Table of Contents About this document.........................................................................................................4 1 Safety regulations ..............................................................................................7 1.1 Country-specific standards...................................................................................7 1.2 Commissioning and testing ..................................................................................7 1.
About this document About this document Purpose This manual is intended as a guide to the installation and configuration for the MM8000 management stations that includes control units supporting the CDDL/CDSF protocol. It presents the MM8000 Add-on module for the CDDL/CDSF support.
About this document - Document Type: All - Image Type: All - Advanced search criterias: Select Brochure No. and enter the document number to search for (A6V10089056). Alternatively, select Title and enter the product name (DMS8000). 2. Click Search to start. 3. In the resulting area on the right, click on Contents link to show the list of search results. For more information such as Siemens news and announcements, visit the STEP Web portal at: https://workspace.sbt.siemens.
About this document point. Conditions that you must complete or must be met before beginning a procedure are designated with a ⊳. Results, after completing a step or at the end of the entire procedure, are designated with a ⇨. ⊳ The report you want to print is open. Bold font in a procedure indicates something you should select or type. Type F for Field panels. Click OK to save changes and close the dialog box. Menu paths are indicated in bold.
Safety regulations Country-specific standards 1 1 Safety regulations This section describes the danger levels and the relevant safety regulations applicable to the use of the products described in this manual. Please read the following work instructions as well as the preceding section About this document thoroughly before beginning any work. 1.1 Country-specific standards Siemens products are developed and produced in compliance with the relevant international and European safety standards.
2 Introduction Modifications to system design and products 2 Introduction CDDL/CDSF protocol Some of the FS-DMS legacy subsystems and a number of 3rd party units have applied the CDDL/CDSF protocol suite to exchange application messages with LMSmodular management station. The CDDL (Cerberus Dati Data Link) is a data-link protocol specifying the data exchange across a serial RS232 point-to-point connection. For more information about CDDL, please refer to document CDI-135-017-E.
Introduction What's new 2.1 2 What's new Here is the list of modifications for new functions and software improvements. Section Modifications N/A N/A 9 Building Technologies Fire Safety & Security Products A6V10067787_a_en 30.06.
3 Installation Add-on distribution package 3 Installation 3.1 Add-on distribution package The MM8000 software for the control unit support is distributed as an add-on package, to be installed on the stations including the Composer tool (client-only and FEP stations are therefore excluded) after the standard MM8000 Setup. The package is named MM8000 MPx.xx.xx - System Extension N.06 (CDSS Vy.yy) and is made up by an installation kit of a few files.
Installation Software installation 3 2. Install the NK8000 units (NK82xx). Refer to NK8000 Installation, Configuration and Commissioning 3. On the station(s) with configuration capability (Composer tool), install the add-on module [➙ 12]. 4. Customise the model [➙ 13] according to the modelling solution. 5. Update the NK8000 firmware [➙ 19]. 3.2 3.2.1 Software installation Requirements This add-on does not add any special requirements to the standard MM8000 setup.
3 Installation Software installation 3.2.3 Installing the Add-on module The following is the installation procedure for the add-on module. WARNING Add-on versions older than MP4.15 require a different installation procedure; for such cases, please refer to the add-on manual of the corresponding version. 3.2.3.1 Installation on MM8000 MP4.15 and later A specific application – the Add-on Manager – is provided starting from MM8000 MP4.15, and allows installing and updating the add-on modules.
Installation Model customisations 3.3 3 Model customisations The CDSF standard (refer to document CDI-130-017-E, edition 01.1994) defines a general message structure which can be applied to any data communication involving a set of multi-state variables. In MM8000 applications, the protocol can be used using a 3-step approach: 1. Meta-model definitions A general set of meta-model definitions have been defined in the web-based Poseidon modelling environment (refer to FS-DMS document 2004-0217-00-Eng).
3 Installation Model customisations 3.3.1 Customisation tool The tool is a Windows program named CDSS Meta Subsystem Tool.exe, which is available in the folder: \DMS8000\Composer\Configuration Data\OTD_Files\ Note: is usually C:\Program Files\ 3.3.1.1 User Interface Starting the program, the following window appears.
Installation Model customisations 3.3.1.2 3 Configuration fields Control Unit Settings Description Name of the model currently opened: a free text Discipline Application discipline, which defines the meta-model that is applied and the correspondent superset of object list. Note that, after you define a specific object to be part of the model, the discipline can no longer be modified.
