MM8000 MP4.81-01 Management Station Release Notes A6V10062509_a_en 30.11.
Table of Contents 1 Introduction......................................................................................................... 5 2 What's new .......................................................................................................... 6 2.1 New Features ....................................................................................................... 6 2.1.1 Software License ................................................................................ 10 2.1.
.4.7 Video ................................................................................................... 42 4.4.8 OPC UA MK8000 Server .................................................................... 45 4.4.9 Printing issues ..................................................................................... 45 4.4.10 NK8000 Network ................................................................................. 46 5 Documentation .......................................................
Introduction 1 1 Introduction The new DMS8000 MP4.80-01 service release is available for MM8000 systems. This document is an update of the original MP4.81 Release Notes and provides a few corrections to the previous edition as well as additional information, including latest connectivity information and known issues. We recommend reading this document carefully before installing and using the software. 5 Building Technologies CPS Fire Safety A6V10062509_a_en 30.11.
2 What's new New Features 2 What's new This section presents the enhancements provided in this new release. 2.1 MP4.81.-01, Nov 2017 New Features The MM8000 MP4.80-01 is a service release including the following defect corrections. Graphics BTQ00279482 - Occasional selection issues in runtime maps Video BTQ00284038 - VideoNetworkManager server crash in MK8000 installation BTQ00276491 - Multiscan++ Firmware v1.
What's new New Features 2 Firewall BTQ00298646 - Missing firewall rule in configuration vbs SPC BTQ00281982 - SPC Integration, hotfix #32 for MM8000 V4.70,4.80,4.
2 What's new New Features NK8000 Vulnerability The NK823x Kernel has been updated to remove multiple vulnerabilities in the Open Source Software (OSS) components PHP, OpenSSL, NTP, Dropbear, and Net-SNMP, including the following versions of OSS components: OSS Component Version PHP V5.6.31 OpenSSL V1.0.2l NTP V4.2.8p10 Dropbear 2017.75 Net-SNMP The component has been disabled due to no known workarounds or upgrades available.
What's new New Features April 2017 Update Sep 2016 Release 2 Sinteso / Cerberus Pro [➙ 15] - Support for Sinteso MP3.0 SR7 and Cerberus PRO IP3 SR7 - Support for Sinteso MP5.2 SR3 and Cerberus PRO IP5 SR3 MM8000 MK8000 Video [➙ 19] - Support for Vectis iX V2.12 MM8000 SiPass [➙ 18] - Errors in the compatibility table have been corrected MM8000 MK8000 Group Description System OS compatibility [➙ 12] - Windows 10 (Professional, Enterprise) New in MP4.81 - Windows 8.
2 What's new AutoCAD® compatibility 2.1.1 Software License An MP4.80 License is required. 2.1.2 Localisation The same MP4.81 localisation toolkit can be used for MM8000 MP4.81 and MP8101. We recommend installing the localised MM8000 texts before starting any project configuration. In fact, a large number of localised texts are instantiated when you create a new Composer project.
What's new Summary of Add-on modules 2 Peripheral equipment and services Equipment Documentation SMS service over GSM: – Siemens Modem M20 – Siemens Modem MC35 – CINTERION Modem MC52i – Gemalto Modem BGS2T MM8000 Installation, Configuration & Commissioning: A6V10062413 E-mail/SMS service over e-mail: – POP3 service provider MM8000 Installation, Configuration & Commissioning: A6V10062413 Paging system: – ESPA 4.4.4 system NOTE: ASCOM, Novalink, and Telepage systems have been tested 2.
2 What's new Operating system compatibility summary 2.5 New in MP4.81-01, Nov 2017 Operating system compatibility summary The following table shows the compatibility MM8000 and MS Windows versions: NOTES: (1) Out of Software Maintenance (2) Client Stations only 12 Building Technologies CPS Fire Safety A6V10062509_a_en 30.11.
