination of the Prealarm and Fault state. The event should now be reset by the operator. 1000 Quiet No abnormal conditions present. 1105 Test Ack The event has been acknowledged. 1106 Test Unack The event should now be acknowledged by the operator. 1305 Disarmed Ack The event has been acknowledged. 1306 Disarmed Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Australian multi detector zone - ( FIDEZOMU ) In a Multi-Logic Fire Zone the alarm decision is based on the response of multiple detection elements affiliated with the zone. The conditions can be parameterised within the FC700A. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 812 Prealarm & Fault Unreset This event is the combination of the Prealarm and Fault state. The event should now be reset by the operator. 1000 Quiet No abnormal conditions present. 1105 Test Ack The event has been acknowledged. 1106 Test Unack The event should now be acknowledged by the operator. 1305 Disarmed Ack The event has been acknowledged. 1306 Disarmed Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Australian manual detector - ( FIDEZOMA ) The Fire Zone Manual object represents a zone made up of manual call-points (emergency alarm buttons). Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The event should now be acknowledged by the operator. 502 Alarm Unreset The event should now be reset by the operator.
Building Technologies Fire Safety & Security Products 1306 Disarmed Unack The event should now be acknowledged by the operator. 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The event should now be acknowledged by the operator. 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Australian flowswitch zone - ( BSCOZOFS ) This object represents a digital zones that processes binary information rather than danger levels. A logical TRUE signal of an individual detection device affiliated with the one suffices to reach the ALARM state.
Building Technologies Fire Safety & Security Products 1306 Disarmed Unack The event should now be acknowledged by the operator. 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The event should now be acknowledged by the operator. 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Australian sprinkler zone - ( FIEXZOSP ) The Extinguishing Sprinkler Zone object represents a zone that processes binary information. Associated extinguisher activators are set in alarm state with a YES/NO binary alarm signal. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 1306 Disarmed Unack The event should now be acknowledged by the operator. 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The event should now be acknowledged by the operator. 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Hong Kong flowswitch zone - ( BSCOZOFS ) This object represents a digital zones that processes binary information rather than danger levels. A logical TRUE signal of an individual detection device affiliated with the one suffices to reach the ALARM state.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Hong Kong sprinkler zone - ( FIEXZOSP ) The Extinguishing Sprinkler Zone object represents a zone that processes binary information. Associated extinguisher activators are set in alarm state with a YES/NO binary alarm signal Multistate Commands 1-Ack 800 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Prealarm Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Singapore flowswitch zone - ( BSCOZOFS ) This object represents a digital zones that processes binary information rather than danger levels. A logical TRUE signal of an individual detection device affiliated with the one suffices to reach the ALARM state.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Singapore sprinkler zone - ( FIEXZOSP ) The Extinguishing Sprinkler Zone object represents a zone that processes binary information. Associated extinguisher activators are set in alarm state with a YES/NO binary alarm signal Multistate Commands 1-Ack 800 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Prealarm Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Transfer record - ( HWCMLIGE ) Representation of a terminal/FG700A connection to the local FC700A Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The fault condition was detected. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Analog plus module - ( HWDADCRO ) Representation of the DS11-A (AnalogPlus) module hardware Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The fault condition was detected. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Analog plus line - ( HWDADCAD ) Representation of a DS11-A (AnalogPlus) detector line. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The event should now be acknowledged by the operator. 502 Alarm Unreset The object is in Alarm state. The event should now be reset by the operator.
Building Technologies Fire Safety & Security Products 2000 Fault Unack The fault conditions was detected.The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Digital collective I/O module - ( HWNOICCO ) Representation of a digital I/O module, Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1351 Anomaly Ack The object is impaired. The event has been acknowledged. 1352 Anomaly Unack The object is impaired. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Analog plus multiDevice - ( HWDAICGE ) Representation of an AnalogPlus digital I/O module, horn output module, collective input module or one part of a T-Tap device. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1351 Anomaly Ack The object is impaired. The event has been acknowledged.
Building Technologies Fire Safety & Security Products Lon device type 2 - ( HWLNCTGE ) Representation of a LON connected fire brigade terminal B3Q590. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1351 Anomaly Ack The object is impaired. The event has been acknowledged. 1352 Anomaly Unack The object is impaired. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Lon device type 3 - ( HWLNCCGE ) Representation of a LON connected floor panel B3Q580. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1351 Anomaly Ack The object is impaired. The event has been acknowledged. 1352 Anomaly Unack The object is impaired. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Lon device type 1&4 - ( HWLNSYGE ) Representation of a LON connected synoptic module K3I110 or K3I050. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1351 Anomaly Ack The object is impaired. The event has been acknowledged. 1352 Anomaly Unack The object is impaired.
Building Technologies Fire Safety & Security Products Lon device type 5 - ( HWLNICGE ) Representation of a LON connected I/O module. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1351 Anomaly Ack The object is impaired. The event has been acknowledged. 1352 Anomaly Unack The object is impaired. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Lon output table - ( HWLNOMGE ) Representation of a block of 16 LON indicators / outputs. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1999 Fault Ack The event has been acknowledged. 2000 Fault Unack The fault condition was detected. The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products FD20 Line - ( HWDADCAD ) Representation of a FD-20 detector line. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The event should now be acknowledged by the operator. 501 Alarm Ack The event has been acknowledged. 510 Alarm & Fault Unack This event is the combination of the Alarm and Fault state.
Building Technologies Fire Safety & Security Products FD20 I/O module - ( HWNODCCO ) Representation of a digital I/O module. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack The event should now be acknowledged by the operator. 502 Alarm Unreset The event should now be reset by the operator. 510 Alarm & Fault Unack This event is the combination of the Alarm and Fault state.
Building Technologies Fire Safety & Security Products FD20 MultiDevice - ( HWDAICGE ) This object represent the FD20 MultiDevice element . Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1351 Anomaly Ack The event has been acknowledged. 1352 Anomaly Unack The event should now be acknowledged by the operator. 1999 Fault Ack The event has been acknowledged.
Building Technologies Fire Safety & Security Products FD20 Element - ( FIDEDEAD ) The FD20 element represents a fire detector for automatic alarm detection Multistate Commands 1-Ack 946 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active Unack The event should now be acknowledged by the operator. 947 Active Ack The event has been acknowledged. 1000 Quiet No abnormal conditions present.
Building Technologies Fire Safety & Security Products Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel +41 41 724 24 24 Fax +41 41 724 35 22 www.sbt.siemens.com Document no. 008596_b Edition FC700A - Version 01.