DMS8000 MP4.
Data and design subject to change without notice. / Supply subject to availability. © 2009 Copyright by Siemens Switzerland Ltd We reserve all rights in this document and in the subject thereof.
Table of contents About this document...............................................................................................4 1 1.1 1.2 1.3 Introduction .............................................................................................6 What has been changed in MP4.20 configuration tools ...........................7 1.1.1 Documentation changes and corrections in this edition .............7 Overview of networks and subsystems ....................................................
.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 Configuring a CS1115...........................................................................101 4.3.1 Configuration checklist............................................................101 4.3.2 Configuration procedures – CS1115 systems ........................103 4.3.3 Configuration procedures – CS1115-x ...................................104 4.3.4 Configuration procedures – CS1115-ECO .............................107 4.3.
.3 5.4 5.5 5.6 6 6.1 6.2 6.3 6.4 7 7.1 7.2 5.2.4 Configuration checklist ...........................................................174 5.2.5 Configuration procedures .......................................................175 Configuring a CS6 Guarto.....................................................................177 5.3.1 Configuration checklist ...........................................................178 5.3.2 Configuration procedures .......................................................
Introduction About this document Purpose of this document This manual is for use during the configuration of Danger Management Systems (DMS) and Building Automation Systems (BMS) that include the following: − MM8000 Management Station − MT8001 Management Terminal − MK8000 OPC Server for Subsystems − NK8000 network devices − DESIGO INSIGHT (for FS devices connectivity via NK8000) It is a guide to, and reference for the manual configuration of networks and subsystems supported by these products.
Introduction 4. Enter the document number in the Brochure No. field (A6V10089056) and press Enter. Operational and safety regulations i Before groups of persons begin work on any DMS system, they must have read and understood the related documents. In particular the Safety Regulations included in the Installation, Configuration, and Commissioning manual (ICC) for each specific product.
Introduction 1 Introduction Siemens fire safety and security products are designed to work together. While there are many occasions where only one product may be used in a facility, when combined our products create a robust and flexible set of architectural and connectivity solutions. The possible combinations of Danger Management Systems (DMS), network choices, and subsystems used in any given plant are extensive. However, the time involved with commissioning tasks can be substantial.
Introduction 1.1 What has been changed in MP4.20 configuration tools Here is the list of modifications included in MP4.20 for new functions and software improvements. 1.1.1 Section, Page Modifications Various pages New NK8232 supporting same features as NK8222. New NK8235 supporting same features as NK8225. New NK82xx reference, also including NK8232 and NK8235. p. 13 Configuration of the project channel: Solutions/Products 4.6, p. 133 New configuration guide for XLS/XNET fire control unit 5.
Introduction 1.2 Overview of networks and subsystems Siemens Building Technologies products are organised into three levels: • Management level: It presents the events, and allows for control of the site via the management station(s). The majority of the human interface takes place at this level. • Automation level: The majority of the real-time control functions are carried out at this level. It provides data communication links between the other two levels and defines the network topology and structure.
Introduction 1.3 Additional documents Depending on your level of experience with Composer, and the architectural solutions available with our products, as well as where you are in the commissioning process, there are a number of additional documents that you may find useful. If you need a document that you do not have, you can download it on the Siemens Intranet.
Configuration process overview 2 Configuration process overview DMS8000 Configuration Process Overview The following overview is a general guide to the phases or steps that occur in the configuration process. Documentation that supports a given step is shown at right. The order in which these tasks are performed may vary depending on personal preference or specifications in the product configuration manual. This is not an absolute guide, but rather lends context to the tasks discussed in this manual. 1.
Configuration process overview 2.1 Porting existing configuration databases The DMS8000 configuration tools allows for restoring the configuration of existing installations. The following formats are supported: • Configuration database backup of previous versions of the same DMS8000 product (MM8000, MK8000, or MT8001). Refer to the specific Release Notes of the latest software for detailed information.
Configuration process overview Use the “right-click” menu for common tasks The right-click menu contains the most common tasks you will need to perform in Composer, such as deleting a folder or icon. Refer to the Composer Technical Manual for general functions and shortcuts While basic tasks for setting up a project in Composer are covered here briefly, Composer contains a number of functions and shortcuts that may prove to be valuable timesavers as you become more familiar with using it.
Configuration process overview 2. Select the entire list of subsystem tools in the right column 3. Click the Install button The list of Plug-ins appears in the Plug-ins Installed pane (see Fig. 1 at p.13). Note that this may take a couple of minutes. Watch the Installer messages at the bottom of the window to monitor the status. 4. Click Exit Fig.
Configuration process overview Product Authorisation Key (PAK) Customer Keys are associated to PAKs that enable the specific connectivity and functions required on each site. Service Keys also require a PAK that only includes the channel (Service or Product) and expiration date. Starting from one month before the actual expiration, a specific message warns Composer users about the need of renewing the service key license. The PAK is printed on the License of Use that came with the hardware key.
Configuration process overview Warning: Before entering the PAK, press the backspace key to ensure that there are no spaces in the PAK field. Also, when you enter the PAK, do not type any dashes or spaces. For example, if the License PAK is: TJNW-NHVX-UKS3-LIAY, the code should be entered as: TJNWNHVXUKS3LIAY. Please note that the number 0 (zero) is not used. 7. Click Save. The license appears in the Available licenses list. 8. Verify that the Valid with version number field reads Y (for Yes), see Fig. 3.
Configuration process overview Import PAK from the .REG file If you received the PAK in a file with the extension .REG, do the following: 1. Copy the file on your local computer disk. 2. Select the menu command File Æ Import PAK. A file browsing window displays. 3. Locate and select the .REG file, click OPEN 4. Confirm you want to merge the new codes in the system registry. The file is read and the PAK code imported.
Configuration process overview 2.3.4 Checking the license requirements Composer can provide the detailed license requirements for the current configuration. Select the main node of the DMS8000 system, e.g. Project Æ MK8000 System Æ MK8000 and then the Node tab (Fig. 6). In the page that appears, click View License Data. The resulting list shows the required license parameters for the current configuration. Note the Available License column that shows Unknown.
Configuration process overview Note: Older version of Composer (e.g. MP3.15 and earlier) will show a different welcome window. Please refer to the previous editions of this guide. Projects can take quite a bit of space on the hard disk. Therefore, it is not recommended that you create multiple copies of the same project. If you wish to save a particular project configuration for later use, you can do this using the backup function (see section 7 at p.224). Fig.
Configuration process overview 2.4.2 Setting up the structure Now that you have created the project, you need to set up the node structure to reflect the structure of the site. Please refer to the specific DMS Installation Configuration & Commissioning manual (ICC) (reference documents are listed in the Resource Information document described at p.4).
Configuration process overview Fig. 10 Selecting project version Here you can select how you want Composer to handle the project, whether you want to update it to a newer version or keep it as it is. Obviously, the decision depends on which DMS8000 product version will be running this project on site. 20 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring networks and network components 3 Configuring networks and network components This section describes how to configure networks. Possible networks are: − Cerloop − CDI-Net − NK8000 − BACnet The networks consist of the following components: − MK7022 − GW21 − GW20 − NK8222 − NK8223 − NK8225 − NK8232 − NK8235 Note: A direct connectivity to the DMS8000 management system is possible for several types of units, either over a serial line or via a local area network.
Configuring networks and network components 3.1 Configuring Cerloop The Cerloop network provides a redundant connectivity solution for Siemens fire, safety, security, and 3rd party control units. The network has a ring topology, and each unit can communicate via two different wiring paths, thus assuring a redundant link in case of failure in any point in the loop.
Configuring networks and network components 3.1.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The number of Cerloop networks. For each Cerloop: – The type of each control unit connected to it (CZ10, CS11, etc.), and its local address (111, 112, etc.) – The number of MK7022 interface(s) to be used for accessing the loop.
Configuring networks and network components 3.1.2 Configuration procedures Adding the Cerloop network node to the network folder 1. Select the destination folder. 2. In the left-hand bar, select the Network folder icon 3. In the menu that appears, select the Cerloop Network icon to add the Cerloop network node (see Fig. 12-A). A new node is added to the project structure. Fig. 12 Selecting the icon to add a new Cerloop node Adding the MK7022 node to the Cerloop network 1.
Configuring networks and network components Fig. 14 Setting the MK7022 local address Linking the MK7022 node to the Cerloop driver Note: These connections can be made once the DMS and the subsystems of the Composer project have been inserted. The order in which you perform these connections may vary from the following steps. Also, note that the MK7022 may also be connected to a CDI-Net or NK8000 port. 1. Select the MK7022 node.
Configuring networks and network components − The communication baud rate (either 1200 or 2400 baud). This value must match the actual MK7022 hardware setting. 3. The flow control parameters - specifically Message rate, Sample time, and Status request timeout – do not usually require any modification. They may be required, however, for tuning the status requests in case of large systems. See p.80. Fig.
Configuring networks and network components 3.2 Configuring CDI-Net The CDI-Net network provides point-to-point connectivity solutions for Siemens fire, safety, security, and 3rd party control units. CDI-Net is a family of products including: • GW20 gateway, that supports up to 20 RS232 lines to subsystems (downstream), and up to 4 RS232 lines to the DMS (upstream). • GW21 gateway, that supports up to 4 RS232 lines to subsystems (downstream), and up to 2 RS232 lines to the DMS (upstream).
Configuring networks and network components 3.2.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The number and the type of gateways, as well as the global connectivity architecture. The hardware configuration in relation to the RS232 lines that should be used for each gateway. The connectivity to the DMS (lines, protocol setting).
Configuring networks and network components 3.2.2 Configuration procedures Adding the CDI-Net network node to the network folder 1. Select the destination folder. 2. In the left-hand bar, select the Network folder icon 3. In the menu that appears, select the CDI-Net icon to add the CDI-Net network node (Fig. 19-A). A new node is added to the project structure. Fig.
Configuring networks and network components Fig. 21 Selecting the icons to add the GW20 pads A Click this icon to add a Subsystem Pad, for connecting a subsystem. B Click this icon to add a NetM Pad, for connecting a GW21 in a 2-level network. C Click this icon to add a FHI Pad, for connecting a Foreign Host. D Click this icon to add a Nise Pad, for connecting NCRS (BAU). Note: Each pad is equipped with 4 serial lines.
Configuring networks and network components Æ See “Expansion option” at p.31. 4. Double-click the Lines folder to open it. 5. Select a line (1-4). 6. Set the Line Type in the Node tab. Æ See Fig. 23, the following table, and the Line type descriptions. 7. Repeat steps 5 and 6 for all four (or six) lines. Fig. 23 Setting the type of GW21 line GW21 line types CMS Line 1 X Line 2 X Subsyst.
