MK8000 OPC Server Interface Specification for CS6 Guarto Building Technologies Fire Safety & Security Products
Building Technologies Fire Safety & Security Products Data and design subject to change without notice. / Supply subject to availability. © Copyright by Siemens Switzerland Ltd We reserve all rights in this document and in the subject thereof.
Building Technologies Fire Safety & Security Products CS6 Guarto The security system CS6 is a combination of various disciplines: - Intrusion detection with individual addressing - Access control - Fire detection - CCTV (closed circuit television) - CMS (control monitoring station) - DOV (data over voice) communication Basically, the system consists of the control unit CC6 and the CT6 operating units. The door module DCU6 enables the access control readers to be connected to the system.
Building Technologies Fire Safety & Security Products CS6 Guarto - ( INNOAPMN ) The `Cs6 Guarto` object represents the entire CS6 and the geographical area covered by the intrusion protection. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present. 1351 Anomaly Ack The control unit is partialy reacheable 1369 Not Aligned The control unit is not aligned to the field.
Building Technologies Fire Safety & Security Products Area - ( INDEARGE ) The `Area` object represents the geographical area covered by the intrusion protection. The area is divided into a number of sections. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Door monitor zone - ( INBUZODM ) The `Door monitor zone` object represents the actual intrusion detectors handled by CS6 for door-motiroing and look-supervision. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected, they assume the state of their parent Section (Armed/Disarmed).
Building Technologies Fire Safety & Security Products 900 Tamper Unack This condition indicates that the detector has been tampered; the event should now be acknowledged by the operator. 901 Tamper Ack The intrusion detector has reported an Bolt Open. 902 Tamper Unreset The event should now be reset by the operator. 910 Tamper & Fault Unack This event is the combination of the Tamper and Fault state.The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack The anomaly indicates that the zone is not ready to be switched on (Armed) because the detector is currently triggered. This condition is reported when the parent section is commanded to switch on but the zone, if set on, would immediately be set in alarm. 1400 Disconnected The zone has been set out of service. When in this condition, the object will not generate alarms, tampers or faults.
Building Technologies Fire Safety & Security Products Terminal main CT6M / CT6C - ( INNOCTMN ) The `Terminal main CT6M / CT6C` object presents the possible conditions related to the CS6 main Terminal. The terminal CT6x is the main operating panel and display unit for the CS6 security and protection system.
Building Technologies Fire Safety & Security Products 802 Prealarm Unreset The event should now be reset by the operator. 810 Prealarm & Fault Unack This event is the combination of the Alarm and Prealarm state.The event should now be acknowledged by the operator. 811 Prealarm & Fault Ack This event is the combination of the Prealarm and Fault state. The event has been reset by the operator. 812 Prealarm & Fault Unreset This event is the combination of the Prealarm and Fault state.
Building Technologies Fire Safety & Security Products 1999 Fault Ack The event has been reset by the operator.
Building Technologies Fire Safety & Security Products Terminal auxiliary CT4-05 / 06 - ( INNOCTAX ) The `Terminal auxiliary CT4-05 / 06` object presents the possible conditions related to the CS6 auxilary Terminal. The CT4-0x is used in simple system as the main operating unit for the CS6.
Building Technologies Fire Safety & Security Products Management station supervision - ( INNOMSGE ) The `Management Station` object presents the possible conditions related to the Management Station connected to CS6. Multistate Commands 1-Ack 400 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm & Tamper Unack This event is the combination of the Alarm and Tamper state.The event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products 802 Prealarm Unreset The event should now be reset by the operator. 810 Prealarm & Fault Unack This event is the combination of the Alarm and Prealarm state.The event should now be acknowledged by the operator. 811 Prealarm & Fault Ack This event is the combination of the Prealarm and Fault state. The event has been reset by the operator. 812 Prealarm & Fault Unreset This event is the combination of the Prealarm and Fault state.
Building Technologies Fire Safety & Security Products 1999 Fault Ack The event has been reset by the operator.
Building Technologies Fire Safety & Security Products User group - ( INNOUGGE ) The `Users group` object represents the collection of the individual `User` objects. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present.
Building Technologies Fire Safety & Security Products User - ( INNOUSGE ) The `User` objects are the logical representation of the users defined in the CS6 system who are authorised to login and use the CT6 terminal for controlling the intrusion system. Multistate Commands 1-Ack 950 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active The user still have the factory code. 1000 Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Detection controller - ( INNODCGE ) Up to four detection Controller(s) are supported by the control unit. Multistate Commands 1-Ack 900 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Tamper Unack Indicates tamper from connection supervision (removal, malconfiguration) from Mbus devices. A fault will additionally be indicated in the object of the respective device.