3 Installation Model customisations value 5 is used to command Zone 5 corresponding to CDSF point 25, assuming the zone type starts at index 21). Full Range Offset: Same as previous, but capable of handing multiple offset ranges (relative addressing; e.g.: the value 15 is used to command Zone 15 corresponding to CDSF point 55, assuming the zone type ranges from 21 to 30 and then from 51 to 60). Parent Point: The parent of the involved point is used as parameter (absolute point addressing).
Installation Model customisations 3.3.1.3 3 Main menu The tool menu includes the following commands: File Open Open one of the existing models, which are stored in .CUB files, located in the same folder as the tool program. Note that a new model can be added by simply typing its name in the Description field, filling in the information, and then saving it. Save Save the model into the .CUB file on disk. Exit Close the tool program.
3 Installation Model customisations 8. Select the CDSF point range (From/To) associated to the Panel object. Typically, this is a single CDSF point (From = To) representing a general summary of the control unit status. Leave the (parent) Point Number = 0. 9. In the Configured States list, add the required lines according to the possible conditions of the CDSF point. 10. For each state, define the associated commands (ID Com) and the CDSF Value. Note that CDSF Message Type is usually =0. 11.
Installation Communication network 3.4 3 Communication network The control unit is connected to the MM8000 system by means of the NK8000 network and namely via the NK82xx units. In order to communicate with the control unit, the NK82xx units should however be equipped with a new firmware that is included in the installation package as an additional component (DLL) to be added to the standard firmware file set.
3 Installation Communication network 2. Expand the Channel collection folder in: Supervision System Settings > MM8000 System > Physical configuration > Station (or FEP) > Channel collection 3. Select the NS8210 driver node and then the Download tab. Download tab 4. Select all the branches (NK82xx) in the list located in the upper part of the form. Note: In order to select multiple branches, keep the CTRL key pressed while you make your selections. See the following: Selecting the NK82xx 5.
Installation Communication network 3 In a few moments, the new firmware shows in the Firmware List. The _0x suffix in the firmware name indicates the add-on index. 6. Select the new firmware version in the Firmware List. 7. Click the Download Firmware button. The download procedure starts. The new firmware is downloaded to the NK82xx units via FTP (File Transfer Protocol) services over the network. 8. Ensure that you have successfully completed all downloads.
4 Configuration Configuration checklist 4 Configuration 4.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. Items needed for configuration The number and model of CDSS systems. The local address (0 to 65535) for each unit. Exact information on the CDSS internal configuration. The exact connection to the NK8000 unit (NK82xx).
Configuration Configuration procedure 4 The new node is added to the project structure. Note: You can customise the default name of the new node typing in a new name in the Description field of the Node tab. Adding an CDSS subsystem Setting the CDSS Local Address 1. Select the CDSS node. 2. Click the Node tab. The Node form page shows. 3. In the Node tab form, you can find: - Description text: the node name you also have on the project structure tree.
4 Configuration Configuration procedure Setting CDSS mode (subtype) and the unit Local Address Manual configuration You can configure the CDSS unit to reflect the actual field configuration. Object types and ranges depend on the model definitions. Linking the Communication network 1. Open NK82xx sub-folders. Expand the NK8000 network folders until you reach the node that represents the NK882x COM port that is physically connected to the control unit. 2. Select the control unit node. 3.
Configuration Configuration procedure 4 Setting the communication baud rate 1. Select the new link node just below the NK82xx serial line node. 2. In the Node tab, set the communication baud rate, which must match the corresponding setting in the control unit. Setting the baud rate Downloading the MM8000 configuration Before operating with the new MM8000 configuration, you need to download it. In Composer, the download command is available in the Tools menu.
4 Configuration Configuration backup and restore - Ensure that you have successfully completed all downloads. Verify that the Cfg Downloaded checkboxes contain X’s 2. In the NS82xx node (select all units one after the other): 4.3 - Right click the node. - In the menu, click Node commands > Download file CNF. Configuration backup and restore The standard Backup and Restore functions in Composer provide for saving the CDDL/CDSF customized models [➙ 14] along with all the project data.
Annex A – CDDL/CDSF meta-models Annex A – CDDL/CDSF meta-models The following meta-models are provided for direct use or further customisations: CP100 gas detection unit AVOTEC fire alarming unit PATROL intrusion detection unit 27 Building Technologies Fire Safety & Security Products A6V10067787_a_en 30.06.
Issued by Siemens Switzerland Ltd Infrastructure & Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID A6V10067787_a_en Edition 30.06.2013 © 2013 Copyright Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.