Configuring networks and network components Fig. 24 Adding the GW21 expansion board Connecting CDI-Net to the DMS This connection can be made once the DMS components of the Composer project have been inserted. The order in which you perform this connection may vary from the following steps. 1. Select the line. Expand the folders in the Communication network until you reach the DMS line. 2. Locate the CDI-Net driver.
Configuring networks and network components Fig. 26 Connecting GW21 line to DMS Setting the communication parameters for the CDI-Net driver (NS8012) 1. Select the Node tab of the COM port link node under CDI-Net driver. 2. Adjust the CDI-Net communication parameters (see Fig. 27): − The number of the hardware port to be used by the DMS − The communication baud rate (ranging from 2400 to 9600 baud) This value must match the actual GW2x hardware setting. 3.
Configuring networks and network components 3. Select the subsystem node. Note: depending on the subsystem type, you may have to select the control unit node (such as CZ10, CS4, CZ12, CF9000 etc.) or its gateway (such as CK11 for CS11, SK11 for STT11 etc.). Æ See specific instructions in the section dedicated to each subsystem. 4. Drag and drop the subsystem to the associated CDI-Net line. See Fig. 28 below. The subsystem node appears in the hierarchical tree under the associated line. Fig.
Configuring networks and network components Fig. 29 Linking GW21 to GW20 in a 2-level CDI-Net 35 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring networks and network components 3.3 Configuring NK8000 The NK8000 network, formerly CDI-WAN, provides IP and Dial-up connectivity solutions for Siemens and 3rd party control units. NK8000 is a family of network products including: • NK8222 Ethernet port: LAN/WAN (CMSDL/IP, CEI-79) and Dial-up (CEI-79) communication unit supporting one subsystem connection over RS232 line or CerCom/LON bus, and local I/O units. It can provide local interactions between the connected subsystem and local I/O.
Configuring networks and network components Failing to correctly set the type results in error in the configuration and download procedures. Depending on the type of upstream connection to the DMS host, the NK8000 network can be set-up in three ways: serial, dial-up or LAN/WAN connectivity. The dial-up solution can also be combined to the LAN/WAN mode as backup option.
Configuring networks and network components It is allowed to mix serial and LAN/WAN mode in a single NK82xx unit. In other words, Composer tool can configure and download NK82xx configurations that include both a LAN/WAN and a serial connection to two DMS hosts. → The DMS8000 LAN mode is presented in section 3.3.3 at p.48. All NK82xx units as well as the network drivers NS8012, NS8210, and NS8011 are fully configured and downloaded in Composer.
Configuring networks and network components 3.3.1.1 Configuration checklist NK82xx units can communicate with DMS8000 host via serial line in the so-called “CDI-Net emulation” mode. If you are familiar with CDI-Net family of products, be informed that this solution results in the NK82xx being used as a GW21. The number of serial connections available at management station level depends on the specific product; please see the relative ICC (Installation, Configuration, and Commissioning) manuals.
Configuring networks and network components ITEMS NEEDED FOR CONFIGURATION The number and the type of gateways, and the global connectivity architecture. The NK82xx IP address, as initially loaded with NW8202 or NW8204. – Refer to NK8000 ICC guide (doc. no A6V10062437). The hardware configuration in relation to the RS232 lines used for subsystem connectivity on each gateway. The connectivity to the DMS (lines, protocol setting).
Configuring networks and network components 3.3.1.2 Configuration procedures Adding and configuring an NK82xx node 1. Select the destination folder. 2. In the left-hand bar, select the Network folder icon 3. In the menu that appears, select the NK82xx icon to add the NK82xx node (see Fig. 31-A). A new node is added to the project structure. Fig. 31 Selecting the icon to add an NK82xx node Connecting NK82xx to DMS 1. Double-click the NK82xx node.
Configuring networks and network components Fig. 32 Connecting NK82xx directly to DMS Setting the communication parameters for the CDI-Net driver (NS8012) 1. Select the Node tab of the COM port link node under CDI-Net driver. 2. Adjust the CDI-Net communication parameters (see Fig. 27 at p.
Configuring networks and network components 3.3.2 NK82xx for dial-up connectivity Fig. 33 Example of NK8000 dial-up connectivity 3.3.2.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. The NW8202 tool should be used prior to configuring NK8000 in Composer. That is required for setting a valid IP address for downloading.
Configuring networks and network components ITEMS NEEDED FOR CONFIGURATION The number and the type of gateways, as well as the global connectivity architecture. The NK82xx IP address, as initially loaded with NW8202 or NW8204. – Refer to NK8000 ICC guide (doc. no A6V10062437). The hardware configuration in relation to the RS232 lines used for subsystem connectivity on each gateway.
Configuring networks and network components Configuring the NS8210 driver 1. Open the Channel collection in: MM8000 (or MK8000) System Æ Physical configuration Æ Station (or FEP) Æ Channel collection 2. Select the NS8210 driver for CEI-79 link to DMS8000. 3. Configure the network options: select the driver node (See Fig. 34). A form appears on the right side of the screen. Fig.
Configuring networks and network components 4. Select the Node tab of the new modem node and configure the following: − Phone number of the DMS8000 location − AT initialization string − AT end-of-command string − AT reset string − Modem signals check interval (in sec.) − If required, set the “Pulse” mode (default is “Tone”).
Configuring networks and network components Adding and configuring the NK82xx modem 1. Select the parent node for the communication network. . 2. In the left-hand bar, select the Network folder icon 3. In the menu that appears, select the Modem icon to add the modem node. A new node is added to the project structure. 4.
Configuring networks and network components 3.3.3 NK82xx for upstream IP connectivity to DMS8000 Fig. 35 Example of NK8223 IP connectivity to DMS8000 Fig. 36 Example of NK8225 IP connectivity to DMS8000 Note that NK8222 and NK8223 do not support BACnet and cannot connect to NS8011 BACnet Driver. 48 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring networks and network components 3.3.3.1 Configuration checklist The NK82xx units can communicate with DMS host over TCP/IP networks. You can define and download the NK8000 technical configuration with Composer tools. The NW8202 or NW8204 tool is necessary to initialise the IP address of NK82xx units prior to downloading configurations from Composer. Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows.
Configuring networks and network components CONFIGURING NK8000 1. Configure the NS8210 or NS8011 driver in the DMS channel p. 51 2. Add folders as required for representing your geographical structure. 3. Add and configure the NK82xx unit p. 52 4. Configure the Ethernet link p. 53 5. Connect NK82xx to the main DMS host on NS8xxx driver p. 55 6. Connect NK82xx to additional DMS host(s) p. 56 7. Connect subsystems to NK82xx p. 59 8. Configure the local I/O modules, if used p. 61 9.
Configuring networks and network components 3.3.3.2 Configuration procedures The following are the configuration procedures required for the NK8000 IP network based on NK82xx units. Configuring the NS8210 driver (or NS8011) 1. Open the Channel collection in: MM8000 (or MK8000) System Æ Physical configuration Æ Station (or FEP) Æ Channel collection 2. Select the NS8210 driver for CMSDL/IP or CEI-79 link to DMS8000 -- or -the NS8011 driver for BACnet/IP connectivity to DESIGO or DMS8000.
Configuring networks and network components BACnet router in DMS8000 Broadcast Distribution Mask BACnet Subnet Mask the DMS8000 PC. In case of multiple LAN adapters, you can select here the one working on BACnet. Subnet Mask should be configured as for any IP device UDP Port UDP data port for BACnet services Data Port is 47808 (BAC0 Hex) by default and normally should not be changed. Device Identifier Address of the DMS8000 system in the BACnet network.
Configuring networks and network components is designed to support the representation of dispersed units, and to allow for distributing the unit nodes in multiple folders. 2. In the left-hand bar, select the Network folder icon 3. In the menu that appears, select the NK82xx icon (see Fig. 39). to add the NK82xx node A new node is added to the project structure. Note: The default configuration includes the first upstream network connection, I2C lines, two serial ports, Clock, and Tamper control.
Configuring networks and network components The CEI protocol must be necessarily selected when the dial-up connectivity is required. An additional connection over serial line (CMSDL) can also be supported. This option, however, will limit the CMSDL/IP or BACnet/IP links to three instead of four. Fig. 40 Configuring IP parameters for a network with NAT gateway 4.
Configuring networks and network components Fig. 41 Configuring NK82xx Ethernet and CEI-79 parameters Connecting NK82xx to the DMS 1. Open the Channel Collection in: MM8000 (or MK8000) System Æ Physical configuration Æ Station (or FEP) Æ Channel collection You will see the NS8210 driver node (CMDSL/IP or CEI-79/IP) or the NS8011 driver (BACnet/IP). 2. Select the NK82xx node. 3. For connecting to NS8210 (but not to NS8011) select the Ethernet node. 4.
Configuring networks and network components Fig. 43 Setting “Branch In Scan” and the CEI Master key in the NK82xx link node Connecting NK82xx to additional DMS hosts (CMSDL/IP) NK82xx can be connected to additional CMSDL/IP hosts, they can support as many as four connections, including serial (max 1) and LAN (max 4) links. – The configuration of each DMS8000 host requires a separate Composer project. In order to add an additional connection, proceed as follows: 1. Select the NK82xx node. 2.
Configuring networks and network components Assuming that as many as four DMS hosts are connected to the same NK82xx, and that the first port (3001) is used by the first DMS (that is, the corresponding icon is linked to the NS8210 driver as described at p.55), then the configuration of the other hosts should include the links of the Ethernet icons with port 3002, 3003 and 3004, respectively.
Configuring networks and network components Note that each host node must be configured on the Node tab with the corresponding unique BACnet Device Identifier (Instance number) as shown in see Fig. 47. Then, the main node of the unit can be connected to the hosts (max four connections) identified by their device identifier.
Configuring networks and network components Fig. 48 Linking an additional host connection over serial line Note that the configuration of the “additional” host will require a separate project where the NK82xx will appear connected to the station over a serial line (see 3.3.1 at p.38). For example, assuming a system with one host on LAN (main DMS) and one host over serial line (additional DMS), you need 2 projects: – Project 1 (main DMS) should include an NK82xx with one Ethernet link and one serial link.
Configuring networks and network components Otherwise, proceed to step 3. 3. Expand the tree structure until you reach the subsystem you want to connect. Note: If needed, you can add the serial line expansion (Fig. 50) or the LON expansion (Fig. 44-B). 4. Select the subsystem node. Note: Depending on the subsystem type, you may have to select the control unit node (such as CZ10, CS4, CZ12, etc.) or its gateway (such as CK11 for CS11, SK11 for STT11, etc.).