What's new Subsystem compatibility summary 2.6 2 Subsystem compatibility summary Control unit Compatibility Connectivity Documentation FS20 Sinteso™ FS720 Cerberus® PRO See the Sinteso/CerberusPro section [➙ 15] LAN. NK8000 Fire Connectivity Guide: A6V10359481 CS11 AlgoRex® EP5 CS11 AlgoRex® EP7 FC700A EP7F Z1, Z2, Z3, Z4, Z5 LAN. NK8000 Fire Connectivity Guide: A6V10359481 CS1115 Phase 4 FC330A Phase 4 CISxx8.
2 What's new Subsystem compatibility summary Control unit Compatibility Philips/Burle CCTV (LTC 8x00) Connectivity Documentation NK8000 (not tested with new NK823x) Video Connectivity Guide: A6V10062457 BOSCH Divar 700 and Divar XF DVRs, VIP X1 XF and VIP X1600 XF encoders, VIP XD decoders. NDC-455 FlexiDome, NDC455-P IVA FlexiDome, and VG4 AutoDome IP cameras. Video SDK 5.11.
What's new Subsystem compatibility summary 2.6.1 Modified in MP4.81-01, Nov 2017 2 Sinteso / Cerberus Pro The following table shows the compatibility between MM8000 and Sinteso / Cerberus Pro versions: NOTES: (1) DMS8000 MP4.50-01 Hotfix #45 is required for compatibility with SintesoWorks MP5.2/Cerberus Engineering Tool IP5.2. (2) With DMS8000 MP4.60, the service Release MP4.60-01 or higher is required for compatibility with SintesoWorks MP5.2/Cerberus Engineering Tool IP5.2. (3) Reimporting of 5.
2 What's new Subsystem compatibility summary 2.6.2 New in MP4.81-01, Nov 2017 XLS FireFinder The following table shows the compatibility between MM8000 and XLS FireFinder versions: 16 Building Technologies CPS Fire Safety A6V10062509_a_en 30.11.
What's new Subsystem compatibility summary 2.6.3 Modified in MP4.81-01, Nov 2017 2 SPC The following table shows the compatibility between MM8000 and SPC versions: NOTES: (1) Where x =4 or 5 (2) Where x=1 or 4 or 5 (3) Support of SPC Intrusion Units via EDP Protocol on UDP, glass break zone not supported (4) Support of SPC Intrusion Units via EDP protocol on UDP/IP and TCP/IP connections (5) Support of SPC Intrusion unit via FlexC protocol on TCP/IP connection 2.6.4 New in MP4.
2 What's new Subsystem compatibility summary 2.6.5 Modified in MP4.81-01, Nov 2017 SiPass The following table shows the compatibility with SiPass versions: NOTES: SiPass Integrated is supported as specified in the table above, with the exclusion of the Granta Controllers, which are not supported.
What's new Subsystem compatibility summary 2.6.6 Modified in MP4.81-01, Nov 2017 2 Video The following table shows the compatibility between MM8000 and video devices. NOTES: (1) Use RAS software V3.6 (2) Use RAS V3.6 and add Admin user on the SISTORE AX device (3) Use RAS V4 (4) Use RAS V4.2 (5) On Windows 10, ONLY use RAS V4.2 (6) On Windows 8.1, use RemoteView V2.90 SP2 M1; on Windows 10, use RemoteView V2.
2 What's new Subsystem compatibility summary 2.6.6.1 Video functionalities The following table shows how various features are supported on the video devices. Siemens SISTORE Siemens Vectis NICE / RIVER Bosch Generic Features AX CX/S X MX SDK 1.4 MX SDK 2.
MP4.81 Software installation Subsystem compatibility summary 3 3 MP4.81 Software installation The MM8000 MP4.81 software is distributed with a complete and assisted setup procedure. For detailed information about the installation procedure, refer to the MM8000 ICC manual (A6V10062413). Installation checklist All requirements and checklists are specified in the MM8000 ICC manual (A6V10062413). If all requirements are matched, the prerequisite software is available on the distribution DVD.
