Product Brochure

Product Specification Sheet HD60.13
Answers for industry.
Heavy Duty Double Throw
Safety Switch
Type VBII, 60 Amp, Type 1 (Indoor)
Standards and Ratings
UL Listed under file #E4776
Meets UL98 for switches and UL 50
for enclosures
Meets NEMA Standard KS-1 for
enclosed switches
Meets NEC wire bending space
requirements
Suitable for use as service
equipment
• Rated 10,000 AIC with Class H or
200,000 AIC when used with or
protected by Class R or J fuses (fuse
ampere rating must not exceed
switch ampere rating)
Features
Quick-make and break switching
action
Double break visible blade design
Highly visible ON/OFF indication
Modular design allows quick and
easy replacement of parts
Front removable lugs which can
easily be converted to copper body
or compression type lugs
Defeatable dual cover interlock
All copper current carrying parts
4
Tangential knockouts
Handle is padlockable in OFF position
Catalog Number Description
Catalog Max Shipping
Number AC Volts Description Weight (lbs.)
DTF322
1
240 Fusible, 3 Pole, 3 Wire 43
DTF362
1
600 Fusible, 3 Pole, 3 Wire 43
DTNF222 240 Non-fusible, 2 Pole, 2 Wire 35
DTNF322 240 Non-fusible, 3 Pole, 3 Wire 36
DTNF362 600 Non-fusible, 3 Pole, 3 Wire 36
Catalog
240V 1Ø 240V 3Ø 480V 3Ø 600V 3Ø 250V DC
Number Std Max Std Max Std Max Std Max Std Max
DTF322 3 10 7¹⁄₂ 15 — 10 —
DTF362 3 10 7¹⁄₂ 15 15 30 15 50 10
DTNF222 10 20 10
DTNF322 10 — 20 — — — — 10
DTNF362 10 — 20 50 60 — 10
General Information
Horsepower Ratings
2
HA161234 Auxiliary Switch (1-NO & 1 NC)
3
HA261234 Auxiliary Switch (2-NO & 2 NC)
3
HA361234 Low Voltage Auxiliary Switch
3
HG61234 Equipment Ground Lug Kit (two lugs provided)
HG261234 Isolated Equipment Ground Lug Kit
HP62 Fuse Puller (3 per kit, (2) kits required per switch)
HN263 Neutral Kit
HR612 240 Volt Class R Fuse Clip Kit (3 fuse clips per kit,
(2) kits required per switch)
HR62 600 Volt Class R Fuse Clip Kit (3 fuse clips per kit,
(2) kits required per switch)
HLC612 Copper Lug Kit (9 lugs per kit)
3
HCL623 Compression Lug Neutral Barrier Kit
1
Fusible switches accept: Class H fuses as standard or Class R fuses with kit. Catalog number DTF362 also
accepts Class J fuses (move load base).
2
Dual horse ratings: Std - applies when non-time delay fuses are installed. Max - applies when time-delay
fuses are installed.
3
(2) required per switch (one for each of the two line bases).
4
Lugs are aluminum alloy as standard. Optional copper body lugs are available.
Accessories