Configuring networks and network components Configuring the local I/O If local I/O modules are used, do the following: 1. Expand the NK82xx folder and select the I2C node. 2. Add the required modules, you can insert as many as: − Two input modules DF8040 (see Fig. 52-A) − One output module DF8020 (see Fig. 52-B) − One power supervision module DF8090 (see Fig. 52-C) Fig.
Configuring networks and network components 3.3.4 NK82xx interactions Automatic functions The NK82xx configuration can include interactions, i.e. reaction programs that the NK82xx executes when a specific set of incoming signals (i.e. point states) is detected. When that occurs, one or more commands are generated according to the programmed interaction logic. The incoming signals are called trigger, whereas the outgoing commands are the effects.
Configuring networks and network components A Click this icon to add a new interaction program B Click this icon to add a new folder 5. Select the node of the new interaction and then the Node tab. Note the Interaction enabled checkbox (Fig. 55), which should be checked in order for the program to be downloaded. Fig. 55 Enabling Single Interaction Note also the Validate interactions checkbox (Fig. 59 at p.
Configuring networks and network components 7. Select the node of the new interaction and then the Interaction editor tab. In the page that appears, you can define the interaction logic filling in the following fields (Fig. 57): − Note: Text field for your comments. − Show. Checkboxes that can change the way trigger and effect names are shown. Namely: Customer text, Technical texts, NK82xx. − Interaction program.
Configuring networks and network components 8.B Enter the trigger list, you can select the following statements/conditions clicking on the left menu: – Comment: to enter a text line. – Field condition: to specify an input state. – OR/XOR: to enter a logic operator and combine two conditions. Note 1: The AND logic applies by default when more conditions are listed together. No explicit operator is required.
Configuring networks and network components 8.D Enter the Effect program, you can select the following statements/conditions clicking on the left menu: – Comment: To enter a text line – Send command: To specify a control action – Wait: To insert a programmable delay in the action list – Wait and re-check: To insert a programmable delay and then re-evaluate the trigger status before proceeding with the action list, e.g. to verify that the trigger status is stable.
Configuring networks and network components Fig. 58 Programming the Interaction 9. When triggers and effects are included, the interaction is ready. At this point, the text on the top should read: “The interaction is valid”. If this is not the case, move the mouse on the (yellow) line, read the tooltip, and follow the instructions about how to complete or fix the interaction program. 10 In the Node tab of the NK82xx node, do not forget to enable the checkbox Validate and download interactions (Fig. 59).
Configuring networks and network components 3.3.5 Downloading NK82xx The NK82xx configuration download allows loading the connectivity setting and the interaction configuration into the NK82xx unit. In case of multiple DMS systems, the NK82xx should be described in each DMS projects, but the download is required only once. Downloading procedure The NK82xx configuration download can be performed from either the NK82xx node or the NS8xxx driver node.
Configuring networks and network components Fig. 60 Testing LAN connection: successful ping check Fig. 61 Testing LAN connection: unsuccessful ping check Downloading NK82xx firmware updates (optional) Note: If you receive a new NK82xx firmware for an update, you need to add the new version before being able to select and download it to the NK82xx units. You do this with the Add button next to the Firmware Version list (see Fig. 63). 1. Check that NK82xx units respond to the ping message (see p.68) 2.
Configuring networks and network components Warning: Check again the "ping" connection of the NK82xx unit before proceeding with further downloads. It is essential to wait for the NK82xx to restart and respond to the ping messages. In fact, starting a new download (e.g. configuration download) before the NK82xx properly restarts may results in the NK82xx unit to crash and even lose its internal IP address. Should that occur, you will need to set the address again using the NW8202 tool.
Configuring networks and network components To download the configuration data, do the following: 1. Check that NK82xx units respond to the ping message (see p.68). 2. Open the Channel collection in DMS. 3. Select the NS8210 or NS8011 driver node and then the Download tab. Fig. 63 Downloading NK82xx configuration and firmware 4. Select one or more branches (NK82xx) in the list in the upper part of the form. See Fig. 63.
Configuring networks and network components Fig. 64 Controlling and checking NK82xx In case of insufficient RAM for allocating the protocol software related to the selected subsystems, some of the protocols may not be downloaded. 72 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring networks and network components 3.4 Configuring BACnet BACnet is a building automation and control networking protocol designed to meet the communication needs of building automation and control systems. After specific enhancements, BACnet can also fully support safety and security applications. DMS8000 uses BACnet in combination with IP networks (typically Ethernet). That solution is called BACnet/IP. 3.4.
Configuring networks and network components Fig. 66 BACnet Tab showing the Device Identifier Multiple IP subnets BBMD routers A BACnet/IP network comprising multiple IP subnets require IP routing services – provided by standard IP equipment– and additional BACnet routing services by a BBMD device (BACnet Broadcast Management Device). BBMD devices handle the BACnet broadcast messages across multiple IP subnets.
Configuring networks and network components 3.4.3 BACnet security BACnet is a public protocol and no encryption is currently supported by management stations and control units. Therefore, network spying and even hacking cannot be excluded, especially when using customer networks in large, campus-wide solutions. This threat requires a serious evaluation when planning for a BACnet network for danger management, and appropriate security measures should be taken into careful account.
Configuring networks and network components 3.5 Serial to network adapters Serial to network adapters (e.g. Lantronix UDS1100) allow for the LAN connection to DMS8000 systems, converting the serial line traffic into network packets and vice versa. On the DMS8000 station, network communication functions are required to acquire the messages. In some cases (Intrunet SI410, see 5.3.3 at p.181), DMS8000 software can directly handle this acquisition.
Configuring networks and network components Fig. 67 UDS1100 Device Installer Once the IP address is set, you can access the UDS1100 unit using a web browser: just type in the IP address. The resulting page provides access to further pages for configuring (UDS Setting: please see serial and network settings) and installing the device. 3.5.1.1 Serial port redirection at DMS8000 server level When the serial connection is “tunnelled” over a network link.
Configuring networks and network components Fig. 68 LANTRONIX Redirector: Configuration As the first step, click the Com Setup button and select the COM port(s) that you want to use (e.g. COM5). Close the window with OK. Fig. 69 LANTRONIX Redirector: COM ports setup Then, click Advanced and: − Set the TCP keep alive time to 30000 ms − Check the Run as a service box − Confirm with OK To correctly run the Lantronix Redirector in service mode, it is necessary to manually remove a registry value.
Configuring networks and network components Fig. 71 LANTRONIX Redirector: Service setup As final step, click Port Settings and configure the parameters shown in Fig. 72: Fig. 72 LANTRONIX Redirector: Port settings Confirm with OK, then Save, and finally Close the configuration. At this point, a reboot may be required. The new (virtual) COM port is now available as shown in the Windows hardware / Device manager list (see example below).
Configuring networks and network components 3.6 Adjusting network settings Once you have connected the network subsystems to the network drivers, you can adjust the network parameters. The type of network determines which setting you can adjust. They include: • Physical layer settings: Port, Baud Rate, Character Bits (Cerloop, CDI-Net, Intrunet).
Configuring networks and network components Fig. 77 Adjusting NK8000 network settings Communication parameters • Serial Port and Baud Rate settings should match the physical connection and settings on the connected hardware. • The flow control parameters do not usually need any adjustment. They are available for the special cases where the status request issued by the DMS towards the control units may create peaks of incoming traffic unsustainable for the network.
Configuring control units – Fire 4 Configuring control units – Fire This section describes how to configure the fire control unit subsystems. The list includes: − FS20/FS720 − CS11 AlgoRex − FC700A − CS1115 − SIGMASYS/D100 − CZ10 − STT11, STT20, STT2410 4.1 Configuring an FS20/FS720 FS20 and FS720 systems The FS20 and FS720 are comprehensive and versatile fire detection and extinguishing systems.
Configuring control units – Fire • FC20xx/FC72x stations interconnected via SAFEDLINK: DMS8000 systems connect to the CAP station that, in turn, connects to other stations on the redundant SAFEDLINK loop. Ethern FC20 CAP StaSAFEDLIN Fig. 80 FS20/FS720 SAFEDLINK architecture • FC20xx/FC72x stations interconnected via Ethernet and SAFEDLINK (mixed solution). Ethern CAP StaSAFEDLIN Fig.
Configuring control units – Fire 4.1.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The number and structure of FS20/FS720 systems. IP and BACnet network addressing of FC20xx/FC72x stations. The SiBX file(s) exported by the FS20/FS720 configuration tool and describing the entire system(s).
Configuring control units – Fire 4.1.2 Configuration procedures Adding NS8011 Network Driver 1. In the Composer project, select the Channel collection in: MM8000 (or MK8000) System Æ Physical configuration Æ Station (or FEP) Æ Channel collection 2. In the command bar on the left, click the NS8011 BACnet Driver. A new node is added to the project structure. Configuring the Driver BACnet parameters 1. Select the new NS8011 BACnet Driver node. 2. Select the Node tab 3.
Configuring control units – Fire 5. Configure the Transaction State Machine parameters. These parameters, and specifically all ADPU timeouts, should match the corresponding ones in the FS20/FS720 local configuration. The following parameters can be customised: − Maximum message latency time − ADPU timeouts − ADPU segment timeouts − Number of ADPU retries Fig. 82 Setting the Driver BACnet parameters Adding the folder for the FS20/FS720 system • Create a folder for the FS20/FS720 components.
Configuring control units – Fire Fig. 83 Adding a new FS20/FS720 node Importing the FS20/FS720 configuration metafile (SiBX) 1. Select the FS20 node. 2. Select Tools Æ Import in the Composer menu to start importing. After a confirmation request, the software presents a browsing window to search for the file to import (a SiBX file with extension XML is expected). 3. Using standard Windows controls, do the following: − Locate the XML file. − Select it and click Open.
Configuring control units – Fire Checking imported BACnet parameters Beyond the node structures of the stations, the import procedure acquires the BACnet parameters set in the fire system. This information shows in the Node tab of the FS20/FS720 System (Fig. 85) and FC20xx/FS72x stations (Fig. 86). Fig. 85 Example of FS20 System BACnet settings In the FS20/FS720 System settings, the BACnet Client Configuration section shows the valid Client Identifiers.
Configuring control units – Fire Fig. 87 Linking a station to NS8011 Network Driver Tip: If several stations have to be linked to the network driver, you can profit of the Composer grid mode and link all stations in one shot.
