Data Sheet for Application
Application Sheet
CBP001/CBP001_H
Passive chilled beam (2 pipe) with hot water radiator on triac output
DXR2..09T-101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-08-16
A6V10662233_en--_c_--_08
• Heating with radiator/floor heating and cooling with passive chilled beam (2 pipe) on triac outputs
• Modulating control of heating and cooling valve
• Downdraft compensation
• Condensation monitoring
• Room temperature operation via KNX PL-Link room operator unit with temperature measurement
Plant diagram
DXR2…
Room automation station
R1
Room operator unit with
D1
Window contact
temperature sensor
D2
Presence detector
YC
Cooling valve
D3
Condensation monitor
YR
Radiator valve
R
Room
Function diagrams
Heating/cooling valves
C
Cooling sequence
TR
Room temperature
H
Heating sequence
Y
Output signal
SpC
Effective cooling setpoint
YC
Cooling valve
SpH
Effective heating setpoint
YH
Heating valve
SpC
0
100
Y [%]
TR [°C]
YH
SpH
YC
C
H