3 MP4.81 Software installation Updating to MP4.81-01 from MP4.81 – If you are not familiar with the setup procedure, refer to the installation section of the MM8000 ICC manual (A6V10062413) for detailed installation instructions. 4. If necessary, install the required Add-on modules. 5. Install the hardware key and enter the license code using the PAK Manager tool. Note that SiPass also requires a license option (Management Station Integration). Notes - Software License: MP4.80 licenses are required.
MP4.81 Software installation Updating to MP4.81 from earlier releases 3 Note that license information is not removed from the registry when you uninstall the software. Localisation Referring to the localised versions, be informed that the language file (ZIP) must be updated using the MP4.81 localization toolkit, which is new in comparison with all the previous versions. See MM8000 Localisation Engineering Guide (A6V10062459) 3.2.1 Updating from MP2.xx and MP3.
3 MP4.81 Software installation Updating to MP4.81 from earlier releases 9. If SiPass is used, align the access control configuration. Different procedures are required depending on the database versions: – [MM8000 Database 3.15-01 and earlier only] The SiPass node in the Composer tree must be deleted and then created again (note that the deletion will force you to reconfigure the access control points in maps, reactions, sequences, etc.). – [MM8000 Database 3.
Known issues Installation issues 4 4 Known issues This section presents a list of known limitations, problems, bugs, and recommended practices at the time the software was released. Compared with previous Release Notes, new and updated points are marked by a side label for easier identification. 4.1 4.1.
4 Known issues Installation issues New in MP4.81 Installation difficulties: Some problems have been reported in installing the software (specifically the Visual C++ Redistributable Package prerequisite) just after the creation of a new virtual machine. Note that some problems may be resolved with a simple reboot. Before installing, we recommend to reboot at least once any new virtual machine. The use of virtual machines may impose severe limitations to live video functionalities.
Known issues Installation issues 4 then selecting Merge. Note that this technique is not recommended and it will not work on 64-bit Windows platforms. Instead, use the PAK Manager Import command as documented in the installation and configuration guides. Demo mode stops after 2 hours Note that systems starting in demo mode will stop operating after 2 hours, even if a valid license is installed during demo operations. To enable the licensed mode, always restart the server after installing the license.
4 Known issues Upgrade and migration issues Localised Composer applied to multiple database versions The translation kit includes the Composer tool models that contain translated default point texts for the Composer configuration. When a new subsystem is created in Composer, the initial point list includes the translated texts.
Known issues Configuration issues 4 STT20: upgrading from MP3.15 STT20 metafile needs to be re-imported after restoring an MP3.15 projects. Otherwise, the download may fail. 4.3 4.3.1 Configuration issues Composer and Tools Issues Composer runs very slowly after installations on Windows 7 Composer response can be quite slow when it is used just after a new Windows 7 installation immediately followed by the DMS8000 software installation. Restarting the PC can solve this difficulty.
4 Known issues Configuration issues Performance issues with Composer via Remote Desktop When using Composer via Remote Desktop, you may experience a slow response, for example in general screen refresh and in setting/resetting the default of a large set of parameters.
Known issues Configuration issues New in MP4.81 4 two separate depths, the system creates multiple calculated pages to ensure the navigation in all cases. The side effect is that you will also get multiple links supporting a horizontal navigation. Unlike the AutoCAD 2010 library, MM8000 does not support "OLE objects with empty data". This incompatibility can cause issues in the maps visualization and preview. In case of problems, please contact the customer support [➙ 51] to correct the map.
4 Known issues Configuration issues SI410 Sintony Uploader SI410 provides one TCP port for external hosts to connect over TCP/IP network (Sintony IP Port 2 field in the Sylcom Tool / System configuration). In connecting to SI410 in IP mode, the Sintony Uploader makes use of this port as does the NS8014 DMS8000 driver for the runtime connection. This implies that you need to stop the DMS8000 server software before being able to use the Sintony Uploader that applies this type of connection.