Configuring control units – Fire Fig. 88 Setting individual/general Ack/Reset Warnings: – Note that moving objects in FS20/FS720 tool may result in inconsistent results as objects in DMS8000 are first deleted and then added again as new items during the subsequent import (same issue as in CS11 AlgoRex). – The time zone setting must be the same in FS20/FS720 systems and DMS8000 in order to get a consistent time display.
Configuring control units – Fire 4.2 Configuring a CS11 General architecture The CS11 AlgoRex is a fire-detection and extinguishing system, which is physically made up of: − CC11 control unit(s) with separated control panels (CT11) − CK11 gateway(s) − CI11 control unit(s), an integrated model that includes the CT11 control panel All of these units are connected over a local bus (C-Bus). The CC11 units handle the actual fire detection and the appropriate alarming outputs.
Configuring control units – Fire 4.2.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The number, version (EP5 or EP7), and model (Data Base Variant) of CS11 systems. The number of CC11 units and CK11 gateways for each CS11. The local address (address 110, 111, 112, etc.) for each unit and gateway.
Configuring control units – Fire CONFIGURING A CS11 1. Add the folder(s) required for identifying the location of the CS11 in the project structure tree p. 94 2. Add the CS11 EP5 or CS11 EP7 node to the new folder p. 94 3. Set the CC11 Local Address and Vitality Timer p. 95 4. Set the CC11 metafile p. 96 5. Import the CC11 metafile p. 96 6. Repeat steps 3 through 5 for the remaining CC11s 7. Add the CK11 node to the CS11 system node p. 98 8. Set the CK11 Local Address and Vitality Timer p.
Configuring control units – Fire 4.2.2 Configuration procedures The following are the configuration procedures for the CS11 system: Adding the folder for the CS11 system 1. Open the Composer project. 2. Create a folder for the Fire / AlgoRex components. Adding the CS11 system node 1. Select the new folder. 2. In the left-hand bar, select the Fire folder icon 3. In the menu that appears, select one of the CS11 system icons to add a CS11 node: CS11 EP5 (see Fig. 89-A) or CS11 EP7 (see Fig. 89-B).
Configuring control units – Fire Adding the CC11 node to the CS11 system node 1. Select the CS11 node. 2. Select one of the CC11 icons: (CC11 EP5) or (CK11 EP5) or (CK11 EP7) or (CC11 EP7) to add a CC11 node in the CS11 (see Fig. 91 and Fig. 92 for EP5 and EP7, respectively). A new node is added to the project structure. Fig. 91 Selecting the icon to add a CC11 control unit in a CS11 EP5 A Click this icon to add a CC11 EP5 B Click this icon to add a CK11 gateway Fig.
Configuring control units – Fire − The Vitality Timer is related to the frequency of the heartbeat message periodically transmitted by the control unit. This value is the maximum tolerated delay in seconds, and should be 3 to 6 times as long as the heartbeat message. For example, if the heartbeat message is 30 seconds, you set the Vitality Timer to 90 to 180 seconds.
Configuring control units – Fire Fig. 94 Starting CC11 import After a confirmation request, the software presents a browsing window to search for the file to import (a metafile with extension TXT is expected). 3. Using standard Windows controls, do the following: − Locate the file − Select it and click Open (see Fig. 95) Fig. 95 Selecting the metafile to import In a few moments, the CC11 structure is imported, and the node is represented in the Composer tree.
Configuring control units – Fire Fig. 96 Manual matching of CC11 objects Adding the CK11 interface node to the CS11 system node After adding all the CC11s, you need to add the CK11 interface node to the CS11 system node. Perform the following steps: 1. Select the CS11 node. 2. Select one of the CK11 icons: (CK11 EP5) or (CK11 EP7) to add the CK11 interface node (see Fig. 91 and Fig. 92 for EP5 and EP7, respectively). A new node is added to the project structure.
Configuring control units – Fire 2. Select ToolsÆImport in the Composer menu to start CK11 import (see Fig. 94). Connecting a CS11 directly to the DMS8000 With DMS8000 it is possible to connect a CS11 (whose CK11 is set for ISO1745 communication) directly to the DMS8000 server instead of through a network. After you have set the vitality, do the following: 1. Drag the CK11 to the DMS8000 Cerloop Driver for each CS11. 2. In the link node that appears, set the communication parameters (see 3.6 at p.80).
Configuring control units – Fire Fig. 98 Linking CK11 to a NK8000 network (NK8223, COM3) When the link is established, a new node appears on the structure tree, and its properties can be seen on the Link tab of both connected nodes (see Fig. 99). Fig. 99 New link to a CK11 in the GW21 line 100 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring control units – Fire 4.3 Configuring a CS1115 The CS1115-x and CS1115-ECO are fire detection systems. Both subsystems support a number of basic features in a pre-assembled unit and additional options. The list includes: − One (CS1115-ECO) or two (CS1115-x) Loops or Collective Lines. − 2, 4, and 16 Loops/Lines extensions are available for CS1115-x. − Four inputs (16 I/O contacts may be optionally added). − Remote transmission outputs and power supply unit.
Configuring control units – Fire CONFIGURING A CS1115 1. Add the folder(s) required for identifying the location of the CS1115 in the project structure tree p. 103 2. Add the CS1115 system node to the new folder p. 103 3. Import the internal configuration p. 104 – OR – enter the fire system configuration, including Physical and Logical structure: - CS1115-x ............................................................................................... p. 104 - CS1115-ECO .................................
Configuring control units – Fire 4.3.2 Configuration procedures – CS1115 systems The following are the configuration procedures for the CS1115 subsystems: Adding the folder for the CS1115 systems 1. Select the new folder. 2. In the left-hand bar, select the folder icon to create a folder for the fire protection components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab (for example, “Fire”). Adding the CS1115 system node 1.
Configuring control units – Fire Importing the CS1115 metafile 1. Select the CS1115 node. 2. Select ToolsÆImport in the Composer menu to start the import procedure. After a confirmation request, the software presents a browsing window to search for the file to import (a metafile with extension C15 is expected). 3.
Configuring control units – Fire - or select the Collective Line icon once to add a collective line node, once to add a loop node. and the Loop icon 4. Select the K3L110 icon (“G”) to add a K3L110 node. Adding this node inserts 16 input nodes. 5. Select the K3M030 icon (“D”) to add a K3M030 node. 6. Choose, based on customer requirements, either the K3M010 or K3M020 (“F”) icon (“E”) to add the respective node. 7.
Configuring control units – Fire Fig. 104 CS1115-x Logical tree icons A B CS1115-x logical tree component icons: Control Zone Fire Zone 2. Select the Fire Zone icon (“B”) and add up to 512 fire zone nodes by continuing to select the icon (keep the SHIFT key pressed when clicking to invoke the multiple insert feature). 3.
Configuring control units – Fire 4. Drag and drop the appropriate collective line nodes to all the appropriate fire zone nodes located in the logical tree. Composer helps you in recognising a valid link by showing a shortcut Link icon instead of the circle No-link icon . When the link is established, a new node appears on the structure tree, and its properties can be seen on the Link tab of both connected nodes Fig. 106 Valid Collective Line links: drag Collective Lines to Fire Zones 4.3.
Configuring control units – Fire Fig. 107 CS1115-ECO Physical Tree icons A B C D CS1115-ECO physical tree component icons: Input Loop Collective Line K3L110 2. Select the Input icon (“A”) to add up to 4 Input nodes. 3. Do one of the following, based on configuration requirements: − Select the Loop icon - or - (“B”) to add a loop node select the Collective Line icon 4. Select the K3L110 icon (“C”) to add a collective line node (“D”) to add a K3L110 node. Adding this node inserts 16 input nodes.
Configuring control units – Fire Fig. 109 CS1115-ECO Logical tree icons A B CS1115-ECO logical tree component icons: Control Zone Fire Zone 2. Select the Fire Zone icon (“B”) and add up to 128 fire zone nodes by continuing to select the icon (keep the SHIFT key pressed when clicking to invoke the multiple insert feature). 3.
Configuring control units – Fire Connecting collective lines to fire zones • Expand the Physical Tree. If this node contains a collective line node, select it, and drag and drop to all the appropriate fire zone nodes located in the logical tree. Note: You cannot link collective lines to fire zone nodes containing detector nodes. Composer helps you in recognising a valid link by showing a shortcut Link icon instead of the circle No-link icon .
Configuring control units – Fire 3. Select the Serial Port in the Node tab of the link node (Fig. 113). Fig. 113 Selecting the Serial Port for CS1115 communication 111 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring control units – Fire 4.4 Configuring an FC700A The FC700A is a fire detection system that is physically made up of: − FC700A control unit(s) − FG700A gateway(s) The FC units handle the actual fire detection and the appropriate alarming outputs. Instead, the FG provides the serial connectivity to a larger system. The physical components are hosted in cabinets equipped with adequate power supply and connectivity to the required external devices.
Configuring control units – Fire DMS8000 connection MM8000 station LAN RS232 E3H02x FC700A 4.4.2 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The number of FC700A systems. The number of FC units and FG gateways for each system. The local address (address 110, 111, 112, etc.) for each unit and gateway.
Configuring control units – Fire CONFIGURING AN FC700A 1. Add the folder(s) required for identifying the location of the FC700A in the project structure tree p. 114 2. Add the FC700A system node to the new folder p. 114 3. Add the FC700A unit node to the system node p. 115 4. Set the FC700A unit Local Address and Vitality Timer p. 115 5. Import the FC700A unit metafile p. 116 6. Repeat steps 3 through 5 for the remaining units of the system. 7. Add the FG700A node to the system node p. 117 8.
Configuring control units – Fire Fig. 114 Selecting the icon to add a FC700A system A Click this icon to add a FC700A system Adding the FC700A control unit to the system node 1. Select the FC700A system node. 2. Select the FG700A (see Fig. 115-A) or the FC700A (see Fig. 115-B) control unit icon to add a FC700A control unit. A new node is added to the project structure. Fig.
Configuring control units – Fire − The Vitality Timer is related to the frequency of the heartbeat message periodically transmitted by the control unit. This value is the maximum tolerated delay in seconds, and should be 3 to 6 times as long as the heartbeat message. For example, if the heartbeat message is 30 seconds, you set the Vitality Timer to 90 to 180 seconds.
Configuring control units – Fire 3. Using standard Windows controls, do the following: − Locate the file − Select it and click Open (see Fig. 118) Fig. 118 Selecting the metafile to import In a few moments, the FC700A structure is imported, and the node is represented in the Composer tree. Some FC700A objects that have been renumbered in the local configuration tool may need to be manually re-assigned to the existing Composer nodes during the subsequent import.
