System limits
14
Building Technologies 007798_g_en NK8000 ICC.doc
Fire Safety & Security Products 06.2006
Fig. 7 MM8000 multiple host station configuration in combination with MK8000
Fig. 8 DESIGO INSIGHT multiple host station configuration
Note: CS11 connectivity direct or via Cerloop.
NK8000 networks support multiple host configurations with up to 4 hosts
(MM8000 / MK8000 / DESIGO INSIGHT).
Note: An additional connection over a serial line (CMSDL) is also supported,
however this option will limit the CMSDL/IP links to 3 instead of 4.
Encryption is not available in these configurations.