Known issues Configuration issues 4.3.6 4 System limitations Limitations in the number of commands from scheduled and manual tasks Tasks defined in the MM8000 scheduler should not include more than 255 commands. Large tasks including such a high number of commands should be split into smaller tasks. SMS in Unicode-PDU mode When text messages (SMS) are sent in Unicode-PDU mode, the phone numbers must be inserted in the DMS8000 Contacts with the international prefix, for example +393481234567 4.3.
4 Known issues Runtime issues 4.4 4.4.1 Runtime issues Critical software issues Restart/shutdown errors (ES server crash) on virtual machines When running on virtual machines, the ES server may crash while Windows starts up or closes down. These errors may result in some data not being properly saved (especially in the history archive). To solve the problem, please follow the instructions below: 1. Create a file named MM8000Shutdown.cmd that contains the text "C:\Program Files\DMS8000\Utilities\Bat\STOP_
Known issues Runtime issues 4 Low virtual memory events Depending on the specific configuration and on the PC hardware characteristics, MM8000 software may use up the memory resources in Windows and cause the Low virtual memory error message to display. Should that occur, you can adjust the virtual memory size (i.e., the size of the paging file where Windows swaps the active memory areas on disk). Using the Administrator login, proceed as follows: 1.
4 Known issues Runtime issues In such a case, note that the Back button command works in the Main View and does not select again the Preferred View. To avoid this effect, make sure to include all linked pages in the Preferred View. Reoccurring event: date and time is not refreshed in assisted treatment In case of a reoccurring event, the date & time is properly updated in the event list.
Known issues Runtime issues 4 until the printer will be reconnected. Problem is present from MP3.20 and later version. Slow login Logging on in may be slow (about 30 sec) when using MM8000 in closed mode. Audio recordings in history records of dialler operating procedure steps In Windows 8.1 systems (32 bit), you cannot open the history audio attachments of operating procedure steps. The problem is related to the default Windows 8.1 app, which does not allow administrator users to open wave files.
4 Known issues Runtime issues accessing MM8000 Web Server and Web Services. To resolve this problem, do the following: 1. Start Internet Explorer 2. Select Tools > Internet Options 3. Click the Security tab 4. Uncheck the Enable Protected Mode check-box Web connection failure after MM8000 server restart on Windows Server 2008/2012 Web connections may fail after MM8000 server restart on Windows Server 2008 R2 and Windows Server 2012 R2. If this occurs, apply the following procedure: 1.
Known issues Runtime issues 4 cases, we recommend setting the History node of the Station ‘out of scan’ in the MM8000 Physical Structure. Restoring history archives: SQL version compatibility MM8000 history archive can work with various SQL Server versions (the exact compatibility is given in the MM8000 ICC manual (A6V10062413) . However, note that not all combinations of versions are supported as far as the history archive backup and restore are concerned.
4 Known issues Runtime issues – Updated in MP4.81 The following SPC events are not supported: - Area Early/Late Set/Unset (solved in SPC V3.4 and higher) - Card format invalid - Card is void - Unknown card - Incorrect site code - Clock and data reversed – SPC VdS compliant configurations are not supported by DMS8000. The grade setting VdS-A and VdS- C do not work. Unrestricted has to be selected as Standards Compliance setting of the SPC panel which allows to configure UDP communication.
Known issues Runtime issues 4 FC2080 Line detection controller events missing after restarting Upon a panel restart, the following FC2080 Line detection controller events are missing: New device found and Unconfigured devices. FS20: excluding loop sounder zones from MM8000 stations Be aware that, in MM8000, you can exclude the loop sounder zones using the appropriate command, while the FS20 panel may not show the excluded zone as the exclusion command is configurable directly on the panel.
4 Known issues Runtime issues In SiPass V2.40 until V2.65, note that the SiPassUser password, required for MM8000 communication, must be in uppercase: SIPASSPASSWORD. New in MP4.81 From SiPass V2.