Configuring control units – Fire The value to set in the Vitality Timer depends on the type of network. The following rule applies: – In Cerloop network, the MK7022 already handles the vitality check, and the DMS host does not receive the heartbeat messages. In this case, set the timer value =0. – In NK8000 and CDI-Net networks, if the connection also includes the MK7022 Cerloop interface, leave the value =0.
Configuring control units – Fire Fig. 120 Linking FG700A to the DMS8000 station (direct link) Fig. 121 Linking FG700A to a NK8000 network (NK8223, COM1) When the link is established, a new node appears on the structure tree, and its properties can be seen on the Link tab of both connected nodes (see Fig. 122). Fig. 122 New link to FG700A in the NK8000 network 119 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring control units – Fire 4.5 Configuring an FC330A The FC330A-x and FC330A-ECO are fire detection systems. Both subsystems support a number of basic features in a pre-assembled unit and additional options. The list includes: − One (FC330A-ECO) or two (FC330A-x) Loops / Collective Lines. − 2, 4, and 16 Loops/Lines extensions are available for FC330A-x.
Configuring control units – Fire CONFIGURING AN FC330A 1. Add the folder(s) required for identifying the location of the FC330A in the project structure tree p. 122 2. Add the FC330A system node to the new folder p. 122 3. Import the internal configuration p. 123 – OR -enter the fire system configuration, including Physical and Logical structure: - FC330A-x .................................................................................................. p. 123 - FC330A-ECO ..............................
Configuring control units – Fire 4.5.2 Configuration procedures – FC330A systems The following are the initial configuration procedures for both of the FC330A subsystems: Adding the folder for the FC330A systems 1. Select the Field node. 2. Select the folder icon to create a folder for the fire protection components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab (for example, “Fire”). Adding the FC330A system node 1.
Configuring control units – Fire Importing the FC330A metafile 1. Select the FC330A node. 2. Select ToolsÆImport in the Composer menu to start the import procedure. After a confirmation request, the software presents a browsing window to search for the file to import (a metafile with extension C15 is expected). 3.
Configuring control units – Fire select the Loop icon - or - (“B”) twice to add 2 Loop nodes select the Collective Line icon once to add a collective line node, once to add a loop node. and the Loop icon 4. Select the K3L110 icon (“G”) to add a K3L110 node. Adding this node inserts 16 input nodes. 5. Select the K3M030 icon (“D”) to add a K3M030 node. 6. Choose, based on customer requirements, either the K3M010 or K3M020 (“F”) icon (“E”) to add the respective node. 7.
Configuring control units – Fire Configuring the logical tree 1. Expand the FC330A-x node and select the Logical Tree node. Fig. 127 FC330A-x Logical tree icons A B FC330A-x logical tree component icons: Control Zone Fire Zone 2. Select the Fire Zone icon (“B”) and add up to 512 fire zone nodes by clicking the icon again (keep the SHIFT key pressed when clicking to invoke the multiple insert feature). 3.
Configuring control units – Fire 2. Expand the K3M030 subtree in the Physical Tree if this node contains any collective line nodes, select the appropriate Collective Line node, and drag and drop them to the appropriate fire zone nodes located in the logical tree. 3. Expand either the K3M010 or the K3M020 node 4. Drag and drop the appropriate Collective Line nodes to all the appropriate Fire zone nodes located in the Logical Tree.
Configuring control units – Fire 4.5.4 Configuration procedures – FC330A-ECO The following are the configuration procedures for the FC330A-ECO subsystem, which are similar to those for the FC330A-x but with fewer components: Configuring the physical tree 1. Expand the FC330A-ECO node and select the Physical Tree node. Fig. 130 FC330A-ECO Physical Tree icons A B C D FC330A-ECO physical tree component icons: Input Loop Collective Line K3L110 2. Select the Input icon (“A”) to add up to 4 Input nodes.
Configuring control units – Fire Fig. 131 FC330A-ECO Physical Tree configuration example Configuring the logical tree 1. Expand the FC330A-ECO node and select the Logical Tree node. Fig. 132 FC330A-ECO Logical tree icons A B FC330A-ECO logical tree component icons: Control Zone Fire Zone 2. Select the Fire Zone icon (“B”) and add up to 128 fire zone nodes by continuing to select the icon (keep the SHIFT key pressed when clicking to invoke the multiple insert feature). 3.
Configuring control units – Fire Connecting collective lines to fire zones • Expand the Physical Tree. If this node contains a collective line node, select it, and drag and drop to all the appropriate fire zone nodes located in the logical tree. Note: You cannot link collective lines to fire zone nodes containing detector nodes. Composer helps you in recognising a valid link by showing a shortcut Link icon instead of the circle No-link icon . Fig.
Configuring control units – Fire 4.5.5 Linking an FC330A system to the DMS 1. Expand the Management Station folder until you reach the NS8015 driver: Æ Physical Configuration Æ Æ Channels Collection Æ NS8015 Fire CNDL 2. Drag the CS1115-ECO node to the NS8015 Fire CNDL node (see Fig. 135). Fig. 135 Linking CS1115 to the DMS system When the link is established, a new node appears on the structure tree, and its properties can be seen on the Node tab. 3.
Configuring control units – Fire 4.5.6 FC330 configuration tips Configuring the communication port in FC330A In FC330A, in order to enable the communication protocol on the serial port, you need to configure the unit at control panel level (please also refer to FC330A Manual n.1583). Follow this procedure: 1. Press “Start” and login for operating access (password required) 2. Select option 4 (“Other Functions”) 3. Select option 4 (“Configuration”) 4.
Configuring control units – Fire 4.5.7 FC330 facts and limitations • FC330A and CS1115 cannot be connected via NK8000 • Automatic zones, manual zones, sprinkler zones etc.
Configuring control units – Fire 4.6 Configuring XLS The XLS FireFinder is a fire detection and extinguishing control unit approved by FM and ULC. It can handle detection lines supporting addressable points and communicate with peer units over an RS-485 network (XNET). XLS units can communicate to an external system over an RS232 connection (RPM interface) using the FSI protocol.
Configuring control units – Fire 4.6.3 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The number of XNETs in the system. The XNET configuration file(s) generated by the Zeus tool (XML files). The exact connection to NK8000 (NK82xx unit and line). Composer plug-ins needed: – Plug-in #356501. This is installed during the software setup procedure.
Configuring control units – Fire Adding the XNET node 1. Select the new folder. 2. In the left-hand bar, select the Fire folder icon . 3. In the menu that appears, click the XNET icon . or, alternatively, select the menu item: Insert Æ Fire Æ XNET A new node is added to the project structure. Note: By default, the new node is named “XNET #1”. You can customise it in the Description field of the Node tab. Importing the XML configuration file 1. Select the XNET node. 2.
Configuring control units – Fire (a global acknowledgement applies to each of the event categories: Alarm, Supervision, Security, and Trouble). 1. In the imported XNET structure, select the first XLS node. In the Node tab, the Panel Properties include the Allow Control for Automatic Acknowledges option. 2. Enable the Allow Control for Automatic Acknowledges option to match the individual event acknowledge setting in the XLS tool (see 4.6.2.1 at p.133).
Configuring control units – Fire 4.7 Configuring SIGMASYS/D100 The SIGMASYS/D100 is a family of fire systems that includes: − SIGMASYS fire control units − D100 fire system These systems can communicate with a head-end host using the VBF (Virtuelle BedienFeld Schnittstelle) protocol. The NK82xx network units can communicate over serial lines using the VBF protocol and convert the application messages appropriately.
Configuring control units – Fire CONFIGURING A SIGMASYS/D100 1. Add the folder(s) required for identifying the location of the SIGMASYS/D100 in the project structure tree p. 138 2. Add the SIGMASYS/D100 control unit node to the new folder p. 138 3. In the PLAN D100 tool, create the configuration files p. 139 4. Import the configuration file p. 139 5. Link the SIGMASYS/D100 to the communication network p. 140 6. Repeat steps above for all the SIGMASYS/D100 units in the project. 4.7.
Configuring control units – Fire Fig. 137 Adding a SIGMASYS/D100 subsystem The unit just added should be the one that can communicate with DMS8000 via NK82xx (master node). In case of complex architectures including multiple units, other SIGMASYS/D100 can be added below the master node in order to represent e.g. an SM88 system (just select the master node and insert the other units).
Configuring control units – Fire − In the folder, locate the XML file (note that the required EXP file is automatically found and processed). − Select the file and click Open. The Panels List window shows the panels included in the export file. Fig. 138 SIGMASYS/D100 panels to import − Select one the panel and click OK. In a few moments, the SIGMASYS/D100 internal structure is imported.
Configuring control units – Fire Fig. 139 Link SIGMASYS/D100 to the NK8000 network When the link is established, a new node appears on the structure tree, and its properties can be seen on the Node tab. 141 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring control units – Fire 4.8 Configuring a CZ10 The CZ10 is a danger detection control unit handling the risk sectors Fire, Extinguishing, Gas and Building Services. The basic control unit (master) permits the connection of 24 collective, or 24 individually addressable signal lines. Physically, the CZ10 is composed of a central module, hosted in a cabinet, and connected to signal lines and alarming devices. Authorised operators can operate the system locally on a CT10 terminal.
Configuring control units – Fire 4.8.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The CZ10 parameter settings, which can be provided in three ways: – The DMS7000 metafile to import – The LMSmodular databases DB_PUL.DBF and DB_SUB.
Configuring control units – Fire 4.8.2 Configuration procedures The following are the configuration procedures for the CZ10 system: Adding the folder for the CZ10 system 1. Open the Composer project. 2. Create a folder for the Fire / CZ10 components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab (for example, “Fire”). Adding the CZ10 system node 1. Select the new folder. 2. In the left-hand bar, select the Fire folder icon 3.
Configuring control units – Fire The value to set in the Vitality Timer depends on the type of network. The following rule applies: – In Cerloop network, the MK7022 already handles the vitality check, and the DMS host does not receive the heartbeat messages. In this case, set the timer value = 0. – In NK8000 and CDI-Net networks, if the connection also includes the MK7022 Cerloop interface, leave the value = 0.
Configuring control units – Fire In a few moments, the CZ10 structure is imported, and the node is represented in the Composer tree. Defining the CZ10 physical configuration If you were not able to import the configuration, you will need to configure the CZ10 by hand to reflect the actual hardware configuration.