Building Technologies Fire Safety & Security Products Power supply - ( INNOPSGE ) The Power Supply object reports the conditions determined by power supply monitoring. There is always a main power supply in the housing of the control pannel.
Building Technologies Fire Safety & Security Products Printer - ( INNOPRGE ) The `Printer` object represents the serial printing device being used in the CS6 control unit. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present. 1326 Blocked The printer is blocked. 1999 Fault Ack The event has been acknowledged.
Building Technologies Fire Safety & Security Products Control panel - ( INNOCCGE ) The `Control panel` object reports the conditions of the CS6 Control panel Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present 1300 Disarmed This condition indicates that the maintenance switch is on.
Building Technologies Fire Safety & Security Products Peripheral device - ( INNOPDGE ) The `Peripheral device` object presents the condition reported by the peripheral (remote alarming) equipment connected to the CS6 control unit. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present. 1400 Disconnected The Peripheral device (remote alarming) is physically disconnected.
Building Technologies Fire Safety & Security Products Cabinet protection - ( INNOCAGE ) The `Cabinet protection` object shows the conditions related to the protection against tampering with the CS6 cabinet. Multistate Commands 1-Ack 900 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Tamper Unack The tamper condition indicates that the CS6 cabinet has been opened; the event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Tamper control - ( INNOTCGE ) The `Tamper control` object shows the conditions related to the general tamper control of the CS6. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Service - ( INNOSRGE ) The `Service` object shows the conditions related to the service mode of the CS6. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present. 1100 Test The control unit is in service mode. Service mode means, the security system is for instance going to be maintained (e.g. detectors changed).
Building Technologies Fire Safety & Security Products Horn controller - ( INNOHCGE ) The `Horn controller` object shows the activity of a horn1 and a horn2 or a flashlight (external alarm equipment). Multistate Commands 1-Ack 950 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active The Horn Controller is active. 1000 Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Horn - ( INNOHOGE ) The `Horn` object represents a status of the horn device. Multistate Commands 1-Ack 900 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Tamper Unack This condition indicates that the horn has been tampered. The event should now be acknowledged by the operator. 902 Tamper Unreset The event should now be reset by the operator.
Building Technologies Fire Safety & Security Products I/O Device - ( INNOIOGE ) The `I/O device` object represents a status of the protected output devices (on Mbus). Important states can be assigned to this device. Multistate Commands 1-Ack 900 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Tamper Unack This condition indicates that the detector has been tampered with; the event should now be acknowledged by the operator.
Building Technologies Fire Safety & Security Products Access control section - ( ACDESEGE ) The `Access control section` is a folder for the Access control zone. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present.
Building Technologies Fire Safety & Security Products Access control zone - ( ACBUDRGE ) The `Access control zone` object represents the Access control zone of the CS6. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected. This object report the code violation, the duress alarm end door open timeout state.
Building Technologies Fire Safety & Security Products 802 Prealarm Unreset The event should now be reset by the operator. 810 Prealarm & Fault Unack This event is the combination of the PreAlarm and Fault state.The event should now be acknowledged by the operator. 811 Prealarm & Fault Ack This event is the combination of the PreAlarm and Fault state. The event has been acknowledged. 812 Prealarm & Fault Unreset This event is the combination of the PreAlarm and Fault state.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack Door open too long. 1400 Disconnected The zone has been set out of service. When in this condition, the object will not generate alarms, tampers or faults. 1999 Fault Ack The zone is in fault or the self test failed. The event has been acknowledged.
Building Technologies Fire Safety & Security Products Burglary zone - ( INBUZOGE ) The `Burglary zone` object represents the actual intrusion detectors handled by CS6. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected, they assume the state of their parent Section (Armed/Disarmed).
Building Technologies Fire Safety & Security Products 910 Tamper & Fault Unack This event is the combination of the Tamper and Fault state.The event should now be acknowledged by the operator. 911 Tamper & Fault Ack This event is the combination of the Tamper and Fault state. The event has been acknowledged. 912 Tamper & Fault Unreset This event is the combination of the Alarm and Fault state.The event should now be reset by the operator. 1000 Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Theft zone - ( INTHZOGE ) The `Theft zone` object represents the actual intrusion detectors handled by CS6. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected, they assume the state of their parent Section (Armed/Disarmed).
