MK8000 OPC Server Interface Specifications for FC700A Siemens Building Technologies Fire & Security Products
Siemens Building Technologies Fire & Security Products Data and design subject to change without notice. / Supply subject to availability. © Copyright by Siemens S.p.A. We reserve all rights in this document and in the subject thereof.
Siemens Building Technologies Fire & Security Products FG700A The FG700A is the interface of the FC700A CPU and its terminals. It is a component of the FC700 fire protection system.
Siemens Building Technologies Fire & Security Products FG700A - ( MGCMAPMN ) The Application object represents the events related to the entire FG700A system. Multistate Commands 1-Ack 500 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Unack Emergency operation alarm. An alarm has been signalled via the emergency operation system. This points to a fault in one of the Cbus node. The alarm point cannot be localized.
Siemens Building Technologies Fire & Security Products 1999 Fault Ack System is not reachable or an internal/external fault ocurred (acknowledged) 2000 Fault Unack System is not reachable or an internal/external fault ocurred (unacknowledged) 2051 Vitality Fault Missing vitality message (heartbeat): trouble in the communication link.
Siemens Building Technologies Fire & Security Products Power supply - ( HWNOPSGE ) Representation of power supply module Multistate Commands 1-Ack 1000 Quiet 1999 Fault Ack 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status One of the following faults exists in the function unit (acknowledged): - Power supply failure - Battery failure - End of battery autonomy - Module does not respond - Configuration error 2000 Fault Unack One of the fol
Siemens Building Technologies Fire & Security Products Transfer records - ( HWCMLIGE ) Representation of a CT11/FG700A connection to the local FG700A Multistate Commands 1-Ack 1000 Quiet 1999 Fault Ack 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Connection fault (acknowledged) 2000 Fault Unack Connection fault (unacknowledged) Page 7 of 8
Siemens Building Technologies Fire & Security Products Binary I/O Controller - ( HWNOICBI ) Representation of digital I/O module Multistate Commands 1-Ack 1000 Quiet 1999 Fault Ack 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status One of the following faults exists in the function unit (acknowledged): - processor failure - general fault - configuration error 2000 Fault Unack One of the following faults exists in the function unit (unackn