Configuring control units – Fire 3. Drag and drop the CZ10 node to the network node (see Fig. 143 and Fig. 144). Note: The valid link position for Cerloop is always the same main node, representing the entire loop. The valid link positions on CDI-Net/NK8000 gateways are distributed along the subsystem lines. Composer helps you in recognising a valid link by showing a shortcut Link icon instead of the circle No-link icon . Fig. 143 Linking CZ10 to a Cerloop network Fig.
Configuring control units – Fire 4.9 Configuring an STT11 STT11 system is designed to perform automatic actions (called “fire actuations”) following the detection of a fire alarm by a CS11 AlgoRex unit. It operates with a CS11 in a common Cerloop network. STT11 is made up of a physical and logical tree.
Configuring control units – Fire CONFIGURING AN STT11 1. Add the folder(s) required for identifying the location of the STT11 in the project structure tree p. 149 2. Add the STT11 system node to the new folder p. 149 3. Add the STT11 CPU node to the new folder p. 150 4.Set the STT11 Local Address and Vitality Timer p. 150 5. Import the STT11 metafile p. 151 6 Repeat steps 3 to 5 for the remaining STT11 CPU (max. 2) 7. Add the SK11 node to the STT11 system p. 151 8. Set the SK11 local address p.
Configuring control units – Fire Fig. 145 Selecting the icon to add an STT11 subsystem Adding the STT11 CPU node 1. Select the STT11 System node. 2. Select the STT11 CPU icon to add a CPU unit to the STT11 system (see Fig. 146). A new node is added to the project structure. Fig. 146 Selecting the icon to add an STT11 CPU Setting the STT11 CPU Local Address and the Vitality Timer 1. Select the STT11 CPU node. 2. In the Node tab, set the Local Address and the Vitality Timer (see Fig. 147).
Configuring control units – Fire The value to set in the Vitality Timer depends on the type of network. The following rule applies: – In Cerloop network, the MK7022 already handles the vitality check, and the DMS host does not receive the heartbeat messages. In this case, set the timer value = 0. – In NK8000 and CDI-Net networks, if the connection also includes the MK7022 Cerloop interface, leave the value = 0.
Configuring control units – Fire Fig. 148 Selecting the icon to add the SK11 node 3. Select the new SK11 node. 4. Set the Local Address and Vitality Timer (see page 150). Linking the SK11 to the Communication network It is now necessary to include the STT11 system in the communication network. You do this by linking the SK11 to the network node it belongs to. Proceed as follows: 1. Expand the network folders until you reach the node that represents the Cerloop network physically connected to the SK11. 2.
Configuring control units – Fire 4.10 Configuring an STT20 STT20 system is designed to perform automatic actions (called “fire actuations”) following the detection of a fire alarm by a CS11 AlgoRex unit. It operates with a CS11 in a common Cerloop network. STT20 is made up of a physical and logical tree. The fire system is logically organised in a 4-level structure (Area, Sections, Functions, and Elements) like the STT11 unit.
Configuring control units – Fire 4.10.2 Configuration procedures The following are the configuration procedures for the STT20: Adding the folder for the STT20 system 1. Open the Composer project. 2. Create a folder for the STT20 components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab. Adding the STT20 system node 1. Select the new folder. 2. In the left-hand bar, select the Fire folder icon 3.
Configuring control units – Fire The value to set in the Vitality Timer depends on the type of network. The following rule applies: – In Cerloop network, the MK7022 already handles the vitality check, and the DMS host does not receive the heartbeat messages. In this case, set the timer value = 0. – In NK8000 and CDI-Net networks, if the connection also includes the MK7022 Cerloop interface, leave the value = 0.
Configuring control units – Fire Composer helps you in recognising a valid link by showing a shortcut Link icon instead of the circle No-link icon . Fig. 152 Connecting the STT20 node to the Cerloop network When the link is established, a new node appears on the structure tree, and its properties can be seen on the Node tab. 156 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring control units – Fire 4.11 Configuring an STT2410 STT2410 system is designed to perform automatic actions (called “fire actuations”) following the detection of a fire alarm by Fire detection unit. In the Composer configuration, the only supported architecture is the Cerloop network. The physical and logical configuration for an STT2410 is first defined for the hardware unit set-up.
Configuring control units – Fire 4.11.2 Configuration procedures The following are the configuration procedures for the STT2410: Adding the folder for the STT2410 system 1. Open the Composer project. 2. Create a folder for the STT2410 components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab. Adding the STT2410 system node 1. Select the new folder. 2. In the left-hand bar, select the Fire folder icon 3.
Configuring control units – Fire Fig. 154 Setting STT2410 Local Address Configuring the STT2410 internal structure 1. Select the STT2410 node. The default structure includes the following nodes: Fig. 155 Default STT2410 structure 2. Select the Controls node The Line command becomes available in the toolbar. Fig. 156 STT2410 ‘Line’ command icon 3. Click the Line icon to add a line Repeat as many times as required by the STT2410 configuration. 4.
Configuring control units – Fire Fig. 157 STT2410 Input/Output command icon 5. Click the Input/Output command icon to add an I/O signal Repeat as many times as required by the STT2410 configuration. Linking the STT2410 to the Communication network It is now necessary to include the STT2410 system in the communication network. You do this by linking the STT2410 node to the network node it belongs to. Proceed as follows: 1.
Configuring control units – Intrusion 5 Configuring control units – Intrusion This section describes how to configure the intrusion control unit subsystems. The list includes: − SI410 Intrunet − SPC6000 − CS6 Guarto − CS4 − CS440 − CZ12 161 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring control units – Intrusion 5.1 Configuring an SI410 Intrunet The SI410 Intrunet is an intrusion detection unit with individual addressing and access control capability. It can handle detection lines on which transponder units can concentrates alarm inputs and outputs. Inputs can be operated in groups, organised in Rooms, Wards, and Clusters.
Configuring control units – Intrusion cess to the LAN (Ethernet 10-Base-T) for DMS8000. NK82xx can also handle local interactions between the connected subsystems. The service PC running the SI410 SYLCOM tool can connect via another serial port or over a LAN link. Note that the LAN connection for the tool requires the SMN36/42/43 module (see 3.5 at p.76).
Configuring control units – Intrusion 5.1.3 SI410 connectivity: technical notes 5.1.3.1 SI410 Intrunet: internal options and settings Serial ports The SI410 Intrunet can provide serial connectivity to host computers on the port J1, J7 and J10 (please refer to SI410 documentation). Port J7 is used for connecting to the Sylcom PC, whereas J1 or J10 is used for DMS8000. In the connection solutions to DMS8000, the J10 port is used when the Sylcom tool is connected to J7.
Configuring control units – Intrusion • Sintony IP Port 2: IP Port number (contact network administration) used by the DMS8000 driver NS8014 to communicate over Ethernet. This is the TCP port number that should be configured in Composer (see Fig. 167 at p.172). Note that the Sintony IP port field is used for the Sylcom network link only. Fig.
Configuring control units – Intrusion ITEMS NEEDED FOR CONFIGURATION If the LAN connectivity is used, the IP address and TCP port of the LAN communication. Plug-ins needed: – Plug-in #352001. This is installed during the software setup procedure. You can check that the Plug-in is actually available using the Composer Plug-in Installer in the DMS8000 start menu. CONFIGURING AN SI410 INTRUNET 1. Generate the SI410 metafile p. 166 2.
Configuring control units – Intrusion a) Direct Serial connection to the PC with the uploading software Configure the serial port in the unit to handle a host serial link on the J10 port (this link is used for both the NK82xx and the upload tool connection). Connect the SI410 port to any COM port of the PC where the Sintony Uploader is available. Use the SAQ18 cable (refer to the SI410 Intrunet documentation) and a crossed serial cable with two DB9/f connectors.
Configuring control units – Intrusion Fig. 160 Sintony Uploader: selecting the connection type Fig. 161 Sintony Uploader: Auto-detecting the COM port 4. At this point, press Next and let the Read Data page show up. 5. Then press the Start button. The software starts communicating with the SI410 and acquiring the configuration data over the serial line. An item list and a progress bar show the activities and the uploading results (see Fig. 162). Fig.
Configuring control units – Intrusion Note: In case of errors, check the SI410 firmware release (compare with latest requirements in the DMS8000 product Release Notes). 6. When the upload process has completed, a success message appears. Click OK to acknowledge it. 7. Save the uploaded data. You have now to select the file name and destination folder of the metafile. Use the browsing button to open the navigation windows (see Fig. 163). Fig. 163 Sintony Uploader: Saving the configuration 8.
Configuring control units – Intrusion Fig. 164 Selecting the SI410 icon (A) to add a new SI410 subsystem Importing the SI410 metafile 1. Select the SI410 node. 2. Select Tools→Import in the Composer menu to start SI410 import. After a confirmation request, the software presents a browsing window to search for the file to import (the INI file is expected, see 5.1.5 at p.166). 3. Select the import file from the file selection window and click Open.
Configuring control units – Intrusion Fig. 165 Linking SI410 to NK82xx Linking the SI410 to the Communication network (MM8000/MK8000) To link the SI410 node to the MM8000/MK8000, do the following: 1. Expand the system station folders (Stand-alone or FEP) until you reach the node that represents the NS8014 driver. 2. Select the NS8014 SI410 Driver node. Note: if this driver is not present, you can add it to the Channels by clicking the corresponding icon on the left toolbar. 3.
Configuring control units – Intrusion Fig. 167 Setting the network communication options 172 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring control units – Intrusion 5.2 Configuring an SPC6000 The SPC6000 is an intrusion detection unit belonging to the SPC series. It can support both wired and wireless intrusion devices (true hybrid controller) and a LAN interface possibly integrated by additional communications modules (PSTN/GSM/RF). Intrusion inputs can be operated in groups, organised in Areas and Zones.
Configuring control units – Intrusion Generating the SPC export file • In File Æ Download, Browse and download the file When the web tool is connected to the SPC6000 unit in Full Engineer mode, then no alarm messages are transmitted to MM8000. 5.2.3 SPC6000 connectivity: technical notes 5.2.4 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows.
Configuring control units – Intrusion 5.2.5 Configuration procedures The following are the configuration procedures for SPC6000. Adding the NS8013 SPC driver 1. Open the Composer Project. 2. If not already done, add the SPC Driver (NS8013) in the path: Supervision System Setting Æ MM8000 System Æ Physical configuration Æ Station (e.g. My Station) Æ Channels collection 3. Click on the NS8013 driver icon in the icon toolbar. The new driver node appears in the station folder. 4.