Known issues Runtime issues New in MP4.81 4 When using SISTORE AX video player RAS V3.6 with a new MM8000/Windows user, you need to start the player as stand-alone application first. This will set the software environment and let the player work properly which is then used in MM8000. On Windows 10, use RAS version 4.2.5. Vectis HX HVR The same limitations of the AX RAS viewer also apply to Vectis HX HVR.
4 Known issues Runtime issues category to None for the Sabotage Exclusion property of the Video Out of the camera. SISTORE MX V2.90 SP2 New in MP4.81 SISTORE MX RemoteView V2.90 SP2 cannot display both Live Video and Playback Recording on Windows 8.1 PCs (Professional and Enterprise editions). On Windows 8.1, use SISTORE MX RemoteView V2.90 SP2 M1. On Windows 10, use SISTORE MX RemoteView V290 SP2 M2.
Known issues Runtime issues 4 Bosch support recommends installing Bosch software and Video SDK runtime package (used by MM8000) on a different machine. Divar DVRs: – In case of a Divar IP camera fault, a no "Camera Signal Loss" message is provided in the live video screen. – No indication or progress bar is provided for the recording search in the play-back screen. – Camera to monitor switching is not supported on Divar DVRs, whereas it can be used between Encoders/IP cameras and Decoders.
4 Known issues Runtime issues 4.4.10 NK8000 Network This is a list of known problems and limitations present in the current version. USB memory devices on NK823x Removing the USB key while the logging is enabled (without using the safely remove command) may cause the NK823x to restart or block (a manual restart is then needed). Always use the Safe Remove command before removing the USB memory device. Some specific USB memory models may not be compatible with NK823x. Note: File system: FAT32; 2-64 GB.
Known issues Runtime issues 4 Network-wide interactions involving NK823x that use different upstream protocols Note that network-wide interactions do not work properly across NK823x units that use two different upstream protocols (e.g. one is using CMSDL/IP and the other BACnet/IP). Fault events on unconnected Ethernet lines On existing NK823x Ethernet nodes with no configured connection, faults events are reported, thus indicating the missing network link (no cable or no hub/switch).
5 Documentation Runtime issues 5 Documentation This section provides you with information about the product documentation. Documentation Updates in MP4.81-01 The following documents’ have been updated in MP.81-01 Sales support: 049_DMS_DMS8000_Application_Specification_Planning_MP4.8101_A6V10063710_a_en 023_DMS_MM8000_Datasheet_MP4.81-01_A6V10062415_a_en 023_DMS_NK8231_Datasheet_MP4.81-01_A6V10238662_a_en 023_DMS_NK8232_Datasheet_MP4.81-01_A6V10238667_a_en 023_DMS_NK8235_Datasheet_MP4.
Documentation DMS8000 Documentation Resource Information & Glossary 5 4. In the list, select one or more documents and click the Download Assets icon. 5. After the download preparation completes (Background Process …), click Download and follow the instructions of your browser. For more information such as Siemens news and announcements, visit the STEP Web portal at: https://workspace.sbt.siemens.com/content/00001123/default.aspx 5.
5 Documentation MM8000 Technical documentation 5.3 MM8000 Technical documentation MM8000 Operation Manual (A6V10062409) This manual is an operation guide, meant for end-users. MM8000 Installation, Configuration and Commissioning (ICC, A6V10062413) The ICC guide provides step-by-step procedures for installation and configuration of the MM8000. During configuration, this manual should be used in tandem with the DMS8000 Connectivity Configuration guides.
Customer support links & resources Siemens BT CPS DMS 6 6 Customer support links & resources In this section you can find to references to support. 6.1 Siemens BT CPS DMS Our Customer Support Centre intranet site at: http://intranet.siemens.com/bt/csc-fs provides useful information and links. In the Online Support section of this intranet page, software downloads and known product issues can be found in the PSP (password-protected Product Support Platform). The support mailbox is: fs.support.
Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID A6V10062509_a_en Edition 30.11.2017 © Siemens Switzerland Ltd, 2017 Technical specifications and availability subject to change without notice.