Building Technologies Fire Safety & Security Products 910 Tamper & Fault Unack This event is the combination of the Tamper and Fault state.The event should now be acknowledged by the operator. 911 Tamper & Fault Ack This event is the combination of the Tamper and Fault state. The event has been acknowledged. 912 Tamper & Fault Unreset This event is the combination of the Alarm and Fault state.The event should now be reset by the operator. 1000 Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Hold-up zone - ( INHOZOGE ) The `Hold-up zone` object represents the actual intrusion detectors handled by CS6. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected, they assume the state of their parent Section (Armed/Disarmed).
Building Technologies Fire Safety & Security Products 910 Tamper & Fault Unack This event is the combination of the Tamper and Fault state. The event should now be acknowledged by the operator. 911 Tamper & Fault Ack This event is the combination of the Tamper and Fault state.The event has been acknowledged by the operator. 912 Tamper & Fault Unreset This event is the combination of the Tamper and Fault state. The event should now be reset by the operator.
Building Technologies Fire Safety & Security Products Duress zone - ( INDUZOGE ) The `Duress zone` object represents the actual intrusion detectors handled by CS6. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected, they assume the state of their parent Section (Armed/Disarmed).
Building Technologies Fire Safety & Security Products 910 Tamper & Fault Unack This event is the combination of the Tamper and Fault state.The event should now be acknowledged by the operator. 911 Tamper & Fault Ack This event is the combination of the Tamper and Fault state. The event has been acknowledged. 912 Tamper & Fault Unreset This event is the combination of the Alarm and Fault state.The event should now be reset by the operator. 1000 Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Fire zone automatic - ( FIDEZOAU ) The `Fire zone automatic` object represents the actual intrusion detectors handled by CS6. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected, they assume the state of their parent Section (Armed/Disarmed).
Building Technologies Fire Safety & Security Products 910 Tamper & Fault Unack This event is the combination of the Tamper and Fault state.The event should now be acknowledged by the operator. 911 Tamper & Fault Ack This event is the combination of the Tamper and Fault state. The event has been acknowledged. 912 Tamper & Fault Unreset This event is the combination of the Alarm and Fault state.The event should now be reset by the operator. 1000 Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Fire zone manual - ( FIDEZOMA ) The `Fire zone manual` object represents the actual intrusion detectors handled by CS6. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected, they assume the state of their parent Section (Armed/Disarmed).
Building Technologies Fire Safety & Security Products 910 Tamper & Fault Unack This event is the combination of the Tamper and Fault state.The event should now be acknowledged by the operator. 911 Tamper & Fault Ack This event is the combination of the Tamper and Fault state. The event has been acknowledged. 912 Tamper & Fault Unreset This event is the combination of the Alarm and Fault state.The event should now be reset by the operator. 1000 Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Building services zone - ( BSDEZOGE ) The `Building services zone` object represents the actual intrusion detectors handled by CS6. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected, they assume the state of their parent Section (Armed/Disarmed).
Building Technologies Fire Safety & Security Products 910 Tamper & Fault Unack This event is the combination of the Tamper and Fault state.The event should now be acknowledged by the operator. 911 Tamper & Fault Ack This event is the combination of the Tamper and Fault state. The event has been acknowledged. 912 Tamper & Fault Unreset This event is the combination of the Alarm and Fault state.The event should now be reset by the operator. 1000 Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Burglary zone antimask - ( INBUZOAM ) The `Burglary zone antimask` object represents the actual intrusion detectors handled by CS6. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected, they assume the state of their parent Section (Armed/Disarmed).
Building Technologies Fire Safety & Security Products 901 Tamper Ack The detector is masked. The event has been acknowledged. 902 Tamper Unreset The event should now be reset by the operator. 910 Tamper & Fault Unack This event is the combination of the Tamper and Fault state.The event should now be acknowledged by the operator. 911 Tamper & Fault Ack This event is the combination of the Tamper and Fault state. The event has been acknowledged.
Building Technologies Fire Safety & Security Products 1999 Fault Ack The zone is in fault or the self test failed. The event has been acknowledged.
Building Technologies Fire Safety & Security Products Intrusion section - ( INDESEGE ) The `Intrusion section` objects are considered parts of the entire intrusion-protected area represented by the `Area` object. Sections can be switched on (Armed) and off (Disarmed) individually, by specific commands, or globally, by switching the Area on and off. A Section is made up of `Zone` objects. The connected zones inherit whatever state the Section is set to.
Building Technologies Fire Safety & Security Products Fire section - ( FIDESEGE ) The `Fire section` objects are considered parts of the entire intrusion-protected area represented by the `Area` object. Sections can be switched on (Armed) and off (Disarmed) individually, by specific commands, or globally, by switching the Area on and off. A Section is made up of `Zone` objects. The connected zones inherit whatever state the Section is set to.