Configuring control units – Intrusion Importing the SPC6000 metafile 1. Select the SPC6000 node. 2. Select Tools→Import in the Composer menu to start the SPC6000 import. After a confirmation request, the software presents a browsing window to search for the file to import. 3. Select the import file from the file selection window and click Open. In a few moments, the SPC6000 structure is imported, and the corresponding nodes are represented in the Composer tree.
Configuring control units – Intrusion 5.3 Configuring a CS6 Guarto The CS6 Guarto is an intrusion detection and access control system with individual addressing. It consists of the CC6 control unit and CT6 operating units. The ADI addressing elements transmit the detector signals to the control unit. The structure of the CS6 is similar to CS4. It is divided into logical system levels, and planning and parameterisation determines its allocation to software and hardware.
Configuring control units – Intrusion 5.3.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The number of CS6 in the system. The CS6 metafiles (CNAP profile files). The CerCom/LON addresses (Subnet, Node, Logical address) for each unit. The connection to the network on CerCom/LON. Note: The connection always requires an NK8000 unit equipped with Cercom/LON adapter.
Configuring control units – Intrusion 5.3.2 Configuration procedures The following are the configuration procedures for the CS6 system. Adding the folder for the CS6 system 1. Open the Composer project. 2. Create a folder for the Intrusion/CS6 components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab. Adding the CS6 system node 1. Select the new folder. 2. In the left-hand bar, select the Intrusion folder icon 3.
Configuring control units – Intrusion Selecting the Import tab results in a page report being displayed. This contains the detailed logs of the latest import procedure, including all the added or removed objects. Linking the CS6 to the Communication network To link the CS6 node to the NK82xx node, do the following: 1. Expand the network folders until you reach the node that represents the NK8000 network node physically connected to the CS6. 2. Select the CS6 node. 3.
Configuring control units – Intrusion Fig. 171 Setting CS6 addresses on CerCom/LON bus 5.3.3 Commissioning tips Commissioning procedure In order to properly set the BACnet logical address on the LON network, we recommend the following procedure: • Switch off power of CS6 control unit(s). • Connect CS6 unit(s) to NK82xx on the LON network. • Switch on power of CS6 control unit(s): after power-up, CS6 has no BACnet logical address. • Reset NK82xx.
Configuring control units – Intrusion 5.4 Configuring a CS4 The CS4 is an intrusion detection system with individual addressing. It consists of the CC4 control unit, and the CT4 operating units. The ADI addressing elements transmit the detector signals to the control unit. The structure of the CS4 is divided into logical system levels, and planning and parameterisation determines its allocation to software and hardware. The logical system levels include: • Area (max.
Configuring control units – Intrusion CONFIGURING A CS4 1. Add the folder(s) required for identifying the location of the CS4 in the project structure tree p. 183 2. Add the CS4 system node to the new folder p. 183 3. Set the CS4 Local Address, Vitality Timer, and Sub type......................... p. 184 4.Import the CS4 List file p. 184 5. Link the CS4 to the Communication device line, according to communication links p. 185 6. Repeat steps above for all the CS4s in the project. 5.4.
Configuring control units – Intrusion Fig. 172 Selecting the icon to add a CS4 subsystem Setting the CS4 Local Address, Vitality Timer and Sub type 1. Select the CS4 node. 2. In the Node tab, set the Local Address, Vitality Timer and Sub type. Please note that: − The address value should range from 111 to 248 according to the DMS7000 addressing scheme (last digit cannot be 0 or 9), and it should match what is set in the configuration of the CS4 unit.
Configuring control units – Intrusion Selecting the Import tab results in a page report being displayed. This contains the detailed logs of the latest import procedure, including all the added or removed objects. Linking the CS4 to the Communication network Link the CS4 node to the Cerloop, CDI-Net, or NK8000 network. 1. Expand the network folders until you reach the node that represents the network that is physically connected to the CS4. 2. Select the CS4 node. 3.
Configuring control units – Intrusion 5.5 Configuring a CS440 The CS440 is a large intrusion detection system with individual addressing. It consists of the CS440 control unit and the CT411 operating units. The ADI addressing elements transmit the detector signals to the control unit. The structure of the CS440 is divided into logical system levels, and planning and parameterisation determines its allocation to software and hardware. The logical system levels include: • Area (max.
Configuring control units – Intrusion 5.5.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The number of CS440s in the system. The local address (111, 112, etc.) for each unit. The metafile generated by the CS440 tool for each unit The connection to the DMS: Cerloop, CDI-Net, or NK8000. Note: The CDI-Net/NK8000 requires a serial line available on the gateway.
Configuring control units – Intrusion 5.5.2 Configuration procedures The following are the configuration procedures for the CS440 system: Adding the folder for the CS440 system 1. Open the Composer project. 2. Create a folder for the Intrusion/ CS440 components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab. Adding the CS440 system node 1. Select the new folder. 2. In the left-hand bar, select the Intrusion folder icon 3.
Configuring control units – Intrusion The value to set in the Vitality Timer depends on the type of network. The following rule applies: – In Cerloop network, the MK7022 already handles the vitality check, and the DMS host does not receive the heartbeat messages. In this case, set the timer value = 0. – In NK8000 and CDI-Net networks, if the connection also includes the MK7022 Cerloop interface, leave the value = 0.
Configuring control units – Intrusion Fig. 175 Linking CS440 to NK82xx (NK8223, COM3) When the link is established, a new node appears on the structure tree, and its properties can be seen on the Node tab. 190 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring control units – Intrusion 5.6 Configuring a CZ12 The CZ12, the predecessor of the CS4, is a control unit for intrusion detection. It was developed as part of the DMS7000 system. The CZ12 is physically composed of a central module, which is housed inside a cabinet, and connected to detection lines and alarming devices. The system can be operated locally on a CT12 terminal by a restricted number of authorised users.
Configuring control units – Intrusion 5.6.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The CZ12 parameter settings, which can be provided in three ways: – The DMS7000 metafile to import – The LMSmodular databases DB_PUL.DBF and DB_SUB.
Configuring control units – Intrusion 5.6.2 Configuration procedures The following are the configuration procedures for the Intrusion/CZ12 system: Adding the folder for the CZ12 system 1. Open the Composer project. 2. Create a folder for the Intrusion/ CZ12 components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab. Adding the CZ12 system node 1. Select the new folder. 2. In the left-hand bar, select the Intrusion folder icon 3.
Configuring control units – Intrusion The value to set in the Vitality Timer depends on the type of network. The following rule applies: – In Cerloop network, the MK7022 already handles the vitality check, and the DMS host does not receive the heartbeat messages. In this case, set the timer value =0. – In NK8000 and CDI-Net networks, if the connection also includes the MK7022 Cerloop interface, leave the value =0.
Configuring control units – Intrusion − Door monitoring zones − Users − Time programs Linking the zones to the sections Drag and drop the zones to the sections where they belong. Linking the CZ12 to the Communication network Link the CZ12 node to the Cerloop, CDI-Net, or NK8000: 1. Expand the network folders until you reach the node that represents the network physically connected to the CZ12 (Cerloop, CDI-Net, or NK8000). 2. Select the CZ12 node. 3. Drag and drop the CZ12 node to the network node (see Fig.
Configuring other control units 6 Configuring other control units This section describes how to configure various subsystems available from Building Technologies. The list includes: − CC60 Gas detection unit − DMS7000 units − CF9000 I/O subsystem − DESIGO PX system 6.1 Configuring a CC60 The CC60 is a gas detection unit. The system is logically organised in up to 56 zones and 56 elements, and collected in a general Gas Sector.
Configuring other control units 6.1.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The CC60 parameter settings, which can be provided in two ways: – The LMSmodular databases DB_PUL.DBF and DB_SUB.DBF to import – Complete information about the CC60 configuration: Output boards, VD60 Displays, Gas zones and elements, etc. The local address (111, 112, etc.).
Configuring other control units 6.1.2 Configuration procedures The following are the configuration procedures for the CC60 system: Adding the folder for the CC60 system 1. Open the Composer project. 2. Create a folder for the CC60 components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab. Adding the CC60 system node 1. Select the new folder. 2. In the left-hand bar, select the Gas folder icon 3.
Configuring other control units The value to set in the Vitality Timer depends on the type of network. The following rule applies: – In Cerloop network, the MK7022 already handles the vitality check, and the DMS host does not receive the heartbeat messages. In this case, set the timer value = 0. – In NK8000 and CDI-Net networks, if the connection also includes the MK7022 Cerloop interface, leave the value = 0.
Configuring other control units Fig. 179 Adding VD60 Displays to a CC60 Fig. 180 Adding Output boards to a CC60 Fig. 181 Adding Outputs to an Output board in a CC60 200 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring other control units Fig. 182 Adding Gas elements to a VD60 in a CC60 Fig. 183 Adding Gas zones to a Gas sector in a CC60 Linking the gas elements to the gas zones 1. Expand the physical tree nodes until you reach the gas elements. 2. Expand the logical tree nodes until you reach the gas zones. 3. Drag and drop a gas element to the corresponding zone (see Fig. 184). Fig.
Configuring other control units 1. Locate the network node. Expand the network folders until you reach the node that represents the network that is physically connected to the CC60 (Cerloop, CDI-Net, or NK8000). 2. Select the CC60 node. 3. Drag and drop the CC60 node to the network node (see Fig. 185). Note: The valid link position for Cerloop is always the same main node, representing the entire loop. The valid link positions on CDI-Net/NK8000 gateways are distributed along the subsystem lines.
Configuring other control units 6.
Configuring other control units DMS7000 systems can provide a metafile describing the general tree structure that can be imported in Composer for DMS8000. Please refer to DMS8000 product ICC manual. 6.2.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The unit local address (111, 112, etc.). For MM7033 units, the number of installed MUX or DMX cards.
Configuring other control units CONFIGURING A DMS7000 UNIT 1. Add the folder(s) required for identifying the location of the DMS7000 unit in the project structure tree p. 206 2. Add the unit node to the new folder p. 206 3. Set the unit Local Address and Vitality Timer p. 206 4. Define the configuration (E2A032 Demultiplex or E2A041 Multiplex modules): p. 207 - MUX_MM_IE4 (48 digital inputs each) - DMX_MM_OE1 (48 digital outputs each) - MUX_MM_IE2 (24 monitored inputs each) 5.
Configuring other control units 6.2.2 Configuration procedures The following are the configuration procedures for the DMS7000 unit: Adding the folder for the DMS7000 units 1. Open the Composer project. 2. Create a folder for the DMS7000 components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab. Adding the DMS7000 node 1. Select the new folder. 2. In the left-hand bar, select the Building Services folder icon 3.
