MM8000 MP4.
Installation Requirement Checklist Administrator account name and password Network names (or IP address) of all the PCs to install The hardware key (dongle) A license PAK Installation CD and Service releases / Hot fixes Localization ZIP file If SiPass is required on the same server, SiPass server software must be installed before MM8000 If required, video application software (e.g.
Stations A Stand-alone station is provided in the default project and it can also be used as Main Station for Client/Server architectures. As first configuration step, set the Station Name of the Main Station.
Network and Control Units Starting from the main project node, add folder nodes to set up the node structure that reflects the structure of the site. Define the communication the network: – Add and configure the required drivers in the Channels Collection – If required, add and configure the network units in a dedicated folder. Various parameters may also be required depending on the type of control units.
Security Configure who has what event treatment capabilities, and who can see and/or send commands.
Operating procedures Configure an operating procedure when assisted event treatment is needed. Notes: – Select Guided treatment when the operator needs to perform a series of steps. – Select Free treatment to provide the operator with a set of tools to treat the event. (See C in Fig. 6.) Fig. 1 Define the operating procedure parameters in the Node tab A B C Procedure step icons Treatment mode setting Auto-assignment parameters 1.
Geographical tree organization The geographical tree represents a facility or structure the way the operator knows it – the way it exists physically. The operator can easily navigate to a specific location by selecting the appropriate node in the tree, and then proceed to perform commands on a detector or group of detectors. Build top-down, starting with the largest item at the site (i.e. campus or building).
CCTV – Video Integration Add the Video Network Manager (VNM) driver to your project for advanced video functionalities. Note: Ensure you have all Composer plug-ins installed before proceeding. For details, see DMS8000 Network, Fire & Intrusion Connectivity Guide (A6V10062425) 1. Select Supervisor System settings MM8000 System Physical Configuration . 2. Select the VNM icon to add the Video Network Manager node. Note: The SIMATRIX subsystem may also be configured without the VNM.
Access control Configure access control for functions related to door command and event management. Note: Ensure you have all Composer plug-ins installed before proceeding. SiPass: 1. Select the Station name node: Supervisor System Settings MM8000 System Physical configuration 2. Select the SiPass driver icon to add a SiPass driver. 3. Add one or more folders to organise the access control (optional), and then select the icon to add a SiPass subsystem. 4.
Reactions and sequences Configure a reaction when you want an automatic response to a change of state. A reaction is composed of one or more triggers (inputs) and effects (outputs). A reaction can also be manually triggered. Configure a sequence when you want MM8000 to execute a set of functions that you define in a macro program. A manual command, a time-driven program (Time program), or a reaction can initiate a sequence. Sequences can also call other sequences.