Building Technologies Fire Safety & Security Products Building services section - ( BSDESEGE ) The `Building services section` objects are considered parts of the entire intrusion-protected area represented by the `Area` object. Sections can be switched on (Armed) and off (Disarmed) individually, by specific commands, or globally, by switching the Area on and off. A Section is made up of `Zone` objects. The connected zones inherit whatever state the Section is set to.
Building Technologies Fire Safety & Security Products Remote controller alarm - ( INNORCAL ) The `Remote transmission controller alarm` object presents the status of the remote calls made after an alarm has been detected. Multistate Commands 1-Ack 950 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active The alarm remote call has been triggered. 1000 Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Remote controller fault - ( INNORCFL ) The `Remote transmission controller fault` object presents the status of the remote calls made after a fault has been detected. Multistate Commands 1-Ack 950 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active The alarm remote call has been triggered. 1000 Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Remote device collective - ( INNORDCO ) The `Remote transmission device - collective` object represents the state of the parallel connected (8 channels) remote transmission device for simple alarming over PSTN.
Building Technologies Fire Safety & Security Products Remote device addressable - ( INNORDAD ) The `Remote transmission device - addressable` object represents the state of the serial connected remote transmission device for detailed alarming over PSTN.
Building Technologies Fire Safety & Security Products Time program - ( INNOTPGE ) The `Time Program` objects represent the time schedules that tell the system when to activate different levels of security during times such as normal business hours, nights, weekends and holidays. Multistate Commands 1-Ack 800 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Prealarm Unack The time program has been illegally manipulated by other means.
Building Technologies Fire Safety & Security Products User group list - ( UDUDOLMN ) The `User Group list` object represents the collection of the individual `User` objects. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present.
Building Technologies Fire Safety & Security Products Monitoring station - ( INNOMOGE ) The `Monitoring Station (CMS)` is a recipient of an addressable remote transmission device Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present. 1999 Fault Ack The event has been acknowledged by the operator.
Building Technologies Fire Safety & Security Products Clock - ( INNOCLGE ) The `Clock` object represents the collection of the information about the time synchronization of the CS6. Multistate Commands 1-Ack 501 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Alarm Ack The clock is not synchronized. The event has been acknowledged. 511 Alarm & Fault Ack This event is the combination of the Alarm and fault.
Building Technologies Fire Safety & Security Products Physical tree - ( UDUDOLMN ) The `Physical tree` object represents the collection of the objects related to the CS6 hardware components. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present.
Building Technologies Fire Safety & Security Products Peripheral devices - ( UDUDOLMN ) The `Peripheral devices` object represents the collection of the objects related to the CS6 peripheral devices. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present.
Building Technologies Fire Safety & Security Products Alarming devices - ( UDUDOLMN ) The `Alarming devices` object represents the collection of the objects related to the CS6 alarming devices.. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present.
Building Technologies Fire Safety & Security Products Intrusion section list - ( UDUDOLMN ) The `Intrusion Section list` object represents the collection of the individual `Section` objects. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present.
Building Technologies Fire Safety & Security Products Time channels list - ( UDUDOLMN ) The `Time Channels list` object represents the collection of the individual `Time program` objects. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present.
Building Technologies Fire Safety & Security Products Access control section list - ( UDUDOLMN ) The `Access Control Section list` object represents the collection of the individual `Access Control Section` objects. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal conditions present.
Building Technologies Fire Safety & Security Products Access control zone alarm - ( ACBUDRUD ) The `Access control zone` object represents the Access control zone of the CS6. The zones are the lowest hierarchical level that is visible to the user. Unless the individual zone has been disconnected. This object report the code violation, the duress alarm end door open timeout state.
Building Technologies Fire Safety & Security Products 802 Prealarm Unreset The event should now be reset by the operator. 810 Prealarm & Fault Unack This event is the combination of the PreAlarm and Fault state.The event should now be acknowledged by the operator. 811 Prealarm & Fault Ack This event is the combination of the PreAlarm and Fault state. The event has been acknowledged. 812 Prealarm & Fault Unreset This event is the combination of the PreAlarm and Fault state.
Building Technologies Fire Safety & Security Products 1351 Anomaly Ack Door open too long. 1400 Disconnected The zone has been set out of service. When in this condition, the object will not generate alarms, tampers or faults. 1999 Fault Ack The zone is in fault or the self test failed. The event has been acknowledged.
Building Technologies Fire Safety & Security Products Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel +41 41 724 24 24 Fax +41 41 724 35 22 www.sbt.siemens.com Document no. 007545_g Edition CS6 Guarto - Version 01.