Configuring other control units The value to set in the Vitality Timer depends on the type of network. The following rule applies: – In Cerloop network, the MK7022 already handles the vitality check, and the DMS host does not receive the heartbeat messages. In this case, set the timer value = 0. – In NK8000 and CDI-Net networks, if the connection also includes the MK7022 Cerloop interface, leave the value = 0.
Configuring other control units Fig. 188 MUX_MM_IE4, 48 digital inputs (E2A041MUX card) Fig. 189 DMX_MM_OE1, 48 digital outputs (E2A032 DMX card) 208 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring other control units Fig.
Configuring other control units Note: The valid link position for Cerloop is always the same main node, representing the entire loop. The valid link positions on CDI-Net/NK8000 gateways are distributed along the subsystem lines. Composer helps you in recognising a valid link by showing a shortcut Link icon instead of the circle No-link icon . Fig.
Configuring other control units 6.3 Configuring a CF9000/DF8000 The DF8000/CF9000 is a family of input/output (I/O) modules that can provide distributed digital I/O over a RS485 line.
Configuring other control units 6.3.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceeding to the configuration checklist that follows. ITEMS NEEDED FOR CONFIGURATION The number of DF8000/CF9000 RS485 lines. The number and the model of DF8003/CF9003 CPU units for each line. The local address (0 to 15) for each unit. The module configuration for each unit, which can be provided in two ways: – The LMSmodular databases DB_PUL.DBF and DB_SUB.
Configuring other control units CONFIGURING A DF8000/CF9000 1. Add the folder(s) required for identifying the location of the DF8000/CF9000 in the project structure tree p.214 2. Add the DF8000/CF9000 system node to the new folder p.214 3. Add the DF8003/CF9003 unit node in the subsystem p.214 4. Set the DF8003/CF9003 Local Address p.215 5a. Import the LMS database, if available -- or -5b. Proceed with defining the DF8003/CF9003 detailed configuration p.215 p.215 6.
Configuring other control units 6.3.2 Configuration procedures The following are the configuration procedures for the CF9000: Adding the folder for DF8000/CF9000 1. Open the Composer project. 2. Create a folder for the I/O components. A new node is added to the project structure. 3. Select the new folder and name it in the Description field of the Node tab. Adding the DF8000/CF9000 system node 1. Select the new folder. 2. In the left-hand bar, select the Building Services folder icon 3.
Configuring other control units Fig. 193 Selecting the icon to add a CF9003 unit Setting the Local Address of the CPU unit 1. Select the DF8003/CF9003 node. 2. In the Node tab, set the Local Address. Note: The address value should range from 0 to 15 and it should match what is set in the hardware setting of the CPU module. Importing the LMSmodular configuration 1. Select the DF8003/CF9003 node. 2. Select Tools Æ Import in the Composer menu to start the import.
Configuring other control units Fig. 194 Adding I/O modules A Click this icon to add a DF9040 ON/OFF input modules B Click this icon to add a DF8045 supervised input module (NO) C Click this icon to add a DF9020 output modules D Click this icon to add a DF8046 supervised input module (NC) Linking the DF8000/CF9000 to the Communication network Link the DF8000/CF9000 node to the CDI-Net or NK8000: 1.
Configuring other control units Fig. 195 Linking a CF9000 to GW21 When the link is established, a new node appears on the structure tree, and its properties can be seen on the Node tab. 217 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Configuring other control units 6.4 Configuring a DESIGO PX The DESIGO PX automation system is used for control and monitoring of heating, ventilation, air-conditioning and other building services. The integration of DESIGO PX in DMS8000 is based on BACnet/IP. Note that LON-based PX units need an IP adapter in order to communicate to DMS8000.
Configuring other control units CONFIGURING A DESIGO PX 1. Add the BACnet driver p. 220 2. Add the folder(s) required for identifying the location of the DESIGO PX system in the project structure tree p. 220 3. Add the DESIGO PX node to the new folder p. 220 4. Set the DESIGO PX subscription p. 221 5. Import the DESIGO PX object file (EDE) p. 221 6. Link the DESIGO PX node to the BACnet driver p. 222 7. Customising the BACnet Notification Classes p. 222 8.
Configuring other control units 6.4.2 Configuration procedures The following are the initial configuration procedures for DESIGO PX system. Adding the NS8011 BACnet driver 1. Open the Composer Project. 2. If not already done, add the BACnet Driver (NS8011) in the path: Supervision System Setting Æ MM8000 System Æ Physical configuration Æ Station (e.g. My Station) Æ Channels collection 3. Click on the NS8011 driver icon in the icon toolbar (Fig. 196). The new driver node appears in the station folder.
Configuring other control units Setting the DESIGO PX BACnet Subscription 1. Select the DESIGO PX node. 2. If no DESIGO INSIGHT is present, then select the Perform BACnet subscription checkbox. Instead, If DESIGO INSIGHT is present, deselect the checkbox (Fig. 198). In the DESIGO INSIGHT settings, configure the DMS8000 as additional subscription host (you will need the Device ID that you can get in the Node tab of the NS8011 driver node). Fig.
Configuring other control units Fig. 199 Selecting the PX unit in the import list Linking the DESIGO PX to the Communication Network 1. Select the DESIGO PX node. 2. Expand the Management Station folder until you reach NS8011 node. -> Physical Configuration -> -> Channels Collection 3. Drag and drop the DESIGO PX node to the NS8011 BACnet driver (Fig. 200) Composer helps you in recognising a valid link by showing a shortcut Link icon instead of the circle No-link icon .
Configuring other control units 4. In the new row, click and select the Notification Class and the Event State, then click the associated DMS8000 property (CNAP Property). 5. The customised classes are listed in the configuration window. You can remove any of them by clicking on the corresponding row and then select Delete Row. Fig. 201 Customising BACnet Notification class 223 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Backing up your project 7 Backing up your project This section discusses why you should backup your project, and details how to do it. 7.1 Do I need to backup? When you leave the Composer environment, your project is saved on your hard disk in the folder (or working area) you specified and/or named when you created or restored the project. You can re-open it in this working area later.
Backing up your project Fig. 202 Starting the Project Backup Fig. 203 Backing up a project When the backup procedure is completed successfully, a message is displayed. Warning: Backup (and Restore) functions can only work on local disks. Network disk units cannot be used. Warning: note that the Composer Backup does not include product-specific files linked to the configuration but external to the Composer, e.g. HTML pages providing event treatment instructions, address book databases.
Appendix A – Network connectivity options KEY: Subsystems Connection Network Direct RS232 Cerloop Direct LAN Direct LAN Upstream interface device Upstream data-link protocol Downstream network Downstream interface device FS20 Sinteso / FS720 Cerberus PRO CS11 AlgoRex EP5 & EP7 FC700A CS1115 / FC330A CZ10, CC60 XLS STT11 STT20 / STT2410 SIGMASYS/D100 (field test only) SPC6000 Intrunet CS440 CZ12 / CS4 CS6 Guarto (via LON interface) SI410 / 420 / Plus Intrunet Propriet.
This page intentionally left blank 227 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Appendix B – Figure list The following is a list of images contained in this guide, and their corresponding page numbers. Fig. 1 Composer Plug-ins (Subsystem Tools or ST) installer p. 13 Fig. 2 PAK Manager p. 14 Fig. 3 Composer license p. 15 Fig. 4 Viewing / modifying PAK p. 15 Fig. 5 Importing PAK p. 16 Fig. 6 Showing the required license p. 17 Fig. 7 Starting Composer: Project Management window p. 18 Fig. 8 Naming the new project p. 18 Fig. 9 Adding a folder to the project (A) p.
Fig. 36 Example of NK8225 IP connectivity to DMS8000 p. 48 Fig. 37 Configuring the parameters for NS8210 Driver p. 51 Fig. 38 Configuring the parameters for NS8011 Driver p. 52 Fig. 39 Selecting the icon to add an NK82xx node p. 53 Fig. 40 Configuring IP parameters for a network with NAT gateway p. 54 Fig. 41 Configuring NK82xx Ethernet and CEI-79 parameters p. 55 Fig. 42 Linking the NK82xx Ethernet line to the NS8210 driver p. 55 Fig.
Fig. 76 Adjusting CDI-Net network settings p. 80 Fig. 77 Adjusting NK8000 network settings p. 81 Fig. 78 Standalone FS20/FS720 system p. 82 Fig. 79 FS20/FS720 Ethernet architecture p. 82 Fig. 80 FS20/FS720 SAFEDLINK architecture p. 83 Fig. 81 FS20/FS720 Mixed Ethernet and SAFEDLINK architecture p. 83 Fig. 82 Setting the Driver BACnet parameters p. 86 Fig. 83 Adding a new FS20/FS720 node p. 87 Fig. 84 Selecting FC20 subsystems to import p. 87 Fig.
Fig. 116 Setting FC700A Local Address and Vitality Timer p. 116 Fig. 117 Starting FC700A import p. 116 Fig. 118 Selecting the metafile to import p. 117 Fig. 119 Setting FG700A Local Address and Vitality Timer p. 118 Fig. 120 Linking FG700A to the DMS8000 station (direct link) p. 119 Fig. 121 Linking FG700A to a NK8000 network (NK8223, COM1) p. 119 Fig. 122 New link to FG700A in the NK8000 network p. 119 Fig. 123 Select the icon to add an FC330A system p. 122 Fig. 124 Choose FC330A system p.
Fig. 156 STT2410 ‘Line’ command icon p. 159 Fig. 157 STT2410 Input/Output command icon p. 160 Fig. 158 Connecting the STT2410 node to the Cerloop network p. 160 Fig. 159 SI410 configuration for network connectivity p. 165 Fig. 160 Sintony Uploader: selecting the connection type p. 168 Fig. 161 Sintony Uploader: Auto-detecting the COM port p. 168 Fig. 162 Sintony Uploader: Uploading the configuration p. 168 Fig. 163 Sintony Uploader: Saving the configuration p. 169 Fig.
Fig. 197 Adding DESIGO PX node p. 220 Fig. 198 BACnet subscription: deselect if DESIGO INSIGHT is present p. 221 Fig. 199 Selecting the PX unit in the import list p. 222 Fig. 200 Linking DESIGO PX to the BACnet driver p. 222 Fig. 201 Customising BACnet Notification class p. 223 Fig. 202 Starting the Project Backup p. 225 Fig. 203 Backing up a project p. 225 233 Building Technologies Fire Safety & Security Products DMS8000 Network, Fire, and Intrusion Connectivity Configuration Guide 06.
Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel +41 41 724 24 24 Fax +41 41 724 35 22 www.sbt.siemens.com Document no. A6V10062425_a_en Edition 06.