User Manual

Building Technologies
Fire Safety & Security Products
The `Management Station` object presents the possible conditions related to the Management Station connected to CS6.
Management station supervision - ( INNOMSGE )
Multistate Commands
1-Ack 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status
400 Alarm & Tamper Unack
This event is the combination of the Alarm and Tamper state.The event should now be acknowledged by the operator.
402 Alarm & Tamper Unreset
This event is the combination of the Alarm and Tamper state. The event should now be reset by the operator.
500 Alarm Unack
This is a severe and high-risk condition which indicates that a threatened user has entered the Duress password on a terminal; the event should now be acknowledged by the operator.
502 Alarm Unreset
The event should now be reset by the operator.
510 Alarm & Fault Unack
This event is the combination of the Alarm and Fault state.The event should now be acknowledged by the operator.
511 Alarm & Fault Ack
This event is the combination of the Alarm and Fault state. The event has been reset by the operator.
512 Alarm & Fault Unreset
This event is the combination of the Alarm and Fault state. The event should now be reset by the operator.
800 Prealarm Unack
This is an indication that a potentially dangerous condition occurred on the Management station, the list includes 2 cases, namely:
- an authorised user (one given special permissions) logged-on to the terminal resetting his/her password because he/she has forgotten his/her valid access code;
- an individual entered a wrong password code too many times on the Management Station;
The event should now be acknowledged by the operator.
Page 13 of 70